SINAMICS V20 A535: Braking resistor overload

A535 on the Siemens SINAMICS V20 is the “Braking resistor overload” alarm. An alarm is a warning: the inverter keeps running, and the alarm clears itself once the condition is gone. Alarms cannot be acknowledged.

The braking resistor is absorbing more energy than its rating allows. The machine is being stopped harder or more often than the resistor was sized for.

Code
A535
Type
Alarm (warning)
Drive
Siemens SINAMICS V20
Kind of fault
Braking resistor

01 / Causes

What causes A535

  • The braking energy is too large.
  • The braking resistor is not suited to the application.

02 / Checks

What to check for A535

In the order Siemens gives them.

  1. 01Reduce the braking energy.
  2. 02Use a braking resistor with a higher rating.

03 / Clearing it

How to clear A535

An alarm is a warning: the inverter keeps running, and the alarm clears itself once the condition is gone. Alarms cannot be acknowledged.

If A535 stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.

04 / On site

How braking resistor faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Compare the stopping duty (how often, from what speed, how much inertia) with the resistor's rating.
  2. 02Check the resistor's resistance against the drive manual's minimum.
  3. 03Check the resistor for heat damage and its wiring for loose terminals.

05 / Repair

When A535 means a repair

A burnt resistor or a shorted braking transistor in the drive has to be replaced.

If A535 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Braking resistor: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F07806 Regenerative power limit exceeded
Siemens SINAMICS V90A52901 Braking resistor reaches alarm threshold
Siemens MICROMASTER 440A0535 Brake resistor hot
Delta C2000bF Brake transistor error
Delta ASDA-B2AL005 Regeneration error · AL085 Regeneration error
Hitachi WJ200E06 Braking resistor overload protection
INVT Goodrive20 (GD20)bCE Braking unit fault
Yaskawa V1000oL7 High-Slip Braking oL · rH Braking Resistor Overheat · rr Dynamic Braking Transistor
Yaskawa A1000boL Braking Transistor Overload Fault · oL7 High Slip Braking oL · rF Braking Resistor Fault · rH Braking Resistor Overheat · rr Dynamic Braking Transistor
Yaskawa GA500boL Braking Transistor Overload Fault · oL7 High Slip Braking Overload · rF Braking Resistor Fault · rH Braking Resistor Overheat · rr Dynamic Braking Transistor Fault
INVT Goodrive200A (GD200A)bCE Braking unit fault
Mitsubishi Electric FR-D700E.BE Brake transistor alarm detection · RB Regenerative brake pre-alarm
Danfoss VLT Micro Drive FC 51Alarm 25 Brake resistor short circuit · Alarm 27 Brake chopper fault · Alarm 28 Brake check failed · Alarm 63 Mechanical brake low

07 / More codes

Other SINAMICS V20 codes

Source

Siemens, SINAMICS V20 Inverter Operating Instructions, 01/2018, A5E34559884-009, Chapter 9, Faults and alarms.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.