Goodrive20 (GD20) UPE: Parameter upload error

UPE on the INVT Goodrive20 (GD20) is the “Parameter upload error” fault. A fault trips the drive and lights the TRIP indicator; the drive stays stopped until the fault is reset.

The drive stopped receiving messages from its controller (a PLC, a fieldbus master, a keypad or a network) within the allowed time. The drive itself is usually fine; the link to it is not.

Code
UPE
Type
Fault (stops the drive)
Drive
INVT Goodrive20 (GD20)
Kind of fault
Communication loss

01 / Causes

What causes UPE

  • The keypad is badly connected or offline.
  • The keypad cable is too long and there is strong interference.
  • Part of the keypad's or main board's communication circuits has failed.

02 / Checks

What to check for UPE

In the order INVT gives them.

  1. 01Check the surroundings and remove the source of interference.
  2. 02Have the hardware replaced and serviced.

Also in the manual

  • Over communication this fault reads as type 27.

03 / Clearing it

How to clear UPE

  • Remove the cause, then reset with the keypad's STOP/RST key, through a digital input, or by switching the power off and on. Once the fault is cleared the motor can be restarted.
  • INVT's order of work: check the keypad is working; read the fault records in group P07 to see the drive's state when the fault happened; follow the table for that code; fix the cause; then reset and run.

Clear it once. If UPE comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How communication loss faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check whether the PLC or master is running and still sending to this drive.
  2. 02Check the communication cable, connectors and termination, and the screen's earth connection.
  3. 03Compare the drive's address, baud rate and timeout settings with the master's.
  4. 04Look for drives, contactors or welders near the cable that could be injecting noise.

05 / Repair

When UPE means a repair

If cable, settings and master are all good and only this drive drops out, its communication port or option card may have failed.

If UPE keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on INVT drives, and they arrive knowing what to look for.

06 / Other drives

Communication loss: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F70 I/O Extension Module communication fault · F71 USS setpoint fault · F72 USS/MODBUS setpoint fault
Siemens SINAMICS G120F01910 Setpoint timeout · F08501 Setpoint timeout · F08502 Monitoring time, sign-of-life expired · F08510 Send configuration data not valid · F08700 Communications error · A01900 PROFIBUS: Configuration telegram faulty
Siemens SINAMICS V90F1030 Sign-of-life failure for master control · A1920 Drive Bus: Receive setpoints after To · A1932 Drive Bus clock cycle synchronization missing for DSC
Siemens MICROMASTER 440F0070 CB setpoint fault · F0071 USS (BOP link) setpoint fault · F0072 USS (COMM link) setpoint fault · A0700 CB alarm 1 · A0710 CB communications error · A0711 CB communications error
Allen-Bradley PowerFlex 525F071 DSI Net Loss · F072 Opt Net Loss · F073 EN Net Loss · F081 DSI Comm Loss · F082 Opt Comm Loss · F083 EN Comm Loss
ABB ACS355F0010 PANEL LOSS · F0028 SERIAL 1 ERR · F0029 EFB CON FILE · A2005 IO COMM · A2008 PANEL LOSS · A5001 Drive is not responding
Delta VFD-EcE01 Illegal function code · cE02 Illegal data address · cE03 Illegal data value · cE04 Slave device failure · cE10 Communication time-out
Delta C2000CE1 Illegal command · CE2 Illegal data address · CE3 Illegal data value · CE4 Data is written to read-only address · CE10 MODBUS transmission time-out · CGdE CANopen guarding error
Delta ASDA-B2AL019 Serial communication error · AL020 Serial communication time out
Hitachi WJ200E40 Operator connection · E41 Modbus communication error · E60 Option error (DeviceNet communications error) · E61 Option error (duplicated MAC ID) · E69 Option error (inverter communication error)
Schneider Electric Altivar ATV320CNF Fieldbus module communication interruption error · COF CANopen communication interruption error · SLF1 Modbus communication interruption error · SLF2 PC communication interruption error · SLF3 HMI communication interruption error
Yaskawa V1000bUS Option Communication Error · CE MEMOBUS/Modbus Communication Error · E5 MECHATROLINK Watchdog Timer Error · oFA00 Option Card Connection Error at Option Port CN5 · oFA01 Option Card Fault · oFA03 Option Card Fault
Yaskawa A1000bUS Option Communication Error · CE MEMOBUS/Modbus Communication Error · E5 MECHATROLINK Watchdog Timer Error · oFA00 Option Card Connection Error at Option Port CN5-A · oFA01 Option Card Fault at Option Port CN5-A · oFb00 Option Card Fault at Option Port CN5-B
Yaskawa GA500bCE Bluetooth Communication Fault · bUS Option Communication Error · CE Modbus Communication Error · E5 MECHATROLINK Watchdog Timer Err · oFA00 Option Not Compatible with Port · oFA01 Option Fault/Connection Error
Siemens MICROMASTER 420F0070 CB setpoint fault · F0071 USS (BOP link) setpoint fault · F0072 USS (COMM link) setpoint fault · A0700 CB alarm 1 · A0701 CB alarm 2 · A0702 CB alarm 3
Siemens MICROMASTER 430F0070 CB setpoint fault · F0071 USS (BOP link) setpoint fault · F0072 USS (COMM link) setpoint fault · A0700 CB alarm 1 · A0701 CB alarm 2 · A0702 CB alarm 3
Siemens SINAMICS G110F0072 USS setpoint fault
INVT Goodrive200A (GD200A)CE RS485 communication fault · PCE Keypad communication fault · UPE Parameter upload error · DNE Parameter download error
Mitsubishi Electric FR-D700E.PUE PU disconnection
Danfoss VLT Micro Drive FC 51Alarm 17 Control word timeout · Error 84 The connection between drive and LCP is lost · Error 90 Parameter database busy

07 / More codes

Other Goodrive20 (GD20) codes

Source

INVT, Goodrive20 Series VFD Manual, Version V2.1 (2025), Chapter 6, Fault tracking (6.2.3 VFD faults and solutions).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

UPE won't clear? Get a technician who knows the Goodrive20 (GD20).

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.