Siemens AC drive (VFD) · fault code

MICROMASTER 440 F0085: External fault

F0085 on the Siemens MICROMASTER 440 is the “External fault” fault. On a fault the inverter switches off and shows the fault code; it will not run until the fault is reset.

Something outside the drive told it to stop: a digital input or a control word bit set up as a fault input. The drive is reporting another device's trip.

Code
F0085
Type
Fault (stops the drive)
Drive
Siemens MICROMASTER 440
Kind of fault
External fault

01 / Causes

What causes F0085

  • An external fault commanded through the terminals.

02 / Checks

What to check for F0085

In the order Siemens gives them.

  1. 01Disable the terminal input that triggers the fault, once the external cause is found.

03 / Clearing it

How to clear F0085

  • Reset a fault in one of three ways: switch the power off and on, press the Fn button on the BOP or AOP, or use digital input 3 (its default setting).
  • Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949, the time of the fault in r0948 and the number of stored faults in P0952.
  • Alarm codes are stored in r2110 (A0503 is stored as 503).

Clear it once. If F0085 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How external fault faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Find which input or control word is set as the external fault source in the drive's parameters.
  2. 02Trace that input to the device driving it (a thermal switch, pressure switch, PLC output or interlock) and find out why it tripped.

05 / Repair

When F0085 means a repair

The fix is usually on the device that raised the input, not in the drive.

If F0085 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

External fault: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F85 External fault
Siemens SINAMICS G120F07860 External fault 1 · F07861 External fault 2 · F07862 External fault 3 · A07850 External alarm 1 · A07851 External alarm 2 · A07852 External alarm 3
Allen-Bradley PowerFlex 525F002 Auxiliary Input · F094 Function Loss
ABB ACS355F0014 EXT FAULT 1 · F0015 EXT FAULT 2 · F0030 FORCE TRIP · A2021 START ENABLE 1 MISSING · A2022 START ENABLE 2 MISSING
Delta VFD-EEF External fault
Delta C2000LMIT Limit error · EF External fault · EF1 Emergency stop · bb External base block · ydc Y-connection / Δ-connection switch error · Brk External brake error
Hitachi WJ200E12 External trip · E36 Braking error · E50 EzSQ user trip 0 · E51 EzSQ user trip 1 · E52 EzSQ user trip 2 · E53 EzSQ user trip 3
Schneider Electric Altivar ATV320BLF Brake control error · BRF Brake feedback error · EPF1 External error · EPF2 Fieldbus external detected error · FCF1 Output contactor closed error · FCF2 Output contactor opened error
INVT Goodrive20 (GD20)EF External fault
Yaskawa V1000dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (input terminal S1) · EF2 External Fault (input terminal S2) · EF3 External Fault (input terminal S3) · EF4 External Fault (input terminal S4)
Yaskawa A1000dWAL DriveWorksEZ Fault · dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (input terminal S1) · EF2 External Fault (input terminal S2) · EF3 External Fault (input terminal S3)
Yaskawa GA500dWF2 DriveWorksEZ Fault 2 · dWF3 DriveWorksEZ Fault 3 · dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (Terminal S1) · EF2 External Fault (Terminal S2)
Siemens MICROMASTER 420F0085 External fault
Siemens MICROMASTER 430F0085 External fault
Siemens SINAMICS G110F0085 External fault
INVT Goodrive200A (GD200A)EF External fault
Mitsubishi Electric FR-D700E.OHT External thermal relay operation · PS PU stop

07 / More codes

Other MICROMASTER 440 codes

Source

Siemens, MICROMASTER 440 Parameter List, Issue 01/06, 6SE6400-5BB00-0BP0, Section 5, Faults and Alarms.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

F0085 won't clear? Get a technician who knows the MICROMASTER 440.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.