Mitsubishi Electric AC drive (VFD) · fault code

FR-D700 E.ILF: Input phase loss

E.ILF on the Mitsubishi Electric FR-D700 is the “Input phase loss” fault. On a fault the inverter trips (shuts off its output) and outputs a fault signal until it is reset.

One of the three supply phases is missing or weak, so the DC bus ripple rose above a safe level. Running on two phases overloads the rectifier and the capacitors.

Code
E.ILF
Type
Fault (stops the drive)
Drive
Mitsubishi Electric FR-D700, FR-D720, FR-D740, FR-D720S, FR-D710W
Kind of fault
Input phase loss

01 / Causes

What causes E.ILF

  • Input phase loss protection is enabled (Pr. 872 = 1) and one phase of the three-phase supply is lost.
  • It can also trip when the phase-to-phase voltages of the three-phase supply are badly unbalanced.

02 / Checks

What to check for E.ILF

In the order Mitsubishi Electric gives them.

  1. 01Check the three-phase supply cables for a break; wire them properly and repair the break.
  2. 02Check the phase-to-phase voltages are not badly unbalanced.
  3. 03Check the Pr. 872 input phase loss protection setting; set Pr. 872 = 0 (no input phase loss protection) when the three-phase input is badly unbalanced.

Also in the manual

  • Available only on three-phase input models. With Pr. 872 at its initial value 0 this fault does not occur. On the FR-PU04 it shows as Fault 14.

03 / Clearing it

How to clear E.ILF

  • When a fault occurs the inverter trips and outputs a fault signal; warnings, the fan alarm and error messages do not shut off the output.
  • Resetting the inverter clears the electronic thermal relay function's accumulated data.
  • E.OHT (external thermal relay) does not restart the inverter on its own, even if the relay contacts reset automatically: the inverter has to be reset.

Clear it once. If E.ILF comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How input phase loss faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Measure all three phases at the drive input terminals with the drive running under load.
  2. 02Check input fuses, the breaker and the contactor for a blown fuse or a burnt contact.
  3. 03Tighten and inspect supply terminals for heat damage.

05 / Repair

When E.ILF means a repair

If all three phases are healthy at the terminals and the code persists, the drive's rectifier or its supply sensing is at fault.

If E.ILF keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Mitsubishi Electric drives, and they arrive knowing what to look for.

06 / Other drives

Input phase loss: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F20 DC ripple too high
Siemens SINAMICS G120F30011 Line phase failure
Siemens SINAMICS V90F30011 Line phase failure in main circuit
Siemens MICROMASTER 440F0020 Line supply phase missing
ABB ACS355F0022 SUPPLY PHASE · A2026 INPUT PHASE LOSS
Delta VFD-EPHL Phase loss
Delta C2000OrP Phase loss protection
Delta ASDA-B2AL022 Main circuit power lack phase
Schneider Electric Altivar ATV320PHF Input phase loss error
INVT Goodrive20 (GD20)SPI Phase loss on input side
Yaskawa V1000PF Input Phase Loss
Yaskawa A1000PF Input Phase Loss
Yaskawa GA500PF Input Phase Loss
Siemens MICROMASTER 430F0020 Line supply phase missing
INVT Goodrive200A (GD200A)SPI Phase loss on input side
Danfoss VLT Micro Drive FC 51Alarm 4 Mains phase loss

07 / More codes

Other FR-D700 codes

Source

Mitsubishi Electric, FR-D700 Instruction Manual, March 2012 (revision D), IB(NA)-0600368ENG-D, 5.3 Causes and corrective actions.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Mitsubishi Electric and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

E.ILF won't clear? Get a technician who knows the FR-D700.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.