F7493 on the Siemens SINAMICS V90 is the “LR: Overflow of the value range for position actual value” fault. A fault triggers the reaction set for it: OFF1 ramps the motor down, OFF2 lets it coast down, OFF3 stops it quickly as an emergency stop, and NONE takes no action. Each fault page gives the reaction and the acknowledgement type.
A setting the drive cannot accept, or an operating state it is reporting. An alarm of this kind does not stop the motor on its own; a setup fault keeps the drive from running until the setting is corrected.
- Code
- F7493
- Type
- Fault (stops the drive)
- Drive
- Siemens SINAMICS V90, SIMOTICS S-1FL6
- Kind of fault
- Setup
01 / Causes
What causes F7493
- The actual position value (r2521) went beyond its range (-2147483648 to 2147483647).
- The encoder's actual position value went beyond its range.
- The maximum encoder value, converted from increments to length units, went beyond the range for showing the actual position.
02 / Checks
What to check for F7493
In the order Siemens gives them.
- 01If needed, reduce the traversing range or the position resolution (p29247).
Also in the manual
- Reaction OFF1 (OFF2, OFF3): the motor ramps down. Acknowledgement IMMEDIATELY: it clears as soon as the cause is removed.
- When the overflow occurs, the "referenced" or "absolute measuring system adjusted" status is reset.
- If the largest possible absolute position in length units is above 4294967296, adjustment is not possible because of the overflow. The manual gives the formulas for rotary multiturn encoders: p29247 × p29248 × 4096 / p29249 in IPOS mode, 1048576 × p29012[x] × 4096 / p29013 in PTI mode.
03 / Clearing it
How to clear F7493
- Remove the cause first. Then acknowledge the fault on the BOP, with the RESET digital input, or in SINAMICS V-ASSISTANT.
- Each fault has its own acknowledgement type: POWER ON (power the drive off and on after removing the cause), IMMEDIATELY (it clears once the cause is removed), or PULSE INHIBIT (it can only be acknowledged with a pulse inhibit).
- If the cause is not removed, the fault can come back after five seconds with no button pressed.
- Alarms acknowledge themselves.
Clear it once. If F7493 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How setup faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the parameters the manual names for this code.
05 / Repair
When F7493 means a repair
No repair: a setting to correct.
If F7493 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Setup: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | A541 Motor data identification active · A921 Analog output parameters not set properly · A923 Both JOG left and JOG right are requested · A936 PID autotuning active |
| Siemens SINAMICS G120 | F01033 Switching over units: Reference parameter value invalid · F01034 Switching over units: Calculation of the parameter values after reference value change unsuccessful · F01122 Frequency at the probe input too high · F01512 An attempt has been made to establish a conversion factor for scaling which does not exist · F06310 Supply voltage (p0210) incorrectly set · F07086 Switching over units: Parameter limit violation |
| Siemens MICROMASTER 440 | A0541 Motor data identification routine active · A0542 Speed controller optimization running · A0920 ADC parameters not correctly set · A0921 DAC parameters not set properly · A0923 JOG counter-clockwise as well as JOG clockwise are requested · A0936 PID auto tuning active |
| ABB ACS355 | F1000 PAR HZRPM · F1003 PAR AI SCALE · F1004 PAR AO SCALE · F1005 PAR PCU 2 · F1006 PAR EXT RO · F1007 PAR FBUSMISS |
| Delta VFD-E | cFA Auto accel/decel failure |
| Delta C2000 | Pcod Password is locked |
| Delta ASDA-B2 | AL008 Abnormal pulse command |
| Hitachi WJ200 | E13 USP · E43 EzSQ invalid instruction · E44 EzSQ nesting count error · E45 EzSQ instruction error |
| Schneider Electric Altivar ATV320 | CFF Incorrect configuration error · CFI Invalid configuration error · CFI2 Configuration transfer error · CSF Channel switching detected error · FBE Function block error · FBES Function block stop error |
| INVT Goodrive20 (GD20) | END Running time reached |
| Yaskawa V1000 | CF Control Fault · nSE Node Setup Error · oPE01 Drive Capacity Setting Fault · oPE02 Parameter Range Setting Error · oPE03 Multi-Function Input Selection Error · oPE04 Initialization required |
| Yaskawa A1000 | CF Control Fault · nSE Node Setup Error · oPE01 Drive Capacity Setting Fault · oPE02 Parameter Range Setting Error · oPE03 Multi-Function Input Selection Error · oPE04 Initialization Required |
| Yaskawa GA500 | CF Control Fault · nSE Node Setup Error · TiM Keypad Time Not Set · oPE01 Drive Capacity Setting Error · oPE02 Parameter Range Setting Error · oPE03 Multi-Function Input Setting Err |
| Siemens MICROMASTER 420 | A0920 ADC parameters not correctly set · A0921 DAC parameters not set properly · A0923 JOG counter-clockwise as well as JOG clockwise are requested |
| Siemens MICROMASTER 430 | A0920 ADC parameters not correctly set · A0921 DAC parameters not correctly set |
| Siemens SINAMICS G110 | F0056 BOP not fitted · F0057 BOP fault · F0058 BOP contents incompatible · A0920 ADC parameters not set properly · A0923 Both JOG left and JOG right are requested |
| INVT Goodrive200A (GD200A) | END Running time reached |
| Mitsubishi Electric FR-D700 | E.AIE Analog input fault · HOLD Operation panel lock · LOCD Password locked · Er1 Write disable error · Er2 Write error during operation · Er3 Calibration error |
| Danfoss VLT Micro Drive FC 51 | Alarm 80 Drive initialised to default value · Error 85 Button disabled · Error 89 Parameter read only · Error 91 Parameter value is not valid in this mode · Error 92 Parameter value exceeds the min/max limits |
07 / More codes
Other SINAMICS V90 codes
Source
Siemens, SINAMICS V90, SIMOTICS S-1FL6 Operating Instructions, 04/2014, 6SL3298-0AV60-0BP0, 11 Diagnostics (11.2 List of faults and alarms).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007