A1000 bUS: Option Communication Error

bUS on the Yaskawa A1000 is the “Option Communication Error” fault. A fault is detected for drive protection: it stops the drive and toggles the fault output on terminals MA-MB-MC. Remove the cause and clear the fault before running again.

The drive stopped receiving messages from its controller (a PLC, a fieldbus master, a keypad or a network) within the allowed time. The drive itself is usually fine; the link to it is not.

Code
bUS
Type
Fault (stops the drive)
Drive
Yaskawa A1000
Kind of fault
Communication loss

01 / Causes

What causes bUS

  • Communication was lost after it had been established. Only detected when the run command or frequency reference comes from an option card.
  • No signal from the PLC, faulty or shorted wiring, noise, a damaged option card, or a card not seated properly.

02 / Checks

What to check for bUS

In the order Yaskawa gives them.

  1. 01Check the communication wiring for faults, disconnected cables and short circuits, and repair them.
  2. 02Counteract noise in the control circuit, main circuit and ground wiring; make sure switches or relays nearby are not the source, and use surge absorbers if needed.
  3. 03Use recommended or other shielded cable, grounding the shield on the controller side or the drive input side.
  4. 04Run communication wiring separately from the drive's power lines, and fit an EMC noise filter on the drive's input.
  5. 05Reinstall the option card, checking its connector pins line up with the drive's.
  6. 06If the wiring is good and the error continues, replace the option card.

Also in the manual

  • The A1000 can also raise this code as an alarm: the ALM light blinks, the code flashes, and the drive does not necessarily stop.

03 / Clearing it

How to clear bUS

  • Remove the cause, then clear the fault manually before running again: the reset key on the digital operator, a multi-function input set to fault reset, or cycling the power.
  • Some faults need a condition met first: oL1 cannot be reset until monitor U4-16 is below 100%. SC will not accept a reset at all, to protect the drive's internal circuits.

Clear it once. If bUS comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How communication loss faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check whether the PLC or master is running and still sending to this drive.
  2. 02Check the communication cable, connectors and termination, and the screen's earth connection.
  3. 03Compare the drive's address, baud rate and timeout settings with the master's.
  4. 04Look for drives, contactors or welders near the cable that could be injecting noise.

05 / Repair

When bUS means a repair

If cable, settings and master are all good and only this drive drops out, its communication port or option card may have failed.

If bUS keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Communication loss: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F70 I/O Extension Module communication fault · F71 USS setpoint fault · F72 USS/MODBUS setpoint fault
Siemens SINAMICS G120F01910 Setpoint timeout · F08501 Setpoint timeout · F08502 Monitoring time, sign-of-life expired · F08510 Send configuration data not valid · F08700 Communications error · A01900 PROFIBUS: Configuration telegram faulty
Siemens SINAMICS V90F1030 Sign-of-life failure for master control · A1920 Drive Bus: Receive setpoints after To · A1932 Drive Bus clock cycle synchronization missing for DSC
Siemens MICROMASTER 440F0070 CB setpoint fault · F0071 USS (BOP link) setpoint fault · F0072 USS (COMM link) setpoint fault · A0700 CB alarm 1 · A0710 CB communications error · A0711 CB communications error
Allen-Bradley PowerFlex 525F071 DSI Net Loss · F072 Opt Net Loss · F073 EN Net Loss · F081 DSI Comm Loss · F082 Opt Comm Loss · F083 EN Comm Loss
ABB ACS355F0010 PANEL LOSS · F0028 SERIAL 1 ERR · F0029 EFB CON FILE · A2005 IO COMM · A2008 PANEL LOSS · A5001 Drive is not responding
Delta VFD-EcE01 Illegal function code · cE02 Illegal data address · cE03 Illegal data value · cE04 Slave device failure · cE10 Communication time-out
Delta C2000CE1 Illegal command · CE2 Illegal data address · CE3 Illegal data value · CE4 Data is written to read-only address · CE10 MODBUS transmission time-out · CGdE CANopen guarding error
Delta ASDA-B2AL019 Serial communication error · AL020 Serial communication time out
Hitachi WJ200E40 Operator connection · E41 Modbus communication error · E60 Option error (DeviceNet communications error) · E61 Option error (duplicated MAC ID) · E69 Option error (inverter communication error)
Schneider Electric Altivar ATV320CNF Fieldbus module communication interruption error · COF CANopen communication interruption error · SLF1 Modbus communication interruption error · SLF2 PC communication interruption error · SLF3 HMI communication interruption error
INVT Goodrive20 (GD20)CE RS485 communication fault · PCE Keypad communication error · UPE Parameter upload error · DNE Parameter download error
Yaskawa V1000bUS Option Communication Error · CE MEMOBUS/Modbus Communication Error · E5 MECHATROLINK Watchdog Timer Error · oFA00 Option Card Connection Error at Option Port CN5 · oFA01 Option Card Fault · oFA03 Option Card Fault
Yaskawa GA500bCE Bluetooth Communication Fault · bUS Option Communication Error · CE Modbus Communication Error · E5 MECHATROLINK Watchdog Timer Err · oFA00 Option Not Compatible with Port · oFA01 Option Fault/Connection Error
Siemens MICROMASTER 420F0070 CB setpoint fault · F0071 USS (BOP link) setpoint fault · F0072 USS (COMM link) setpoint fault · A0700 CB alarm 1 · A0701 CB alarm 2 · A0702 CB alarm 3
Siemens MICROMASTER 430F0070 CB setpoint fault · F0071 USS (BOP link) setpoint fault · F0072 USS (COMM link) setpoint fault · A0700 CB alarm 1 · A0701 CB alarm 2 · A0702 CB alarm 3
Siemens SINAMICS G110F0072 USS setpoint fault
INVT Goodrive200A (GD200A)CE RS485 communication fault · PCE Keypad communication fault · UPE Parameter upload error · DNE Parameter download error
Mitsubishi Electric FR-D700E.PUE PU disconnection
Danfoss VLT Micro Drive FC 51Alarm 17 Control word timeout · Error 84 The connection between drive and LCP is lost · Error 90 Parameter database busy

07 / More codes

Other A1000 codes

Source

Yaskawa, YASKAWA AC Drive A1000 Quick Start Guide, 41G, TOEP C710616 41, 5.2 to 5.5: Fault Detection, Alarm Detection, Operator Programming Errors, Auto-Tuning Fault Detection.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

bUS won't clear? Get a technician who knows the A1000.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.