F041 on the Allen-Bradley PowerFlex 525 is the “Phase UV Short” fault. A fault stops the drive; it will not restart until the fault is cleared.
The drive detected a short between two output phases. It stops at once, because a phase-to-phase short drives current far beyond what the output stage can carry.
- Code
- F041
- Type
- Fault (stops the drive)
- Drive
- Allen-Bradley PowerFlex 525, PowerFlex 523
- Kind of fault
- Output short circuit
01 / Causes
What causes F041
Rockwell Automation's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing output short circuit faults explains where it usually comes from.
02 / Checks
What to check for F041
In the order Rockwell Automation gives them.
- 01Check the motor and the drive's output terminal wiring for a short.
- 02Replace the drive if the fault cannot be cleared.
03 / Clearing it
How to clear F041
- Rockwell's parameter A551 [Fault Clear] resets a fault when set to 1 (Reset Fault); setting it to 2 (Clear Buffer) also clears the fault queue.
- Correct the cause first: F033 means the drive has already used up its automatic restart attempts on a fault that is still there.
Clear it once. If F041 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How output short circuit faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Isolate and discharge, then disconnect the motor cable at the drive terminals.
- 02Measure phase to phase on the cable and on the motor separately, and insulation-test between phases.
- 03Inspect the motor terminal box for loose links, tracking or a burnt terminal board.
- 04Check that nothing between drive and motor (a contactor, isolator or junction box) has failed or been miswired.
05 / Repair
When F041 means a repair
If the cable and motor are clear and the fault stays with nothing connected to the output, the drive's output stage has failed.
If F041 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Allen-Bradley drives, and they arrive knowing what to look for.
06 / Other drives
Output short circuit: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F07807 Short-circuit detected |
| ABB ACS355 | F0004 SHORT CIRC |
| Delta C2000 | occ IGBT short circuit between upper bridge and lower bridge |
| Delta ASDA-B2 | AL083 Servo drive outputs excessive current |
| Schneider Electric Altivar ATV320 | HDF IGBT desaturation error · SCF1 Motor short circuit error · SCF5 Motor short circuit error |
| INVT Goodrive20 (GD20) | OUt1 Inverter unit U phase protection · OUt2 Inverter unit V phase protection · OUt3 Inverter unit W phase protection |
| Yaskawa V1000 | SC IGBT Short Circuit |
| Yaskawa A1000 | SC Output Short Circuit or IGBT Fault |
| Yaskawa GA500 | SC Short Circuit/IGBT Failure |
| Siemens MICROMASTER 430 | F0022 Hardware monitoring active |
| INVT Goodrive200A (GD200A) | OUt1 Inverter unit U-phase protection · OUt2 Inverter unit V-phase protection · OUt3 Inverter unit W-phase protection |
| Danfoss VLT Micro Drive FC 51 | Alarm 16 Short circuit |
07 / More codes
Other PowerFlex 525 codes
Source
Rockwell Automation, PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start, November 2017, 520-QS001B-EN-E, Fault Codes.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Allen-Bradley and is not its authorised service partner.