E.OHT on the Mitsubishi Electric FR-D700 is the “External thermal relay operation” fault. On a fault the inverter trips (shuts off its output) and outputs a fault signal until it is reset.
Something outside the drive told it to stop: a digital input or a control word bit set up as a fault input. The drive is reporting another device's trip.
- Code
- E.OHT
- Type
- Fault (stops the drive)
- Drive
- Mitsubishi Electric FR-D700, FR-D720, FR-D740, FR-D720S, FR-D710W
- Kind of fault
- External fault
01 / Causes
What causes E.OHT
- The external thermal relay for motor overheat protection, or a temperature relay inside the motor, switched on (contacts opened), so the inverter stopped its output.
02 / Checks
What to check for E.OHT
In the order Mitsubishi Electric gives them.
- 01Check whether the motor is overheating, and reduce the load and how often it runs.
- 02Check the OH signal (7) is set correctly in one of Pr. 178 to Pr. 182 (input terminal function selection).
Also in the manual
- Only works with the OH signal assigned to an input terminal. Even if the relay contacts reset automatically, the inverter does not restart until it is reset.
03 / Clearing it
How to clear E.OHT
- When a fault occurs the inverter trips and outputs a fault signal; warnings, the fan alarm and error messages do not shut off the output.
- Resetting the inverter clears the electronic thermal relay function's accumulated data.
- E.OHT (external thermal relay) does not restart the inverter on its own, even if the relay contacts reset automatically: the inverter has to be reset.
Clear it once. If E.OHT comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How external fault faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Find which input or control word is set as the external fault source in the drive's parameters.
- 02Trace that input to the device driving it (a thermal switch, pressure switch, PLC output or interlock) and find out why it tripped.
05 / Repair
When E.OHT means a repair
The fix is usually on the device that raised the input, not in the drive.
If E.OHT keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Mitsubishi Electric drives, and they arrive knowing what to look for.
06 / Other drives
External fault: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F85 External fault |
| Siemens SINAMICS G120 | F07860 External fault 1 · F07861 External fault 2 · F07862 External fault 3 · A07850 External alarm 1 · A07851 External alarm 2 · A07852 External alarm 3 |
| Siemens MICROMASTER 440 | F0085 External fault |
| Allen-Bradley PowerFlex 525 | F002 Auxiliary Input · F094 Function Loss |
| ABB ACS355 | F0014 EXT FAULT 1 · F0015 EXT FAULT 2 · F0030 FORCE TRIP · A2021 START ENABLE 1 MISSING · A2022 START ENABLE 2 MISSING |
| Delta VFD-E | EF External fault |
| Delta C2000 | LMIT Limit error · EF External fault · EF1 Emergency stop · bb External base block · ydc Y-connection / Δ-connection switch error · Brk External brake error |
| Hitachi WJ200 | E12 External trip · E36 Braking error · E50 EzSQ user trip 0 · E51 EzSQ user trip 1 · E52 EzSQ user trip 2 · E53 EzSQ user trip 3 |
| Schneider Electric Altivar ATV320 | BLF Brake control error · BRF Brake feedback error · EPF1 External error · EPF2 Fieldbus external detected error · FCF1 Output contactor closed error · FCF2 Output contactor opened error |
| INVT Goodrive20 (GD20) | EF External fault |
| Yaskawa V1000 | dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (input terminal S1) · EF2 External Fault (input terminal S2) · EF3 External Fault (input terminal S3) · EF4 External Fault (input terminal S4) |
| Yaskawa A1000 | dWAL DriveWorksEZ Fault · dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (input terminal S1) · EF2 External Fault (input terminal S2) · EF3 External Fault (input terminal S3) |
| Yaskawa GA500 | dWF2 DriveWorksEZ Fault 2 · dWF3 DriveWorksEZ Fault 3 · dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (Terminal S1) · EF2 External Fault (Terminal S2) |
| Siemens MICROMASTER 420 | F0085 External fault |
| Siemens MICROMASTER 430 | F0085 External fault |
| Siemens SINAMICS G110 | F0085 External fault |
| INVT Goodrive200A (GD200A) | EF External fault |
07 / More codes
Other FR-D700 codes
Source
Mitsubishi Electric, FR-D700 Instruction Manual, March 2012 (revision D), IB(NA)-0600368ENG-D, 5.3 Causes and corrective actions.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Mitsubishi Electric and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007