FR-D700 E.THT: Inverter overload trip (electronic thermal O/L relay function)

E.THT on the Mitsubishi Electric FR-D700 is the “Inverter overload trip (electronic thermal O/L relay function)” fault. On a fault the inverter trips (shuts off its output) and outputs a fault signal until it is reset.

The drive's own overload model says it has carried more current, for longer, than its rating allows. The drive is undersized for the duty, or the load has grown.

Code
E.THT
Type
Fault (stops the drive)
Drive
Mitsubishi Electric FR-D700, FR-D720, FR-D740, FR-D720S, FR-D710W
Kind of fault
Drive overload

01 / Causes

What causes E.THT

  • The output transistor temperature exceeded the protection level while at least the rated inverter current flowed without an overcurrent trip (200% or less), so the electronic thermal relay stopped the output. Overload capacity is 150% for 60 s and 200% for 0.5 s.

02 / Checks

What to check for E.THT

In the order Mitsubishi Electric gives them.

  1. 01Check the acceleration and deceleration times are not too short, and lengthen them.
  2. 02Check the torque boost setting is not too large (or too small), and adjust it.
  3. 03Check the load pattern selection suits the machine's load pattern.
  4. 04Check whether the motor is used under overload, and reduce the load.
  5. 05Check the surrounding air temperature is not too high, and bring it within the specification.

03 / Clearing it

How to clear E.THT

  • When a fault occurs the inverter trips and outputs a fault signal; warnings, the fan alarm and error messages do not shut off the output.
  • Resetting the inverter clears the electronic thermal relay function's accumulated data.
  • E.OHT (external thermal relay) does not restart the inverter on its own, even if the relay contacts reset automatically: the inverter has to be reset.

Clear it once. If E.THT comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How drive overload faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Record the running current and compare it with the drive's rated current.
  2. 02Look for a change in the load: a dragging bearing, a tighter belt, a heavier product, a blocked impeller.
  3. 03Check acceleration time and boost settings; long periods at high torque add up quickly.

05 / Repair

When E.THT means a repair

If the current is well within the rating and the code keeps returning, the drive's current measurement should be checked on the bench.

If E.THT keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Mitsubishi Electric drives, and they arrive knowing what to look for.

06 / Other drives

Drive overload: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F5 Inverter I2t · A505 Inverter I2t
Siemens SINAMICS G120F30005 I2t inverter overload · A07805 Drive: Power unit overload I2t
Siemens SINAMICS V90F30005 Power unit: Overload I2t
Siemens MICROMASTER 440F0005 Inverter I2T · A0505 Inverter I2T
Allen-Bradley PowerFlex 525F064 Drive Overload
Delta VFD-EoL Overload
Delta C2000oL Over load · oL3 Overload protection at low frequency
Hitachi WJ200E38 Low-speed overload protection
INVT Goodrive20 (GD20)OL2 VFD overload
Yaskawa V1000oL2 Drive Overload
Yaskawa A1000oL2 Drive Overload
Yaskawa GA500oL2 Drive Overload
Siemens MICROMASTER 420F0005 Inverter I2t · A0505 Inverter I2t
Siemens MICROMASTER 430F0005 Inverter I2t · A0505 Inverter I2t · A0506 Inverter load duty cycle
Siemens SINAMICS G110F0005 Inverter I2t · A0505 Inverter I2t
INVT Goodrive200A (GD200A)OL2 VFD overload
Danfoss VLT Micro Drive FC 51Alarm 9 Inverter overloaded

07 / More codes

Other FR-D700 codes

Source

Mitsubishi Electric, FR-D700 Instruction Manual, March 2012 (revision D), IB(NA)-0600368ENG-D, 5.3 Causes and corrective actions.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Mitsubishi Electric and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007