STPo on the Yaskawa GA500 is the “Motor Step-Out Detected” fault. A fault shuts off the drive's output and the motor coasts to a stop (some faults let you choose the stopping method). ALM/ERR stays lit, a terminal set to H2-01 to H2-03 = E activates, and the drive will not run until the fault is reset.
The drive could not get the motor to follow the commanded speed: it sat at its current limit for too long. The load is too heavy for the ramp, the motor is jammed, or the motor is connected or set up wrongly.
- Code
- STPo
- Type
- Fault (stops the drive)
- Drive
- Yaskawa GA500
- Kind of fault
- Motor stall
01 / Causes
What causes STPo
- The PM motor code is set wrongly, the load or its inertia is too large, acceleration and deceleration are too short, or the speed response is too slow.
02 / Checks
What to check for STPo
In the order Yaskawa gives them.
- 01Set E5-01 (PM Motor Code Selection) for the motor; for special motors, set the E5 parameters from the motor test report.
- 02Raise n8-55 (Motor to Load Inertia Ratio) and n8-51 (Pull-in Current at Acceleration); if STPo then occurs in deceleration, set n8-79 below n8-51.
- 03Reduce the load, or fit a larger drive and motor.
- 04Lengthen C1-01 to C1-08 and C2-01.
03 / Clearing it
How to clear STPo
- Remove the cause, then reset in one of three ways: the reset key on the keypad while the code is shown, a multi-function input set to H1-xx = 14 (terminal S4 by default), or switching off the main circuit power and switching it back on once the keypad display has gone out.
- A fault will not reset while a run command is active from the terminals or a communication option; the keypad shows CrST until the run command is removed.
- oL1 resets only once monitor U4-16 (Motor oL1 Level) is below 100.
Clear it once. If STPo comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How motor stall faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the load turns freely and nothing is jammed.
- 02Lengthen the acceleration time and check the current limit setting.
- 03Check motor connections (star or delta) against the rating plate and the drive's motor data.
05 / Repair
When STPo means a repair
A free-turning load, correct setup and repeated stalls point at a motor winding fault or a drive output problem.
If STPo keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Motor stall: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F07900 Motor blocked · F07902 Motor stalled · A07903 Motor speed deviation |
| Siemens SINAMICS V90 | F7450 Standstill monitoring has responded · F7452 Following error too high · F7900 Motor blocked/speed controller at its limit |
| Siemens MICROMASTER 440 | F0453 Motor stalled |
| Allen-Bradley PowerFlex 525 | F006 Motor Stalled |
| ABB ACS355 | F0012 MOTOR STALL · A2012 MOTOR STALL |
| Delta C2000 | oSL Over slip error · SdRv Reverse direction of the speed feedback · SdOr Over speed rotation feedback · SdDe Large deviation of speed feedback · SfLK PMLess shaft lock |
| Delta ASDA-B2 | AL009 Excessive deviation of position command |
| Schneider Electric Altivar ATV320 | ANF Load slipping error · SSF Torque limitation error |
| INVT Goodrive20 (GD20) | dEu Speed deviation fault |
| Yaskawa V1000 | STo Motor Pull Out or Step Out Detection |
| Yaskawa A1000 | LSo LSo Fault · STo Pull-Out Detection |
| Mitsubishi Electric FR-D700 | E.OLT Stall prevention stop |
| Danfoss VLT Micro Drive FC 51 | Warning 12 Torque limit |
07 / More codes
Other GA500 codes
Source
Yaskawa, GA500 Drive Technical Reference, C, SIEP C710617 52, 7 Troubleshooting (7.4 to 7.7, 7.9).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007