MachineryFix

Mitsubishi Electric AC drive (VFD) · alarm code

FR-D700 oL: Stall prevention (overvoltage)

oL on the Mitsubishi Electric FR-D700 is the “Stall prevention (overvoltage)” alarm. Error messages, warnings and the fan alarm are shown while the inverter keeps its output on.

The voltage on the drive's internal DC bus rose above its limit. Either the incoming supply is too high, or the motor is feeding energy back into the drive because the load is being slowed faster than friction alone would slow it, or an overhauling load is driving the motor.

Code
oL
Type
Alarm (warning)
Drive
Mitsubishi Electric FR-D700, FR-D720, FR-D740, FR-D720S, FR-D710W
Kind of fault
DC bus overvoltage

01 / Causes

What causes oL

  • During deceleration the motor's regenerative energy exceeded what the inverter can absorb, so the inverter stopped lowering the frequency to prevent an overvoltage trip; deceleration resumes once the energy falls.
  • With the regeneration avoidance function selected (Pr. 882 = 1), the inverter raises the speed instead to prevent an overvoltage trip.

02 / Checks

What to check for oL

In the order Mitsubishi Electric gives them.

  1. 01Check for a sudden speed reduction.
  2. 02Check whether the regeneration avoidance function (Pr. 882, Pr. 883, Pr. 885, Pr. 886) is in use.
  3. 03Lengthen the deceleration time in Pr. 8 (the deceleration time may change while oL is active).

Also in the manual

  • Mitsubishi lists this as a warning: the inverter's output is not shut off.

03 / Clearing it

How to clear oL

Error messages, warnings and the fan alarm are shown while the inverter keeps its output on.

If oL stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.

04 / On site

How dc bus overvoltage faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Note when it trips. Overvoltage while stopping almost always means regenerated energy; overvoltage at standstill points at the supply.
  2. 02Measure the incoming supply between phases, at the drive terminals, during the time the trip happens.
  3. 03Compare the deceleration time with the inertia of the load: fans, flywheels and loaded conveyors need long ramps or a braking resistor.
  4. 04If a braking resistor is fitted, check its resistance and wiring and that the braking function is enabled in the drive.

05 / Repair

When oL means a repair

If the supply is normal, the ramp is long and the fault still appears, the braking chopper, the resistor or the drive's voltage measurement may have failed.

If oL keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Mitsubishi Electric drives, and they arrive knowing what to look for.

06 / Other drives

DC bus overvoltage: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F2 Overvoltage · A502 Overvoltage limit · A910 Vdc_max controller deactivated · A911 Vdc_max controller active
Siemens SINAMICS G120F30002 DC-link voltage overvoltage · A07400 DC-link voltage maximum controller active · A30502 DC-link overvoltage
Siemens SINAMICS V90F7404 Upper DC link voltage threshold reached · F30002 DC link voltage, overvoltage
Siemens MICROMASTER 440F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active
Allen-Bradley PowerFlex 525F005 OverVoltage
ABB ACS355F0002 DC OVERVOLT · A2002 OVERVOLTAGE
Delta VFD-Eov Over-voltage
Delta C2000ovA Over-voltage during acceleration · ovd Over-voltage during deceleration · ovn Over-voltage at constant speed · ovS Over-voltage at stop
Delta ASDA-B2AL002 Over voltage
Hitachi WJ200E07 Over-voltage protection · E15 Input over-voltage
Schneider Electric Altivar ATV320OBF DC bus overvoltage error · OSF Supply mains overvoltage error
INVT Goodrive20 (GD20)OV1 Overvoltage during acceleration · OV2 Overvoltage during deceleration · OV3 Overvoltage during constant speed running
Yaskawa V1000ov Overvoltage
Yaskawa A1000ov Overvoltage
Yaskawa GA500ov Overvoltage
Siemens MICROMASTER 420F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active
Siemens MICROMASTER 430F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active
Siemens SINAMICS G110F0002 Overvoltage · A0502 Overvoltage limit · A0910 Vdc-max controller de-activated · A0911 Vdc-max controller active
INVT Goodrive200A (GD200A)OV1 Overvoltage during acceleration · OV2 Overvoltage during deceleration · OV3 Overvoltage during constant speed running
Danfoss VLT Micro Drive FC 51Alarm 7 DC overvoltage

07 / More codes

Other FR-D700 codes

Source

Mitsubishi Electric, FR-D700 Instruction Manual, March 2012 (revision D), IB(NA)-0600368ENG-D, 5.3 Causes and corrective actions.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Mitsubishi Electric and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

oL won't clear? Get a technician who knows the FR-D700.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.