F07806 on the Siemens SINAMICS G120 is the “Regenerative power limit exceeded” fault. A fault generally switches the motor off, and it must be acknowledged before the inverter runs again.
The braking resistor is absorbing more energy than its rating allows. The machine is being stopped harder or more often than the resistor was sized for.
- Code
- F07806
- Type
- Fault (stops the drive)
- Drive
- Siemens SINAMICS G120, CU240B-2, CU240E-2
- Kind of fault
- Braking resistor
01 / Causes
What causes F07806
Siemens's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing braking resistor faults explains where it usually comes from.
02 / Checks
What to check for F07806
In the order Siemens gives them.
- 01Lengthen the deceleration ramp.
- 02Reduce the driving load.
- 03Use a power unit with higher energy recovery capability.
- 04For vector control, the regenerative power limit in p1531 can be lowered until the fault no longer occurs.
03 / Clearing it
How to clear F07806
- Remove the cause, then acknowledge the fault in one of four ways: through bit 7 of PROFIdrive control word 1 (r2090.7), through a digital input set for acknowledgement, from the operator panel, or by switching the inverter's supply off and on.
- Faults found by the inverter's own monitoring of its hardware and firmware can only be acknowledged by switching the supply voltage off and on.
- Alarms need no acknowledgement: they disappear once the cause is removed.
Clear it once. If F07806 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How braking resistor faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Compare the stopping duty (how often, from what speed, how much inertia) with the resistor's rating.
- 02Check the resistor's resistance against the drive manual's minimum.
- 03Check the resistor for heat damage and its wiring for loose terminals.
05 / Repair
When F07806 means a repair
A burnt resistor or a shorted braking transistor in the drive has to be replaced.
If F07806 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Braking resistor: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | A535 Braking resistor overload |
| Siemens SINAMICS V90 | A52901 Braking resistor reaches alarm threshold |
| Siemens MICROMASTER 440 | A0535 Brake resistor hot |
| Delta C2000 | bF Brake transistor error |
| Delta ASDA-B2 | AL005 Regeneration error · AL085 Regeneration error |
| Hitachi WJ200 | E06 Braking resistor overload protection |
| INVT Goodrive20 (GD20) | bCE Braking unit fault |
| Yaskawa V1000 | oL7 High-Slip Braking oL · rH Braking Resistor Overheat · rr Dynamic Braking Transistor |
| Yaskawa A1000 | boL Braking Transistor Overload Fault · oL7 High Slip Braking oL · rF Braking Resistor Fault · rH Braking Resistor Overheat · rr Dynamic Braking Transistor |
| Yaskawa GA500 | boL Braking Transistor Overload Fault · oL7 High Slip Braking Overload · rF Braking Resistor Fault · rH Braking Resistor Overheat · rr Dynamic Braking Transistor Fault |
| INVT Goodrive200A (GD200A) | bCE Braking unit fault |
| Mitsubishi Electric FR-D700 | E.BE Brake transistor alarm detection · RB Regenerative brake pre-alarm |
| Danfoss VLT Micro Drive FC 51 | Alarm 25 Brake resistor short circuit · Alarm 27 Brake chopper fault · Alarm 28 Brake check failed · Alarm 63 Mechanical brake low |