A0710 on the Siemens MICROMASTER 440 is the “CB communications error” alarm. An alarm is a warning the inverter shows while it keeps running; some alarms reduce the output or pulse frequency to protect the inverter.
The drive stopped receiving messages from its controller (a PLC, a fieldbus master, a keypad or a network) within the allowed time. The drive itself is usually fine; the link to it is not.
- Code
- A0710
- Type
- Alarm (warning)
- Drive
- Siemens MICROMASTER 440
- Kind of fault
- Communication loss
01 / Causes
What causes A0710
- Communication with the communications board (CB) has been lost.
02 / Checks
What to check for A0710
In the order Siemens gives them.
- 01Check the communications board hardware.
03 / Clearing it
How to clear A0710
An alarm is a warning the inverter shows while it keeps running; some alarms reduce the output or pulse frequency to protect the inverter.
If A0710 stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.
04 / On site
How communication loss faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check whether the PLC or master is running and still sending to this drive.
- 02Check the communication cable, connectors and termination, and the screen's earth connection.
- 03Compare the drive's address, baud rate and timeout settings with the master's.
- 04Look for drives, contactors or welders near the cable that could be injecting noise.
05 / Repair
When A0710 means a repair
If cable, settings and master are all good and only this drive drops out, its communication port or option card may have failed.
If A0710 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Communication loss: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F70 I/O Extension Module communication fault · F71 USS setpoint fault · F72 USS/MODBUS setpoint fault |
| Siemens SINAMICS G120 | F01910 Setpoint timeout · F08501 Setpoint timeout · F08502 Monitoring time, sign-of-life expired · F08510 Send configuration data not valid · F08700 Communications error · A01900 PROFIBUS: Configuration telegram faulty |
| Siemens SINAMICS V90 | F1030 Sign-of-life failure for master control · A1920 Drive Bus: Receive setpoints after To · A1932 Drive Bus clock cycle synchronization missing for DSC |
| Allen-Bradley PowerFlex 525 | F071 DSI Net Loss · F072 Opt Net Loss · F073 EN Net Loss · F081 DSI Comm Loss · F082 Opt Comm Loss · F083 EN Comm Loss |
| ABB ACS355 | F0010 PANEL LOSS · F0028 SERIAL 1 ERR · F0029 EFB CON FILE · A2005 IO COMM · A2008 PANEL LOSS · A5001 Drive is not responding |
| Delta VFD-E | cE01 Illegal function code · cE02 Illegal data address · cE03 Illegal data value · cE04 Slave device failure · cE10 Communication time-out |
| Delta C2000 | CE1 Illegal command · CE2 Illegal data address · CE3 Illegal data value · CE4 Data is written to read-only address · CE10 MODBUS transmission time-out · CGdE CANopen guarding error |
| Delta ASDA-B2 | AL019 Serial communication error · AL020 Serial communication time out |
| Hitachi WJ200 | E40 Operator connection · E41 Modbus communication error · E60 Option error (DeviceNet communications error) · E61 Option error (duplicated MAC ID) · E69 Option error (inverter communication error) |
| Schneider Electric Altivar ATV320 | CNF Fieldbus module communication interruption error · COF CANopen communication interruption error · SLF1 Modbus communication interruption error · SLF2 PC communication interruption error · SLF3 HMI communication interruption error |
| INVT Goodrive20 (GD20) | CE RS485 communication fault · PCE Keypad communication error · UPE Parameter upload error · DNE Parameter download error |
| Yaskawa V1000 | bUS Option Communication Error · CE MEMOBUS/Modbus Communication Error · E5 MECHATROLINK Watchdog Timer Error · oFA00 Option Card Connection Error at Option Port CN5 · oFA01 Option Card Fault · oFA03 Option Card Fault |
| Yaskawa A1000 | bUS Option Communication Error · CE MEMOBUS/Modbus Communication Error · E5 MECHATROLINK Watchdog Timer Error · oFA00 Option Card Connection Error at Option Port CN5-A · oFA01 Option Card Fault at Option Port CN5-A · oFb00 Option Card Fault at Option Port CN5-B |
| Yaskawa GA500 | bCE Bluetooth Communication Fault · bUS Option Communication Error · CE Modbus Communication Error · E5 MECHATROLINK Watchdog Timer Err · oFA00 Option Not Compatible with Port · oFA01 Option Fault/Connection Error |
| Siemens MICROMASTER 420 | F0070 CB setpoint fault · F0071 USS (BOP link) setpoint fault · F0072 USS (COMM link) setpoint fault · A0700 CB alarm 1 · A0701 CB alarm 2 · A0702 CB alarm 3 |
| Siemens MICROMASTER 430 | F0070 CB setpoint fault · F0071 USS (BOP link) setpoint fault · F0072 USS (COMM link) setpoint fault · A0700 CB alarm 1 · A0701 CB alarm 2 · A0702 CB alarm 3 |
| Siemens SINAMICS G110 | F0072 USS setpoint fault |
| INVT Goodrive200A (GD200A) | CE RS485 communication fault · PCE Keypad communication fault · UPE Parameter upload error · DNE Parameter download error |
| Mitsubishi Electric FR-D700 | E.PUE PU disconnection |
| Danfoss VLT Micro Drive FC 51 | Alarm 17 Control word timeout · Error 84 The connection between drive and LCP is lost · Error 90 Parameter database busy |
07 / More codes
Other MICROMASTER 440 codes
Source
Siemens, MICROMASTER 440 Parameter List, Issue 01/06, 6SE6400-5BB00-0BP0, Section 5, Faults and Alarms.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007