MachineryFix

Delta AC drive (VFD) · fault code

C2000 Pcod: Password is locked

Pcod on the Delta C2000 is the “Password is locked” fault. A fault stops the drive's output. On over-current and over-voltage faults the drive closes its output gate at once and the motor coasts to a stop.

A setting the drive cannot accept, or an operating state it is reporting. An alarm of this kind does not stop the motor on its own; a setup fault keeps the drive from running until the setting is corrected.

Code
Pcod
Type
Fault (stops the drive)
Drive
Delta C2000
Kind of fault
Setup

01 / Causes

What causes Pcod

  • A wrong password was entered in Pr. 00-07 three times in a row.

02 / Checks

What to check for Pcod

In the order Delta Electronics gives them.

  1. 01Switch the drive off and on again and enter the correct password.
  2. 02If the password is forgotten: enter 9999 and press ENTER, then enter 9999 and press ENTER again, both within 10 seconds (start again if it takes longer). Finishing this returns the parameters to their defaults.

Also in the manual

  • Fault ID 52. Reset by switching the power off.

03 / Clearing it

How to clear Pcod

  • Remove the cause first. Then press STOP/RESET on the keypad, or switch on a multi-function input set to 5 (Reset).
  • Most faults can be reset 5 seconds after the fault has cleared. Over-voltage faults reset only once the DC bus is below 90% of the trip level, and overheating faults only once the temperature is 10°C below it.
  • Some faults can only be cleared by switching the power off: the current detection and hardware protection faults (cd1 to cd3, Hd0 to Hd3), the watchdog (WDTT), STO Loss (STL1 to STL3) and the CPU error (TRAP).
  • After resetting, if the keypad returns to its main page and shows no fault after ESC, the fault is cleared.

Clear it once. If Pcod comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How setup faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the parameters the manual names for this code.

05 / Repair

When Pcod means a repair

No repair: a setting to correct.

If Pcod keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.

06 / Other drives

Setup: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20A541 Motor data identification active · A921 Analog output parameters not set properly · A923 Both JOG left and JOG right are requested · A936 PID autotuning active
Siemens SINAMICS G120F01033 Switching over units: Reference parameter value invalid · F01034 Switching over units: Calculation of the parameter values after reference value change unsuccessful · F01122 Frequency at the probe input too high · F01512 An attempt has been made to establish a conversion factor for scaling which does not exist · F06310 Supply voltage (p0210) incorrectly set · F07086 Switching over units: Parameter limit violation
Siemens SINAMICS V90F7085 Open-loop/closed-loop control parameters changed · F7442 LR: Multiturn does not match the modulo range · F7490 Enable signal withdrawn while traversing · F7493 LR: Overflow of the value range for position actual value · F52904 Control mode change · F52911 Positive torque limitation value error
Siemens MICROMASTER 440A0541 Motor data identification routine active · A0542 Speed controller optimization running · A0920 ADC parameters not correctly set · A0921 DAC parameters not set properly · A0923 JOG counter-clockwise as well as JOG clockwise are requested · A0936 PID auto tuning active
ABB ACS355F1000 PAR HZRPM · F1003 PAR AI SCALE · F1004 PAR AO SCALE · F1005 PAR PCU 2 · F1006 PAR EXT RO · F1007 PAR FBUSMISS
Delta VFD-EcFA Auto accel/decel failure
Delta ASDA-B2AL008 Abnormal pulse command
Hitachi WJ200E13 USP · E43 EzSQ invalid instruction · E44 EzSQ nesting count error · E45 EzSQ instruction error
Schneider Electric Altivar ATV320CFF Incorrect configuration error · CFI Invalid configuration error · CFI2 Configuration transfer error · CSF Channel switching detected error · FBE Function block error · FBES Function block stop error
INVT Goodrive20 (GD20)END Running time reached
Yaskawa V1000CF Control Fault · nSE Node Setup Error · oPE01 Drive Capacity Setting Fault · oPE02 Parameter Range Setting Error · oPE03 Multi-Function Input Selection Error · oPE04 Initialization required
Yaskawa A1000CF Control Fault · nSE Node Setup Error · oPE01 Drive Capacity Setting Fault · oPE02 Parameter Range Setting Error · oPE03 Multi-Function Input Selection Error · oPE04 Initialization Required
Yaskawa GA500CF Control Fault · nSE Node Setup Error · TiM Keypad Time Not Set · oPE01 Drive Capacity Setting Error · oPE02 Parameter Range Setting Error · oPE03 Multi-Function Input Setting Err
Siemens MICROMASTER 420A0920 ADC parameters not correctly set · A0921 DAC parameters not set properly · A0923 JOG counter-clockwise as well as JOG clockwise are requested
Siemens MICROMASTER 430A0920 ADC parameters not correctly set · A0921 DAC parameters not correctly set
Siemens SINAMICS G110F0056 BOP not fitted · F0057 BOP fault · F0058 BOP contents incompatible · A0920 ADC parameters not set properly · A0923 Both JOG left and JOG right are requested
INVT Goodrive200A (GD200A)END Running time reached
Mitsubishi Electric FR-D700E.AIE Analog input fault · HOLD Operation panel lock · LOCD Password locked · Er1 Write disable error · Er2 Write error during operation · Er3 Calibration error
Danfoss VLT Micro Drive FC 51Alarm 80 Drive initialised to default value · Error 85 Button disabled · Error 89 Parameter read only · Error 91 Parameter value is not valid in this mode · Error 92 Parameter value exceeds the min/max limits

07 / More codes

Other C2000 codes

Source

Delta Electronics, C2000 Series User Manual, Issued edition 01, firmware V2.05 (2019-02-13), DELTA_IA-MDS_VFD-C2000_UM_EN_20190213, Chapter 14, Fault Codes and Descriptions.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

Pcod won't clear? Get a technician who knows the C2000.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.