oL7 on the Yaskawa GA500 is the “High Slip Braking Overload” fault. A fault shuts off the drive's output and the motor coasts to a stop (some faults let you choose the stopping method). ALM/ERR stays lit, a terminal set to H2-01 to H2-03 = E activates, and the drive will not run until the fault is reset.
The braking resistor is absorbing more energy than its rating allows. The machine is being stopped harder or more often than the resistor was sized for.
- Code
- oL7
- Type
- Fault (stops the drive)
- Drive
- Yaskawa GA500
- Kind of fault
- Braking resistor
01 / Causes
What causes oL7
- The load inertia is too large, an external force turned the motor, or something on the load side prevents deceleration.
- n3-04 (HSB Overload Time) is too short.
02 / Checks
What to check for oL7
In the order Yaskawa gives them.
- 01Where High Slip Braking is not needed, adjust the deceleration times; use a braking resistor to shorten deceleration.
- 02Raise n3-04, or fit a thermal overload relay to the motor and set n3-04 = 1200 s.
03 / Clearing it
How to clear oL7
- Remove the cause, then reset in one of three ways: the reset key on the keypad while the code is shown, a multi-function input set to H1-xx = 14 (terminal S4 by default), or switching off the main circuit power and switching it back on once the keypad display has gone out.
- A fault will not reset while a run command is active from the terminals or a communication option; the keypad shows CrST until the run command is removed.
- oL1 resets only once monitor U4-16 (Motor oL1 Level) is below 100.
Clear it once. If oL7 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How braking resistor faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Compare the stopping duty (how often, from what speed, how much inertia) with the resistor's rating.
- 02Check the resistor's resistance against the drive manual's minimum.
- 03Check the resistor for heat damage and its wiring for loose terminals.
05 / Repair
When oL7 means a repair
A burnt resistor or a shorted braking transistor in the drive has to be replaced.
If oL7 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Braking resistor: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | A535 Braking resistor overload |
| Siemens SINAMICS G120 | F07806 Regenerative power limit exceeded |
| Siemens SINAMICS V90 | A52901 Braking resistor reaches alarm threshold |
| Siemens MICROMASTER 440 | A0535 Brake resistor hot |
| Delta C2000 | bF Brake transistor error |
| Delta ASDA-B2 | AL005 Regeneration error · AL085 Regeneration error |
| Hitachi WJ200 | E06 Braking resistor overload protection |
| INVT Goodrive20 (GD20) | bCE Braking unit fault |
| Yaskawa V1000 | oL7 High-Slip Braking oL · rH Braking Resistor Overheat · rr Dynamic Braking Transistor |
| Yaskawa A1000 | boL Braking Transistor Overload Fault · oL7 High Slip Braking oL · rF Braking Resistor Fault · rH Braking Resistor Overheat · rr Dynamic Braking Transistor |
| INVT Goodrive200A (GD200A) | bCE Braking unit fault |
| Mitsubishi Electric FR-D700 | E.BE Brake transistor alarm detection · RB Regenerative brake pre-alarm |
| Danfoss VLT Micro Drive FC 51 | Alarm 25 Brake resistor short circuit · Alarm 27 Brake chopper fault · Alarm 28 Brake check failed · Alarm 63 Mechanical brake low |