MachineryFix

Yaskawa AC drive (VFD) · fault code

GA500 End6: Leakage Inductance Alarm

End6 on the Yaskawa GA500 is the “Leakage Inductance Alarm” fault. A fault shuts off the drive's output and the motor coasts to a stop (some faults let you choose the stopping method). ALM/ERR stays lit, a terminal set to H2-01 to H2-03 = E activates, and the drive will not run until the fault is reset.

The drive's motor identification (autotune) run did not finish. The drive measures the motor to set up its control; it stopped because the motor was missing, the data entered was wrong, or a limit was reached.

Code
End6
Type
Fault (stops the drive)
Drive
Yaskawa GA500
Kind of fault
Motor identification

01 / Causes

What causes End6

  • The results were outside range, or A1-02 (control method) does not suit.

02 / Checks

What to check for End6

In the order Yaskawa gives them.

  1. 01Check A1-02.
  2. 02Check the nameplate data and tune again.

Also in the manual

  • An End code means Auto-Tuning completed with calculation errors. Fix the cause and tune again, or set the motor parameters by hand; if no cause can be found, Yaskawa says the drive can still be used.

03 / Clearing it

How to clear End6

  • Remove the cause, then reset in one of three ways: the reset key on the keypad while the code is shown, a multi-function input set to H1-xx = 14 (terminal S4 by default), or switching off the main circuit power and switching it back on once the keypad display has gone out.
  • A fault will not reset while a run command is active from the terminals or a communication option; the keypad shows CrST until the run command is removed.
  • oL1 resets only once monitor U4-16 (Motor oL1 Level) is below 100.

Clear it once. If End6 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How motor identification faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the motor is connected and the output contactor (if any) is closed during the run.
  2. 02Check the rating plate data entered in the drive and the motor connection (star or delta).
  3. 03Repeat the identification with the motor cold and uncoupled where possible.

05 / Repair

When End6 means a repair

Repeated failures on a correctly entered, healthy motor point at a winding fault or a drive measurement problem.

If End6 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Motor identification: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F41 Motor data identification failure
Siemens SINAMICS G120A07980 Rotary measurement activated · A07981 No enabling for rotary measurement · A07991 Motor identification activated
Siemens SINAMICS V90F7995 Motor identification failure · A7971 Angular commutation offset determination activated · A7991 Motor data identification activated
Siemens MICROMASTER 440F0041 Failure, motor data identification · F0042 Fault/error when optimizing the speed controller
Allen-Bradley PowerFlex 525F080 Autotune Failure
ABB ACS355F0011 ID RUN FAIL · A2019 ID RUN · A2025 FIRST START
Delta VFD-EAUE Auto tuning error
Delta C2000AUE Auto-tuning error · AUE1 Auto-tune error 1 · AUE2 Auto-tune error 2 · AUE3 Auto-tune error 3 · AUE4 Auto-tune error 4
Schneider Electric Altivar ATV320ASF Angle error · TNF Autotuning detected error
INVT Goodrive20 (GD20)tE Motor autotuning fault · STo Maladjustment fault
Yaskawa V1000Er-01 Motor Data Error · Er-02 Minor Fault · Er-03 STOP Button Input · Er-04 Line-to-Line Resistance Error · Er-05 No-Load Current Error · Er-08 Rated Slip Error
Yaskawa A1000dv7 Initial Polarity Estimation Timeout · End1 Excessive V/f Setting · End2 Motor Iron-Core Saturation Coefficient · End3 Rated Current Setting Alarm · End4 Adjusted Slip Calculation Error · End5 Resistance Tuning Error
Siemens MICROMASTER 420F0041 Failure, motor data identification · A0541 Motor data identification routine active
Siemens MICROMASTER 430F0041 Failure, motor data identification · A0541 Motor data identification routine active
INVT Goodrive200A (GD200A)tE Motor autotuning fault
Danfoss VLT Micro Drive FC 51Alarm 51 AMT check Unom and Inom · Alarm 52 AMT low Inom · Alarm 53 AMT motor too big · Alarm 54 AMT motor too small · Alarm 55 AMT parameter out of range

07 / More codes

Other GA500 codes

Source

Yaskawa, GA500 Drive Technical Reference, C, SIEP C710617 52, 7 Troubleshooting (7.4 to 7.7, 7.9).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

End6 won't clear? Get a technician who knows the GA500.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.