ACE on the Delta C2000 is the “ACI loss” fault. A fault stops the drive's output. On over-current and over-voltage faults the drive closes its output gate at once and the motor coasts to a stop.
An analog input (usually a 4-20 mA speed reference or feedback) dropped out of its expected range, most often from a broken wire or a failed transmitter.
- Code
- ACE
- Type
- Fault (stops the drive)
- Drive
- Delta C2000
- Kind of fault
- Analog signal loss
01 / Causes
What causes ACE
- The ACI cable is loose or cut.
- The external device has failed.
- A hardware failure.
02 / Checks
What to check for ACE
In the order Delta Electronics gives them.
- 01Tighten the terminal, or replace the cable.
- 02Replace the device.
- 03Check all the wiring. If it is still there, Delta's instruction is to return the drive to the factory for repair.
Also in the manual
- Fault ID 48. A 4 to 20 mA analog input fell below 4 mA. Pr. 03-19 sets the response: 3 stops the drive and shows ACE as a fault, reset manually; 1 and 2 are warnings shown as ANL that clear once the signal is back above 4 mA.
03 / Clearing it
How to clear ACE
- Remove the cause first. Then press STOP/RESET on the keypad, or switch on a multi-function input set to 5 (Reset).
- Most faults can be reset 5 seconds after the fault has cleared. Over-voltage faults reset only once the DC bus is below 90% of the trip level, and overheating faults only once the temperature is 10°C below it.
- Some faults can only be cleared by switching the power off: the current detection and hardware protection faults (cd1 to cd3, Hd0 to Hd3), the watchdog (WDTT), STO Loss (STL1 to STL3) and the CPU error (TRAP).
- After resetting, if the keypad returns to its main page and shows no fault after ESC, the fault is cleared.
Clear it once. If ACE comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How analog signal loss faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Measure the signal at the drive terminals while the system runs.
- 02Check the wiring back to the source for breaks and loose terminals.
- 03Check the transmitter or the PLC's analog output that supplies the signal.
05 / Repair
When ACE means a repair
If the signal is correct at the terminals, the drive's analog input may have failed.
If ACE keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.
06 / Other drives
Analog signal loss: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F80 Signal lost on analog input |
| Siemens SINAMICS G120 | F03505 Analog input, wire break |
| Siemens MICROMASTER 440 | F0080 ADC input signal lost |
| Allen-Bradley PowerFlex 525 | F029 Analog In Loss |
| ABB ACS355 | F0007 AI1 LOSS · F0008 AI2 LOSS · A2006 AI1 LOSS · A2007 AI2 LOSS |
| Delta VFD-E | AErr ACI signal error |
| Schneider Electric Altivar ATV320 | LFF3 AI3 4-20mA loss error |
| INVT Goodrive20 (GD20) | PIDE PID feedback offline fault |
| Siemens MICROMASTER 420 | F0080 ADC input signal lost |
| Siemens MICROMASTER 430 | F0080 ADC input signal lost |
| INVT Goodrive200A (GD200A) | PIDE PID feedback offline fault |
| Danfoss VLT Micro Drive FC 51 | Alarm 2 Live zero error |
07 / More codes
Other C2000 codes
Source
Delta Electronics, C2000 Series User Manual, Issued edition 01, firmware V2.05 (2019-02-13), DELTA_IA-MDS_VFD-C2000_UM_EN_20190213, Chapter 14, Fault Codes and Descriptions.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007