A01053 on the Siemens SINAMICS G120 is the “System overload measured” alarm. An alarm has no direct effect on the inverter. It disappears once the cause is removed and needs no acknowledgement.
The drive's own electronics reported a problem: a self-test, a processor, an internal link or the power module's identification. There is nothing in the machine to fix.
- Code
- A01053
- Type
- Alarm (warning)
- Drive
- Siemens SINAMICS G120, CU240B-2, CU240E-2
- Kind of fault
- Internal drive fault
01 / Causes
What causes A01053
- The Control Unit's maximum computing power was exceeded.
02 / Checks
What to check for A01053
In the order Siemens gives them.
- 01Use only one data record (CDS and DDS).
- 02Use only the basic safety functions.
- 03Deactivate the technology controller.
- 04Use the simple ramp-function generator instead of the extended one.
- 05Do not use free function blocks, or reduce their sampling time.
03 / Clearing it
How to clear A01053
An alarm has no direct effect on the inverter. It disappears once the cause is removed and needs no acknowledgement.
If A01053 stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.
04 / On site
How internal drive fault faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Power-cycle the drive and note whether the fault returns.
- 02Check for electrical noise: screened cables, earthing and an EMC filter where the manual calls for one.
- 03Note the fault value the drive shows with the code; the manufacturer uses it to narrow the cause.
05 / Repair
When A01053 means a repair
If the fault survives a power cycle, the drive needs a bench repair or replacement.
If A01053 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Internal drive fault: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F52 Inverter software fault · F60 Asic timeout · F100 Watchdog reset · F101 Stack overflow · F200 Script error · F350 Configuration vector for the inverter failed |
| Siemens SINAMICS V90 | F1000 Internal software error · F1001 FloatingPoint exception · F1002 Internal software error · F1003 Acknowledgement delay when accessing the memory · F1015 Internal software error · F1018 Booting has been interrupted several times |
| Siemens MICROMASTER 440 | F0040 Fault, for automatic calibration · F0052 Power stack fault · F0053 I/O EEPROM fault · F0054 Incorrect I/O module · F0060 Asic time slice overflow · F0101 Stack overflow |
| Allen-Bradley PowerFlex 525 | F070 Power Unit · F105 C Connect Err · F106 Incompat C-P · F107 Replaced C-P · F109 Mismatch C-P · F110 Keypad Membrane |
| ABB ACS355 | F0021 CURR MEAS · F0027 CONFIG FILE · F0036 INCOMPATIBLE SW · F0101 SERF CORRUPT · F0103 SERF MACRO · F0201 DSP T1 OVERLOAD |
| Delta VFD-E | HPF1 CC, OC hardware protection failure · HPF2 OV hardware protection failure · HPF3 GFF hardware protection failure · HPF4 OC hardware protection failure · codE Software protection failure · cF3.0 U-phase error |
| Delta C2000 | cd1 U-phase error · cd2 V-phase error · cd3 W-phase error · Hd0 cc hardware failure · Hd1 oc hardware error · Hd2 ov hardware error |
| Delta ASDA-B2 | AL012 Adjustment error · AL555 System failure · AL880 System failure |
| Hitachi WJ200 | E10 Current detection error · E11 CPU error · E22 CPU communication error · E25 Main circuit error · E30 Driver error · E63 Option error |
| Schneider Electric Altivar ATV320 | CRF1 Precharge capacitor error · ILF Internal link error · INF1 Internal error 1 (Rating) · INF2 Internal error 2 (Soft) · INF3 Internal error 3 (Intern Comm) · INF4 Internal error 4 (Manufacturing) |
| INVT Goodrive20 (GD20) | ItE Current detection fault |
| Yaskawa V1000 | CoF Current Offset Fault · CPF02 A/D Conversion Error · CPF03 PWM Data Error · CPF07 Terminal Board Communications Error · CPF08 EEPROM Serial Communication Fault · CPF11 RAM Fault |
| Yaskawa A1000 | CoF Current Offset Fault · CPF02 A/D Conversion Error · CPF03 Control Board Connection Error · CPF07 Terminal Board Connection Error · CPF08 Terminal Board Connection Error · CPF11 RAM Fault |
| Yaskawa GA500 | bAT Keypad Battery Low Voltage · CoF Current Offset Fault · CPF00 Control Circuit Error · CPF01 Control Circuit Error · CPF02 Control Circuit Error · CPF03 Control Circuit Error |
| Siemens MICROMASTER 420 | F0052 Power stack fault · F0060 Asic time slice overflow · F0101 Stack overflow · F0450 Failure BIST tests · A0600 RTOS data loss alarm |
| Siemens MICROMASTER 430 | F0052 Power stack fault · F0054 Incorrect I/O module · F0060 Asic time slice overflow · F0101 Stack overflow · F0450 Failure BIST tests · A0522 Read I2C, time exceeded |
| Siemens SINAMICS G110 | F0052 Power stack fault · F0060 Asic timeout · F0100 Watchdog reset · F0101 Stack overflow |
| INVT Goodrive200A (GD200A) | ItE Current detection fault |
| Mitsubishi Electric FR-D700 | E.CPU CPU fault · E.IOH Inrush current limit circuit fault |
| Danfoss VLT Micro Drive FC 51 | Alarm 38 Internal fault · Alarm 46 Gate drive voltage fault · Alarm 47 Control voltage fault |
07 / More codes
Other SINAMICS G120 codes
Source
Siemens, SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units, Operating Instructions, 04/2018, FW V4.7 SP10, A5E34259001B AF, 8.6 List of alarms and faults (Table 8-7, the most important alarms and faults).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007