LF on the Yaskawa A1000 is the “Output Phase Loss” fault. A fault is detected for drive protection: it stops the drive and toggles the fault output on terminals MA-MB-MC. Remove the cause and clear the fault before running again.
The drive sees current in only two of the three motor phases. A phase is open somewhere between the drive and the motor winding.
- Code
- LF
- Type
- Fault (stops the drive)
- Drive
- Yaskawa A1000
- Kind of fault
- Output phase loss
01 / Causes
What causes LF
- A phase is lost on the output side (detection on with L8-07 = 1 or 2): a disconnected output cable, a damaged motor winding, a loose output terminal, a motor below 5% of the drive's rated current, a damaged output transistor, or a single-phase motor.
02 / Checks
What to check for LF
In the order Yaskawa gives them.
- 01Check the output cable and correct the wiring.
- 02Check the resistance between motor lines and replace the motor if the winding is damaged.
- 03Tighten the output terminals to the torque in the manual.
- 04Check the drive and motor capacities.
- 05The drive cannot run a single-phase motor.
03 / Clearing it
How to clear LF
- Remove the cause, then clear the fault manually before running again: the reset key on the digital operator, a multi-function input set to fault reset, or cycling the power.
- Some faults need a condition met first: oL1 cannot be reset until monitor U4-16 is below 100%. SC will not accept a reset at all, to protect the drive's internal circuits.
Clear it once. If LF comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How output phase loss faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Isolate and check continuity of each phase from the drive terminals to the motor terminals.
- 02Inspect any contactor, isolator or junction box in the motor circuit.
- 03Measure winding resistance phase to phase at the motor.
05 / Repair
When LF means a repair
When cable, connections and windings are all good, an output phase in the drive itself may be open.
If LF keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Output phase loss: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | A922 No load applied to inverter |
| Siemens SINAMICS G120 | F30015 Motor cable phase failure |
| Siemens SINAMICS V90 | F7410 Current controller output limited · F30015 Phase failure motor cable |
| Siemens MICROMASTER 440 | F0023 Output fault · F0422 No load applied to inverter · A0523 Output fault · A0922 No load at the inverter |
| Allen-Bradley PowerFlex 525 | F021 Output Ph Loss |
| ABB ACS355 | F0034 MOTOR PHASE |
| Delta C2000 | OPHL Output phase loss |
| Delta ASDA-B2 | AL031 Incorrect wiring of the motor power line U, V, W, GND |
| Schneider Electric Altivar ATV320 | OPF1 Single output phase loss error · OPF2 Output phase loss error |
| INVT Goodrive20 (GD20) | SPO Phase loss on output side |
| Yaskawa V1000 | LF Output Phase Loss · LF2 Output current imbalance |
| Yaskawa GA500 | LF Output Phase Loss · LF2 Output Current Imbalance |
| Siemens MICROMASTER 430 | F0023 Output fault · A0523 Output fault |
| INVT Goodrive200A (GD200A) | SPO Phase loss on output side |
| Mitsubishi Electric FR-D700 | E.LF Output phase loss |
| Danfoss VLT Micro Drive FC 51 | Alarm 30 Motor phase U missing · Alarm 31 Motor phase V missing · Alarm 32 Motor phase W missing |
07 / More codes
Other A1000 codes
Source
Yaskawa, YASKAWA AC Drive A1000 Quick Start Guide, 41G, TOEP C710616 41, 5.2 to 5.5: Fault Detection, Alarm Detection, Operator Programming Errors, Auto-Tuning Fault Detection.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007