E.LF on the Mitsubishi Electric FR-D700 is the “Output phase loss” fault. On a fault the inverter trips (shuts off its output) and outputs a fault signal until it is reset.
The drive sees current in only two of the three motor phases. A phase is open somewhere between the drive and the motor winding.
- Code
- E.LF
- Type
- Fault (stops the drive)
- Drive
- Mitsubishi Electric FR-D700, FR-D720, FR-D740, FR-D720S, FR-D710W
- Kind of fault
- Output phase loss
01 / Causes
What causes E.LF
- One of the three output phases (U, V, W) was lost while running (except during DC injection braking or below 1 Hz), so the inverter stopped its output.
02 / Checks
What to check for E.LF
In the order Mitsubishi Electric gives them.
- 01Check the wiring and that the motor is normal; wire the cables properly.
- 02Check the motor's capacity is not smaller than the inverter's.
- 03Check the Pr. 251 output phase loss protection setting.
03 / Clearing it
How to clear E.LF
- When a fault occurs the inverter trips and outputs a fault signal; warnings, the fan alarm and error messages do not shut off the output.
- Resetting the inverter clears the electronic thermal relay function's accumulated data.
- E.OHT (external thermal relay) does not restart the inverter on its own, even if the relay contacts reset automatically: the inverter has to be reset.
Clear it once. If E.LF comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How output phase loss faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Isolate and check continuity of each phase from the drive terminals to the motor terminals.
- 02Inspect any contactor, isolator or junction box in the motor circuit.
- 03Measure winding resistance phase to phase at the motor.
05 / Repair
When E.LF means a repair
When cable, connections and windings are all good, an output phase in the drive itself may be open.
If E.LF keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Mitsubishi Electric drives, and they arrive knowing what to look for.
06 / Other drives
Output phase loss: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | A922 No load applied to inverter |
| Siemens SINAMICS G120 | F30015 Motor cable phase failure |
| Siemens SINAMICS V90 | F7410 Current controller output limited · F30015 Phase failure motor cable |
| Siemens MICROMASTER 440 | F0023 Output fault · F0422 No load applied to inverter · A0523 Output fault · A0922 No load at the inverter |
| Allen-Bradley PowerFlex 525 | F021 Output Ph Loss |
| ABB ACS355 | F0034 MOTOR PHASE |
| Delta C2000 | OPHL Output phase loss |
| Delta ASDA-B2 | AL031 Incorrect wiring of the motor power line U, V, W, GND |
| Schneider Electric Altivar ATV320 | OPF1 Single output phase loss error · OPF2 Output phase loss error |
| INVT Goodrive20 (GD20) | SPO Phase loss on output side |
| Yaskawa V1000 | LF Output Phase Loss · LF2 Output current imbalance |
| Yaskawa A1000 | LF Output Phase Loss · LF2 Output Current Imbalance · LF3 Power Unit Output Phase Loss 3 · UnbC Current Unbalance |
| Yaskawa GA500 | LF Output Phase Loss · LF2 Output Current Imbalance |
| Siemens MICROMASTER 430 | F0023 Output fault · A0523 Output fault |
| INVT Goodrive200A (GD200A) | SPO Phase loss on output side |
| Danfoss VLT Micro Drive FC 51 | Alarm 30 Motor phase U missing · Alarm 31 Motor phase V missing · Alarm 32 Motor phase W missing |
07 / More codes
Other FR-D700 codes
Source
Mitsubishi Electric, FR-D700 Instruction Manual, March 2012 (revision D), IB(NA)-0600368ENG-D, 5.3 Causes and corrective actions.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Mitsubishi Electric and is not its authorised service partner.