Yaskawa AC drive (VFD) · fault code

GA500 oPE03: Multi-Function Input Setting Err

oPE03 on the Yaskawa GA500 is the “Multi-Function Input Setting Err” fault. A fault shuts off the drive's output and the motor coasts to a stop (some faults let you choose the stopping method). ALM/ERR stays lit, a terminal set to H2-01 to H2-03 = E activates, and the drive will not run until the fault is reset.

A setting the drive cannot accept, or an operating state it is reporting. An alarm of this kind does not stop the motor on its own; a setup fault keeps the drive from running until the setting is corrected.

Code
oPE03
Type
Fault (stops the drive)
Drive
Yaskawa GA500
Kind of fault
Setup

01 / Causes

What causes oPE03

  • The multi-function input settings (H1-01 to H1-07, H7-01 to H7-04) conflict: functions overlap, a required pair is incomplete (Up/Down, Up 2/Down 2, 2-wire sequence 2), or incompatible functions are set together.
  • Fast Stop N.O. and N.C. are both set, or External Reference 1/2 selection conflicts with the pulse train, option card or analog input settings.

02 / Checks

What to check for oPE03

In the order Yaskawa gives them.

  1. 01Remove overlapping or unused input functions, and set required pairs together.
  2. 02Keep only one of Fast Stop N.O. (15) and N.C. (17).
  3. 03With H1-xx = 2: set H6-01 = 0 for pulse train reference, connect the option card for option reference, or set H3-02 or H3-10 = 0 for analog reference.
  4. 04Correct H2-xx = 38 (Drive Enabled) set with no input set to 6A (Drive Enable), H1-xx = 7E (Reverse Rotation Identifier) set without H6-01 = 3, and H1-xx = 75/76 set with H3-01 or H3-09 = 1.

Also in the manual

  • A parameter setting error gives no fault or alarm signal, but the drive will not run until the setting is corrected.

03 / Clearing it

How to clear oPE03

  • Remove the cause, then reset in one of three ways: the reset key on the keypad while the code is shown, a multi-function input set to H1-xx = 14 (terminal S4 by default), or switching off the main circuit power and switching it back on once the keypad display has gone out.
  • A fault will not reset while a run command is active from the terminals or a communication option; the keypad shows CrST until the run command is removed.
  • oL1 resets only once monitor U4-16 (Motor oL1 Level) is below 100.

Clear it once. If oPE03 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How setup faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the parameters the manual names for this code.

05 / Repair

When oPE03 means a repair

No repair: a setting to correct.

If oPE03 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Setup: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20A541 Motor data identification active · A921 Analog output parameters not set properly · A923 Both JOG left and JOG right are requested · A936 PID autotuning active
Siemens SINAMICS G120F01033 Switching over units: Reference parameter value invalid · F01034 Switching over units: Calculation of the parameter values after reference value change unsuccessful · F01122 Frequency at the probe input too high · F01512 An attempt has been made to establish a conversion factor for scaling which does not exist · F06310 Supply voltage (p0210) incorrectly set · F07086 Switching over units: Parameter limit violation
Siemens SINAMICS V90F7085 Open-loop/closed-loop control parameters changed · F7442 LR: Multiturn does not match the modulo range · F7490 Enable signal withdrawn while traversing · F7493 LR: Overflow of the value range for position actual value · F52904 Control mode change · F52911 Positive torque limitation value error
Siemens MICROMASTER 440A0541 Motor data identification routine active · A0542 Speed controller optimization running · A0920 ADC parameters not correctly set · A0921 DAC parameters not set properly · A0923 JOG counter-clockwise as well as JOG clockwise are requested · A0936 PID auto tuning active
ABB ACS355F1000 PAR HZRPM · F1003 PAR AI SCALE · F1004 PAR AO SCALE · F1005 PAR PCU 2 · F1006 PAR EXT RO · F1007 PAR FBUSMISS
Delta VFD-EcFA Auto accel/decel failure
Delta C2000Pcod Password is locked
Delta ASDA-B2AL008 Abnormal pulse command
Hitachi WJ200E13 USP · E43 EzSQ invalid instruction · E44 EzSQ nesting count error · E45 EzSQ instruction error
Schneider Electric Altivar ATV320CFF Incorrect configuration error · CFI Invalid configuration error · CFI2 Configuration transfer error · CSF Channel switching detected error · FBE Function block error · FBES Function block stop error
INVT Goodrive20 (GD20)END Running time reached
Yaskawa V1000CF Control Fault · nSE Node Setup Error · oPE01 Drive Capacity Setting Fault · oPE02 Parameter Range Setting Error · oPE03 Multi-Function Input Selection Error · oPE04 Initialization required
Yaskawa A1000CF Control Fault · nSE Node Setup Error · oPE01 Drive Capacity Setting Fault · oPE02 Parameter Range Setting Error · oPE03 Multi-Function Input Selection Error · oPE04 Initialization Required
Siemens MICROMASTER 420A0920 ADC parameters not correctly set · A0921 DAC parameters not set properly · A0923 JOG counter-clockwise as well as JOG clockwise are requested
Siemens MICROMASTER 430A0920 ADC parameters not correctly set · A0921 DAC parameters not correctly set
Siemens SINAMICS G110F0056 BOP not fitted · F0057 BOP fault · F0058 BOP contents incompatible · A0920 ADC parameters not set properly · A0923 Both JOG left and JOG right are requested
INVT Goodrive200A (GD200A)END Running time reached
Mitsubishi Electric FR-D700E.AIE Analog input fault · HOLD Operation panel lock · LOCD Password locked · Er1 Write disable error · Er2 Write error during operation · Er3 Calibration error
Danfoss VLT Micro Drive FC 51Alarm 80 Drive initialised to default value · Error 85 Button disabled · Error 89 Parameter read only · Error 91 Parameter value is not valid in this mode · Error 92 Parameter value exceeds the min/max limits

07 / More codes

Other GA500 codes

Source

Yaskawa, GA500 Drive Technical Reference, C, SIEP C710617 52, 7 Troubleshooting (7.4 to 7.7, 7.9).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.