MachineryFix

Yaskawa AC drive (VFD) · fault code

V1000 oL7: High-Slip Braking oL

oL7 on the Yaskawa V1000 is the “High-Slip Braking oL” fault. A fault interrupts the drive's output and the motor coasts to a stop (unless set to stop another way). The drive stays inoperable until the fault is reset, and a digital output set for fault (H2-oo = E) closes.

The braking resistor is absorbing more energy than its rating allows. The machine is being stopped harder or more often than the resistor was sized for.

Code
oL7
Type
Fault (stops the drive)
Drive
Yaskawa V1000
Kind of fault
Braking resistor

01 / Causes

What causes oL7

  • During High-slip Braking the output frequency stayed constant for longer than n3-04.
  • Too much load inertia, the motor driven by the load, something restricting deceleration, or an n3-04 time too short.

02 / Checks

What to check for oL7

In the order Yaskawa gives them.

  1. 01Where High-slip Braking is not used, shorten the deceleration (C1-02, -04, -06, -08) and use a braking resistor.
  2. 02Increase n3-04, or fit a thermal relay and set n3-04 to its maximum.

03 / Clearing it

How to clear oL7

  • Fix the cause, then reset with the reset key on the digital operator, or by closing and opening terminal S4, which is the fault reset input by default.
  • If neither clears it, switch off the drive's main power and switch it back on once the operator display has gone out.
  • Some faults need a condition met before they reset: oL1 cannot be reset until monitor U4-16 is below 100.

Clear it once. If oL7 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How braking resistor faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Compare the stopping duty (how often, from what speed, how much inertia) with the resistor's rating.
  2. 02Check the resistor's resistance against the drive manual's minimum.
  3. 03Check the resistor for heat damage and its wiring for loose terminals.

05 / Repair

When oL7 means a repair

A burnt resistor or a shorted braking transistor in the drive has to be replaced.

If oL7 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Braking resistor: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20A535 Braking resistor overload
Siemens SINAMICS G120F07806 Regenerative power limit exceeded
Siemens SINAMICS V90A52901 Braking resistor reaches alarm threshold
Siemens MICROMASTER 440A0535 Brake resistor hot
Delta C2000bF Brake transistor error
Delta ASDA-B2AL005 Regeneration error · AL085 Regeneration error
Hitachi WJ200E06 Braking resistor overload protection
INVT Goodrive20 (GD20)bCE Braking unit fault
Yaskawa A1000boL Braking Transistor Overload Fault · oL7 High Slip Braking oL · rF Braking Resistor Fault · rH Braking Resistor Overheat · rr Dynamic Braking Transistor
Yaskawa GA500boL Braking Transistor Overload Fault · oL7 High Slip Braking Overload · rF Braking Resistor Fault · rH Braking Resistor Overheat · rr Dynamic Braking Transistor Fault
INVT Goodrive200A (GD200A)bCE Braking unit fault
Mitsubishi Electric FR-D700E.BE Brake transistor alarm detection · RB Regenerative brake pre-alarm
Danfoss VLT Micro Drive FC 51Alarm 25 Brake resistor short circuit · Alarm 27 Brake chopper fault · Alarm 28 Brake check failed · Alarm 63 Mechanical brake low

07 / More codes

Other V1000 codes

Source

Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

oL7 won't clear? Get a technician who knows the V1000.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.