dWF1 on the Yaskawa GA500 is the “EEPROM Memory DWEZ Data Error” fault. A fault shuts off the drive's output and the motor coasts to a stop (some faults let you choose the stopping method). ALM/ERR stays lit, a terminal set to H2-01 to H2-03 = E activates, and the drive will not run until the fault is reset.
The drive could not read or write its stored parameters, or found them invalid. The drive may start with wrong settings, or refuse to start.
- Code
- dWF1
- Type
- Fault (stops the drive)
- Drive
- Yaskawa GA500
- Kind of fault
- Parameter memory
01 / Causes
What causes dWF1
- An error in the EEPROM peripheral circuit, or in the DriveWorksEZ program data saved to EEPROM.
02 / Checks
What to check for dWF1
In the order Yaskawa gives them.
- 01Re-energize the drive; if the fault stays, replace the control board or the drive (contact Yaskawa about replacing the control board).
- 02Initialize the drive (A1-03 = 2220 or 3330) and upload the DriveWorksEZ project again.
03 / Clearing it
How to clear dWF1
- Remove the cause, then reset in one of three ways: the reset key on the keypad while the code is shown, a multi-function input set to H1-xx = 14 (terminal S4 by default), or switching off the main circuit power and switching it back on once the keypad display has gone out.
- A fault will not reset while a run command is active from the terminals or a communication option; the keypad shows CrST until the run command is removed.
- oL1 resets only once monitor U4-16 (Motor oL1 Level) is below 100.
Clear it once. If dWF1 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How parameter memory faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Power-cycle the drive and see whether the fault clears.
- 02If it returns, restore the parameters from a backup, or reset to factory settings and set the drive up again.
- 03Keep a parameter backup of every drive, so this never means guessing the settings.
05 / Repair
When dWF1 means a repair
A memory fault that survives a factory reset needs the control board repaired or replaced.
If dWF1 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Parameter memory: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F51 Parameter EEPROM fault · F61 SD card parameter cloning failed · F62 Parameter cloning contents invalid · F63 Parameter cloning contents incompatible · F64 Inverter attempted to do an automatic clone during startup · F395 Acceptance test/confirmation pending |
| Siemens SINAMICS G120 | F01040 Parameters must be saved · F01044 Error loading data from memory card · F01105 CU: Insufficient memory · F13100 Know-how protection: Copy protection error · F13101 Know-how protection: Copy protection cannot be activated · A01101 Memory card not available |
| Siemens SINAMICS V90 | A1019 Writing to the removable data medium unsuccessful · A1032 All parameters must be saved · A1045 Configuring data invalid · A52900 Failure during data copying |
| Siemens MICROMASTER 440 | F0051 Parameter EEPROM fault |
| Allen-Bradley PowerFlex 525 | F048 Params Defaulted · F100 Parameter Chksum · F101 External Storage |
| ABB ACS355 | A5010 Corrupted panel parameter backup file · A5018 Parameter default value is not found · A5025 Software is being uploaded or downloaded · A5029 Memory is not ready · A5040 Parameter download error: the selected set is not in the backup file · A5041 Parameter backup file does not fit into memory |
| Delta VFD-E | cF1.0 Power board CPU write failure · cF1.1 Control board CPU write failure · cF2.0 Power board CPU read failure · cF2.1 Control board CPU read failure |
| Delta C2000 | cF1 EEPROM write error · cF2 EEPROM read error |
| Delta ASDA-B2 | AL017 Abnormal EEPROM · AL099 DSP firmware upgrade |
| Hitachi WJ200 | E08 EEPROM error |
| Schneider Electric Altivar ATV320 | EEF1 EEprom control error · EEF2 EEprom power error |
| INVT Goodrive20 (GD20) | EEP EEPROM operation fault |
| Yaskawa V1000 | CPF06 EEPROM Data Error · Err EEPROM Write Error |
| Yaskawa A1000 | CPF06 EEPROM Memory Data Error · dWF1 EEPROM Memory DriveWorksEZ Data Error · Err EEPROM Write Error |
| Siemens MICROMASTER 420 | F0051 Parameter EEPROM fault |
| Siemens MICROMASTER 430 | F0051 Parameter EEPROM fault · F0053 I/O EEPROM fault |
| Siemens SINAMICS G110 | F0051 Parameter EEPROM fault · F0055 BOP-EEPROM fault |
| INVT Goodrive200A (GD200A) | EEP EEPROM operation fault |
| Mitsubishi Electric FR-D700 | E.PE Parameter storage device fault (control circuit board) |
| Danfoss VLT Micro Drive FC 51 | Error 86 Copy fail · Error 87 LCP data invalid · Error 88 LCP data not compatible |
07 / More codes
Other GA500 codes
Source
Yaskawa, GA500 Drive Technical Reference, C, SIEP C710617 52, 7 Troubleshooting (7.4 to 7.7, 7.9).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007