MachineryFix

Mitsubishi Electric AC drive (VFD) · fault code

FR-D700 E.BE: Brake transistor alarm detection

E.BE on the Mitsubishi Electric FR-D700 is the “Brake transistor alarm detection” fault. On a fault the inverter trips (shuts off its output) and outputs a fault signal until it is reset.

The braking resistor is absorbing more energy than its rating allows. The machine is being stopped harder or more often than the resistor was sized for.

Code
E.BE
Type
Fault (stops the drive)
Drive
Mitsubishi Electric FR-D700, FR-D720, FR-D740, FR-D720S, FR-D710W
Kind of fault
Braking resistor

01 / Causes

What causes E.BE

  • A brake transistor fault occurred, for example from large regenerative energy from the motor, and the inverter tripped.

02 / Checks

What to check for E.BE

In the order Mitsubishi Electric gives them.

  1. 01Reduce the load inertia.
  2. 02Check the brake is not used too often.
  3. 03Check the correct brake resistor is selected.
  4. 04Replace the inverter.

Also in the manual

  • Mitsubishi says the inverter must be powered off immediately when this occurs.

03 / Clearing it

How to clear E.BE

  • When a fault occurs the inverter trips and outputs a fault signal; warnings, the fan alarm and error messages do not shut off the output.
  • Resetting the inverter clears the electronic thermal relay function's accumulated data.
  • E.OHT (external thermal relay) does not restart the inverter on its own, even if the relay contacts reset automatically: the inverter has to be reset.

Clear it once. If E.BE comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How braking resistor faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Compare the stopping duty (how often, from what speed, how much inertia) with the resistor's rating.
  2. 02Check the resistor's resistance against the drive manual's minimum.
  3. 03Check the resistor for heat damage and its wiring for loose terminals.

05 / Repair

When E.BE means a repair

A burnt resistor or a shorted braking transistor in the drive has to be replaced.

If E.BE keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Mitsubishi Electric drives, and they arrive knowing what to look for.

06 / Other drives

Braking resistor: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20A535 Braking resistor overload
Siemens SINAMICS G120F07806 Regenerative power limit exceeded
Siemens SINAMICS V90A52901 Braking resistor reaches alarm threshold
Siemens MICROMASTER 440A0535 Brake resistor hot
Delta C2000bF Brake transistor error
Delta ASDA-B2AL005 Regeneration error · AL085 Regeneration error
Hitachi WJ200E06 Braking resistor overload protection
INVT Goodrive20 (GD20)bCE Braking unit fault
Yaskawa V1000oL7 High-Slip Braking oL · rH Braking Resistor Overheat · rr Dynamic Braking Transistor
Yaskawa A1000boL Braking Transistor Overload Fault · oL7 High Slip Braking oL · rF Braking Resistor Fault · rH Braking Resistor Overheat · rr Dynamic Braking Transistor
Yaskawa GA500boL Braking Transistor Overload Fault · oL7 High Slip Braking Overload · rF Braking Resistor Fault · rH Braking Resistor Overheat · rr Dynamic Braking Transistor Fault
INVT Goodrive200A (GD200A)bCE Braking unit fault
Danfoss VLT Micro Drive FC 51Alarm 25 Brake resistor short circuit · Alarm 27 Brake chopper fault · Alarm 28 Brake check failed · Alarm 63 Mechanical brake low

07 / More codes

Other FR-D700 codes

Source

Mitsubishi Electric, FR-D700 Instruction Manual, March 2012 (revision D), IB(NA)-0600368ENG-D, 5.3 Causes and corrective actions.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Mitsubishi Electric and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

E.BE won't clear? Get a technician who knows the FR-D700.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.