F0453 on the Siemens MICROMASTER 440 is the “Motor stalled” fault. On a fault the inverter switches off and shows the fault code; it will not run until the fault is reset.
The drive could not get the motor to follow the commanded speed: it sat at its current limit for too long. The load is too heavy for the ramp, the motor is jammed, or the motor is connected or set up wrongly.
- Code
- F0453
- Type
- Fault (stops the drive)
- Drive
- Siemens MICROMASTER 440
- Kind of fault
- Motor stall
01 / Causes
What causes F0453
- The ramp up or down is too steep.
- The inverter was started on a motor that was still turning, without flying restart.
- The motor is connected incorrectly.
- The motor is too small.
- The voltage boost for sensorless vector control (P1611) is too low.
02 / Checks
What to check for F0453
In the order Siemens gives them.
- 01Check the motor connections.
- 02Increase the ramp-up time (P1120) or ramp-down time (P1121).
- 03Turn on flying restart (P1200).
- 04Use a larger motor.
- 05Increase the voltage boost (P1611) for sensorless vector control.
- 06Use vector control with an encoder, or V/f control (P1300 below 20), instead of sensorless vector control.
03 / Clearing it
How to clear F0453
- Reset a fault in one of three ways: switch the power off and on, press the Fn button on the BOP or AOP, or use digital input 3 (its default setting).
- Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949, the time of the fault in r0948 and the number of stored faults in P0952.
- Alarm codes are stored in r2110 (A0503 is stored as 503).
Clear it once. If F0453 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How motor stall faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the load turns freely and nothing is jammed.
- 02Lengthen the acceleration time and check the current limit setting.
- 03Check motor connections (star or delta) against the rating plate and the drive's motor data.
05 / Repair
When F0453 means a repair
A free-turning load, correct setup and repeated stalls point at a motor winding fault or a drive output problem.
If F0453 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Motor stall: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F07900 Motor blocked · F07902 Motor stalled · A07903 Motor speed deviation |
| Siemens SINAMICS V90 | F7450 Standstill monitoring has responded · F7452 Following error too high · F7900 Motor blocked/speed controller at its limit |
| Allen-Bradley PowerFlex 525 | F006 Motor Stalled |
| ABB ACS355 | F0012 MOTOR STALL · A2012 MOTOR STALL |
| Delta C2000 | oSL Over slip error · SdRv Reverse direction of the speed feedback · SdOr Over speed rotation feedback · SdDe Large deviation of speed feedback · SfLK PMLess shaft lock |
| Delta ASDA-B2 | AL009 Excessive deviation of position command |
| Schneider Electric Altivar ATV320 | ANF Load slipping error · SSF Torque limitation error |
| INVT Goodrive20 (GD20) | dEu Speed deviation fault |
| Yaskawa V1000 | STo Motor Pull Out or Step Out Detection |
| Yaskawa A1000 | LSo LSo Fault · STo Pull-Out Detection |
| Yaskawa GA500 | LSo Low Speed Motor Step-Out · STPo Motor Step-Out Detected |
| Mitsubishi Electric FR-D700 | E.OLT Stall prevention stop |
| Danfoss VLT Micro Drive FC 51 | Warning 12 Torque limit |
07 / More codes
Other MICROMASTER 440 codes
Source
Siemens, MICROMASTER 440 Parameter List, Issue 01/06, 6SE6400-5BB00-0BP0, Section 5, Faults and Alarms.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007