CFI on the Schneider Electric Altivar ATV320 is the “Invalid configuration error” fault. A detected error stops the drive until it is cleared, in the way the manual gives for that code.
A setting the drive cannot accept, or an operating state it is reporting. An alarm of this kind does not stop the motor on its own; a setup fault keeps the drive from running until the setting is corrected.
- Code
- CFI
- Type
- Fault (stops the drive)
- Drive
- Schneider Electric Altivar ATV320
- Kind of fault
- Setup
01 / Causes
What causes CFI
- The configuration loaded into the drive over the bus or network is inconsistent.
02 / Checks
What to check for CFI
In the order Schneider Electric gives them.
- 01Check the configuration loaded earlier.
- 02Load a compatible configuration.
Also in the manual
- Clears by itself as soon as the cause is gone.
03 / Clearing it
How to clear CFI
- Remove the cause first. A resettable error can then be cleared by switching the drive off until the display goes out completely and back on, automatically by the Auto Fault Reset (ATR) function, through an input or control bit assigned to Fault reset (RST), or with the STOP/RESET key on the graphic display terminal when it is the active command channel.
- Some codes need a power reset (ANF, ASF, BLF, BRF, CRF1, EEF1, EEF2, FCF1, HDF, ILF, the INF codes, SAFF, SOF, SPF); ASF, BRF, SOF, SPF and TNF can also be cleared remotely with Fault Reset Assign (RSF).
- For an error that cannot be reset, Schneider's steps are: disconnect all power, including external control power; lock the disconnects open; wait 15 minutes for the DC bus capacitors to discharge; check the DC bus between PA/+ and PC/- is below 42 V DC; find and fix the cause; then restore power to confirm.
Clear it once. If CFI comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How setup faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the parameters the manual names for this code.
05 / Repair
When CFI means a repair
No repair: a setting to correct.
If CFI keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Schneider Electric drives, and they arrive knowing what to look for.
06 / Other drives
Setup: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | A541 Motor data identification active · A921 Analog output parameters not set properly · A923 Both JOG left and JOG right are requested · A936 PID autotuning active |
| Siemens SINAMICS G120 | F01033 Switching over units: Reference parameter value invalid · F01034 Switching over units: Calculation of the parameter values after reference value change unsuccessful · F01122 Frequency at the probe input too high · F01512 An attempt has been made to establish a conversion factor for scaling which does not exist · F06310 Supply voltage (p0210) incorrectly set · F07086 Switching over units: Parameter limit violation |
| Siemens SINAMICS V90 | F7085 Open-loop/closed-loop control parameters changed · F7442 LR: Multiturn does not match the modulo range · F7490 Enable signal withdrawn while traversing · F7493 LR: Overflow of the value range for position actual value · F52904 Control mode change · F52911 Positive torque limitation value error |
| Siemens MICROMASTER 440 | A0541 Motor data identification routine active · A0542 Speed controller optimization running · A0920 ADC parameters not correctly set · A0921 DAC parameters not set properly · A0923 JOG counter-clockwise as well as JOG clockwise are requested · A0936 PID auto tuning active |
| ABB ACS355 | F1000 PAR HZRPM · F1003 PAR AI SCALE · F1004 PAR AO SCALE · F1005 PAR PCU 2 · F1006 PAR EXT RO · F1007 PAR FBUSMISS |
| Delta VFD-E | cFA Auto accel/decel failure |
| Delta C2000 | Pcod Password is locked |
| Delta ASDA-B2 | AL008 Abnormal pulse command |
| Hitachi WJ200 | E13 USP · E43 EzSQ invalid instruction · E44 EzSQ nesting count error · E45 EzSQ instruction error |
| INVT Goodrive20 (GD20) | END Running time reached |
| Yaskawa V1000 | CF Control Fault · nSE Node Setup Error · oPE01 Drive Capacity Setting Fault · oPE02 Parameter Range Setting Error · oPE03 Multi-Function Input Selection Error · oPE04 Initialization required |
| Yaskawa A1000 | CF Control Fault · nSE Node Setup Error · oPE01 Drive Capacity Setting Fault · oPE02 Parameter Range Setting Error · oPE03 Multi-Function Input Selection Error · oPE04 Initialization Required |
| Yaskawa GA500 | CF Control Fault · nSE Node Setup Error · TiM Keypad Time Not Set · oPE01 Drive Capacity Setting Error · oPE02 Parameter Range Setting Error · oPE03 Multi-Function Input Setting Err |
| Siemens MICROMASTER 420 | A0920 ADC parameters not correctly set · A0921 DAC parameters not set properly · A0923 JOG counter-clockwise as well as JOG clockwise are requested |
| Siemens MICROMASTER 430 | A0920 ADC parameters not correctly set · A0921 DAC parameters not correctly set |
| Siemens SINAMICS G110 | F0056 BOP not fitted · F0057 BOP fault · F0058 BOP contents incompatible · A0920 ADC parameters not set properly · A0923 Both JOG left and JOG right are requested |
| INVT Goodrive200A (GD200A) | END Running time reached |
| Mitsubishi Electric FR-D700 | E.AIE Analog input fault · HOLD Operation panel lock · LOCD Password locked · Er1 Write disable error · Er2 Write error during operation · Er3 Calibration error |
| Danfoss VLT Micro Drive FC 51 | Alarm 80 Drive initialised to default value · Error 85 Button disabled · Error 89 Parameter read only · Error 91 Parameter value is not valid in this mode · Error 92 Parameter value exceeds the min/max limits |
07 / More codes
Other Altivar ATV320 codes
Source
Schneider Electric, Altivar Machine ATV320 Programming Manual, 04/2025, NVE41295.06, Diagnostics and Troubleshooting.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Schneider Electric and is not its authorised service partner.