PowerFlex 525 F081: DSI Comm Loss

F081 on the Allen-Bradley PowerFlex 525 is the “DSI Comm Loss” fault. A fault stops the drive; it will not restart until the fault is cleared.

The drive stopped receiving messages from its controller (a PLC, a fieldbus master, a keypad or a network) within the allowed time. The drive itself is usually fine; the link to it is not.

Code
F081
Type
Fault (stops the drive)
Drive
Allen-Bradley PowerFlex 525, PowerFlex 523
Kind of fault
Communication loss

01 / Causes

What causes F081

Rockwell Automation's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing communication loss faults explains where it usually comes from.

02 / Checks

What to check for F081

In the order Rockwell Automation gives them.

  1. 01Cycle power.
  2. 02Check the communications cabling, and the Modbus or DSI settings and status.
  3. 03Change the drive's response with C125 [Comm Loss Action] if needed.
  4. 04Connecting I/O terminals C1 and C2 to ground may improve noise immunity.
  5. 05Replace the wiring, the Modbus master device or the control module.

03 / Clearing it

How to clear F081

  • Rockwell's parameter A551 [Fault Clear] resets a fault when set to 1 (Reset Fault); setting it to 2 (Clear Buffer) also clears the fault queue.
  • Correct the cause first: F033 means the drive has already used up its automatic restart attempts on a fault that is still there.

Clear it once. If F081 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How communication loss faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check whether the PLC or master is running and still sending to this drive.
  2. 02Check the communication cable, connectors and termination, and the screen's earth connection.
  3. 03Compare the drive's address, baud rate and timeout settings with the master's.
  4. 04Look for drives, contactors or welders near the cable that could be injecting noise.

05 / Repair

When F081 means a repair

If cable, settings and master are all good and only this drive drops out, its communication port or option card may have failed.

If F081 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Allen-Bradley drives, and they arrive knowing what to look for.

06 / Other drives

Communication loss: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F70 I/O Extension Module communication fault · F71 USS setpoint fault · F72 USS/MODBUS setpoint fault
Siemens SINAMICS G120F01910 Setpoint timeout · F08501 Setpoint timeout · F08502 Monitoring time, sign-of-life expired · F08510 Send configuration data not valid · F08700 Communications error · A01900 PROFIBUS: Configuration telegram faulty
Siemens SINAMICS V90F1030 Sign-of-life failure for master control · A1920 Drive Bus: Receive setpoints after To · A1932 Drive Bus clock cycle synchronization missing for DSC
Siemens MICROMASTER 440F0070 CB setpoint fault · F0071 USS (BOP link) setpoint fault · F0072 USS (COMM link) setpoint fault · A0700 CB alarm 1 · A0710 CB communications error · A0711 CB communications error
ABB ACS355F0010 PANEL LOSS · F0028 SERIAL 1 ERR · F0029 EFB CON FILE · A2005 IO COMM · A2008 PANEL LOSS · A5001 Drive is not responding
Delta VFD-EcE01 Illegal function code · cE02 Illegal data address · cE03 Illegal data value · cE04 Slave device failure · cE10 Communication time-out
Delta C2000CE1 Illegal command · CE2 Illegal data address · CE3 Illegal data value · CE4 Data is written to read-only address · CE10 MODBUS transmission time-out · CGdE CANopen guarding error
Delta ASDA-B2AL019 Serial communication error · AL020 Serial communication time out
Hitachi WJ200E40 Operator connection · E41 Modbus communication error · E60 Option error (DeviceNet communications error) · E61 Option error (duplicated MAC ID) · E69 Option error (inverter communication error)
Schneider Electric Altivar ATV320CNF Fieldbus module communication interruption error · COF CANopen communication interruption error · SLF1 Modbus communication interruption error · SLF2 PC communication interruption error · SLF3 HMI communication interruption error
INVT Goodrive20 (GD20)CE RS485 communication fault · PCE Keypad communication error · UPE Parameter upload error · DNE Parameter download error
Yaskawa V1000bUS Option Communication Error · CE MEMOBUS/Modbus Communication Error · E5 MECHATROLINK Watchdog Timer Error · oFA00 Option Card Connection Error at Option Port CN5 · oFA01 Option Card Fault · oFA03 Option Card Fault
Yaskawa A1000bUS Option Communication Error · CE MEMOBUS/Modbus Communication Error · E5 MECHATROLINK Watchdog Timer Error · oFA00 Option Card Connection Error at Option Port CN5-A · oFA01 Option Card Fault at Option Port CN5-A · oFb00 Option Card Fault at Option Port CN5-B
Yaskawa GA500bCE Bluetooth Communication Fault · bUS Option Communication Error · CE Modbus Communication Error · E5 MECHATROLINK Watchdog Timer Err · oFA00 Option Not Compatible with Port · oFA01 Option Fault/Connection Error
Siemens MICROMASTER 420F0070 CB setpoint fault · F0071 USS (BOP link) setpoint fault · F0072 USS (COMM link) setpoint fault · A0700 CB alarm 1 · A0701 CB alarm 2 · A0702 CB alarm 3
Siemens MICROMASTER 430F0070 CB setpoint fault · F0071 USS (BOP link) setpoint fault · F0072 USS (COMM link) setpoint fault · A0700 CB alarm 1 · A0701 CB alarm 2 · A0702 CB alarm 3
Siemens SINAMICS G110F0072 USS setpoint fault
INVT Goodrive200A (GD200A)CE RS485 communication fault · PCE Keypad communication fault · UPE Parameter upload error · DNE Parameter download error
Mitsubishi Electric FR-D700E.PUE PU disconnection
Danfoss VLT Micro Drive FC 51Alarm 17 Control word timeout · Error 84 The connection between drive and LCP is lost · Error 90 Parameter database busy

07 / More codes

Other PowerFlex 525 codes

Source

Rockwell Automation, PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start, November 2017, 520-QS001B-EN-E, Fault Codes.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Allen-Bradley and is not its authorised service partner.