INVT AC drive (VFD) · fault code

Goodrive20 (GD20) PIDE: PID feedback offline fault

PIDE on the INVT Goodrive20 (GD20) is the “PID feedback offline fault” fault. A fault trips the drive and lights the TRIP indicator; the drive stays stopped until the fault is reset.

An analog input (usually a 4-20 mA speed reference or feedback) dropped out of its expected range, most often from a broken wire or a failed transmitter.

Code
PIDE
Type
Fault (stops the drive)
Drive
INVT Goodrive20 (GD20)
Kind of fault
Analog signal loss

01 / Causes

What causes PIDE

  • The PID feedback is offline.
  • The PID feedback source has disappeared.

02 / Checks

What to check for PIDE

In the order INVT gives them.

  1. 01Check the PID feedback signal.
  2. 02Check the PID feedback source.

Also in the manual

  • Over communication this fault reads as type 22.

03 / Clearing it

How to clear PIDE

  • Remove the cause, then reset with the keypad's STOP/RST key, through a digital input, or by switching the power off and on. Once the fault is cleared the motor can be restarted.
  • INVT's order of work: check the keypad is working; read the fault records in group P07 to see the drive's state when the fault happened; follow the table for that code; fix the cause; then reset and run.

Clear it once. If PIDE comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How analog signal loss faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Measure the signal at the drive terminals while the system runs.
  2. 02Check the wiring back to the source for breaks and loose terminals.
  3. 03Check the transmitter or the PLC's analog output that supplies the signal.

05 / Repair

When PIDE means a repair

If the signal is correct at the terminals, the drive's analog input may have failed.

If PIDE keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on INVT drives, and they arrive knowing what to look for.

06 / Other drives

Analog signal loss: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F80 Signal lost on analog input
Siemens SINAMICS G120F03505 Analog input, wire break
Siemens MICROMASTER 440F0080 ADC input signal lost
Allen-Bradley PowerFlex 525F029 Analog In Loss
ABB ACS355F0007 AI1 LOSS · F0008 AI2 LOSS · A2006 AI1 LOSS · A2007 AI2 LOSS
Delta VFD-EAErr ACI signal error
Delta C2000AFE PID loss ACI · ACE ACI loss
Schneider Electric Altivar ATV320LFF3 AI3 4-20mA loss error
Siemens MICROMASTER 420F0080 ADC input signal lost
Siemens MICROMASTER 430F0080 ADC input signal lost
INVT Goodrive200A (GD200A)PIDE PID feedback offline fault
Danfoss VLT Micro Drive FC 51Alarm 2 Live zero error

07 / More codes

Other Goodrive20 (GD20) codes

Source

INVT, Goodrive20 Series VFD Manual, Version V2.1 (2025), Chapter 6, Fault tracking (6.2.3 VFD faults and solutions).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

PIDE won't clear? Get a technician who knows the Goodrive20 (GD20).

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.