F073 on the Allen-Bradley PowerFlex 525 is the “EN Net Loss” fault. A fault stops the drive; it will not restart until the fault is cleared.
The drive stopped receiving messages from its controller (a PLC, a fieldbus master, a keypad or a network) within the allowed time. The drive itself is usually fine; the link to it is not.
- Code
- F073
- Type
- Fault (stops the drive)
- Drive
- Allen-Bradley PowerFlex 525, PowerFlex 523
- Kind of fault
- Communication loss
01 / Causes
What causes F073
Rockwell Automation's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing communication loss faults explains where it usually comes from.
02 / Checks
What to check for F073
In the order Rockwell Automation gives them.
- 01Cycle power.
- 02Check the communications cabling.
- 03Check the EtherNet/IP settings.
- 04Check the external network's status.
Also in the manual
- This fault does not apply to the PowerFlex 523, only the PowerFlex 525.
03 / Clearing it
How to clear F073
- Rockwell's parameter A551 [Fault Clear] resets a fault when set to 1 (Reset Fault); setting it to 2 (Clear Buffer) also clears the fault queue.
- Correct the cause first: F033 means the drive has already used up its automatic restart attempts on a fault that is still there.
Clear it once. If F073 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How communication loss faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check whether the PLC or master is running and still sending to this drive.
- 02Check the communication cable, connectors and termination, and the screen's earth connection.
- 03Compare the drive's address, baud rate and timeout settings with the master's.
- 04Look for drives, contactors or welders near the cable that could be injecting noise.
05 / Repair
When F073 means a repair
If cable, settings and master are all good and only this drive drops out, its communication port or option card may have failed.
If F073 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Allen-Bradley drives, and they arrive knowing what to look for.
06 / Other drives
Communication loss: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F70 I/O Extension Module communication fault · F71 USS setpoint fault · F72 USS/MODBUS setpoint fault |
| Siemens SINAMICS G120 | F01910 Setpoint timeout · F08501 Setpoint timeout · F08502 Monitoring time, sign-of-life expired · F08510 Send configuration data not valid · F08700 Communications error · A01900 PROFIBUS: Configuration telegram faulty |
| Siemens SINAMICS V90 | F1030 Sign-of-life failure for master control · A1920 Drive Bus: Receive setpoints after To · A1932 Drive Bus clock cycle synchronization missing for DSC |
| Siemens MICROMASTER 440 | F0070 CB setpoint fault · F0071 USS (BOP link) setpoint fault · F0072 USS (COMM link) setpoint fault · A0700 CB alarm 1 · A0710 CB communications error · A0711 CB communications error |
| ABB ACS355 | F0010 PANEL LOSS · F0028 SERIAL 1 ERR · F0029 EFB CON FILE · A2005 IO COMM · A2008 PANEL LOSS · A5001 Drive is not responding |
| Delta VFD-E | cE01 Illegal function code · cE02 Illegal data address · cE03 Illegal data value · cE04 Slave device failure · cE10 Communication time-out |
| Delta C2000 | CE1 Illegal command · CE2 Illegal data address · CE3 Illegal data value · CE4 Data is written to read-only address · CE10 MODBUS transmission time-out · CGdE CANopen guarding error |
| Delta ASDA-B2 | AL019 Serial communication error · AL020 Serial communication time out |
| Hitachi WJ200 | E40 Operator connection · E41 Modbus communication error · E60 Option error (DeviceNet communications error) · E61 Option error (duplicated MAC ID) · E69 Option error (inverter communication error) |
| Schneider Electric Altivar ATV320 | CNF Fieldbus module communication interruption error · COF CANopen communication interruption error · SLF1 Modbus communication interruption error · SLF2 PC communication interruption error · SLF3 HMI communication interruption error |
| INVT Goodrive20 (GD20) | CE RS485 communication fault · PCE Keypad communication error · UPE Parameter upload error · DNE Parameter download error |
| Yaskawa V1000 | bUS Option Communication Error · CE MEMOBUS/Modbus Communication Error · E5 MECHATROLINK Watchdog Timer Error · oFA00 Option Card Connection Error at Option Port CN5 · oFA01 Option Card Fault · oFA03 Option Card Fault |
| Yaskawa A1000 | bUS Option Communication Error · CE MEMOBUS/Modbus Communication Error · E5 MECHATROLINK Watchdog Timer Error · oFA00 Option Card Connection Error at Option Port CN5-A · oFA01 Option Card Fault at Option Port CN5-A · oFb00 Option Card Fault at Option Port CN5-B |
| Yaskawa GA500 | bCE Bluetooth Communication Fault · bUS Option Communication Error · CE Modbus Communication Error · E5 MECHATROLINK Watchdog Timer Err · oFA00 Option Not Compatible with Port · oFA01 Option Fault/Connection Error |
| Siemens MICROMASTER 420 | F0070 CB setpoint fault · F0071 USS (BOP link) setpoint fault · F0072 USS (COMM link) setpoint fault · A0700 CB alarm 1 · A0701 CB alarm 2 · A0702 CB alarm 3 |
| Siemens MICROMASTER 430 | F0070 CB setpoint fault · F0071 USS (BOP link) setpoint fault · F0072 USS (COMM link) setpoint fault · A0700 CB alarm 1 · A0701 CB alarm 2 · A0702 CB alarm 3 |
| Siemens SINAMICS G110 | F0072 USS setpoint fault |
| INVT Goodrive200A (GD200A) | CE RS485 communication fault · PCE Keypad communication fault · UPE Parameter upload error · DNE Parameter download error |
| Mitsubishi Electric FR-D700 | E.PUE PU disconnection |
| Danfoss VLT Micro Drive FC 51 | Alarm 17 Control word timeout · Error 84 The connection between drive and LCP is lost · Error 90 Parameter database busy |
07 / More codes
Other PowerFlex 525 codes
Source
Rockwell Automation, PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start, November 2017, 520-QS001B-EN-E, Fault Codes.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Allen-Bradley and is not its authorised service partner.