MachineryFix

Yaskawa AC drive (VFD) · fault code

GA500 oL7: High Slip Braking Overload

oL7 on the Yaskawa GA500 is the “High Slip Braking Overload” fault. A fault shuts off the drive's output and the motor coasts to a stop (some faults let you choose the stopping method). ALM/ERR stays lit, a terminal set to H2-01 to H2-03 = E activates, and the drive will not run until the fault is reset.

The braking resistor is absorbing more energy than its rating allows. The machine is being stopped harder or more often than the resistor was sized for.

Code
oL7
Type
Fault (stops the drive)
Drive
Yaskawa GA500
Kind of fault
Braking resistor

01 / Causes

What causes oL7

  • The load inertia is too large, an external force turned the motor, or something on the load side prevents deceleration.
  • n3-04 (HSB Overload Time) is too short.

02 / Checks

What to check for oL7

In the order Yaskawa gives them.

  1. 01Where High Slip Braking is not needed, adjust the deceleration times; use a braking resistor to shorten deceleration.
  2. 02Raise n3-04, or fit a thermal overload relay to the motor and set n3-04 = 1200 s.

03 / Clearing it

How to clear oL7

  • Remove the cause, then reset in one of three ways: the reset key on the keypad while the code is shown, a multi-function input set to H1-xx = 14 (terminal S4 by default), or switching off the main circuit power and switching it back on once the keypad display has gone out.
  • A fault will not reset while a run command is active from the terminals or a communication option; the keypad shows CrST until the run command is removed.
  • oL1 resets only once monitor U4-16 (Motor oL1 Level) is below 100.

Clear it once. If oL7 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How braking resistor faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Compare the stopping duty (how often, from what speed, how much inertia) with the resistor's rating.
  2. 02Check the resistor's resistance against the drive manual's minimum.
  3. 03Check the resistor for heat damage and its wiring for loose terminals.

05 / Repair

When oL7 means a repair

A burnt resistor or a shorted braking transistor in the drive has to be replaced.

If oL7 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Braking resistor: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20A535 Braking resistor overload
Siemens SINAMICS G120F07806 Regenerative power limit exceeded
Siemens SINAMICS V90A52901 Braking resistor reaches alarm threshold
Siemens MICROMASTER 440A0535 Brake resistor hot
Delta C2000bF Brake transistor error
Delta ASDA-B2AL005 Regeneration error · AL085 Regeneration error
Hitachi WJ200E06 Braking resistor overload protection
INVT Goodrive20 (GD20)bCE Braking unit fault
Yaskawa V1000oL7 High-Slip Braking oL · rH Braking Resistor Overheat · rr Dynamic Braking Transistor
Yaskawa A1000boL Braking Transistor Overload Fault · oL7 High Slip Braking oL · rF Braking Resistor Fault · rH Braking Resistor Overheat · rr Dynamic Braking Transistor
INVT Goodrive200A (GD200A)bCE Braking unit fault
Mitsubishi Electric FR-D700E.BE Brake transistor alarm detection · RB Regenerative brake pre-alarm
Danfoss VLT Micro Drive FC 51Alarm 25 Brake resistor short circuit · Alarm 27 Brake chopper fault · Alarm 28 Brake check failed · Alarm 63 Mechanical brake low

07 / More codes

Other GA500 codes

Source

Yaskawa, GA500 Drive Technical Reference, C, SIEP C710617 52, 7 Troubleshooting (7.4 to 7.7, 7.9).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

oL7 won't clear? Get a technician who knows the GA500.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.