AL085 on the Delta ASDA-B2 is the “Regeneration error” alarm. This alarm switches the servo off, so the motor is no longer driven until the alarm is cleared.
The braking resistor is absorbing more energy than its rating allows. The machine is being stopped harder or more often than the resistor was sized for.
- Code
- AL085
- Type
- Alarm (stops the drive)
- Drive
- Delta ASDA-B2
- Kind of fault
- Braking resistor
01 / Causes
What causes AL085
- The wrong regenerative resistor is chosen, or no external regenerative resistor is connected.
- P1-53 is not set to zero when no regenerative resistor is used.
- P1-52 and P1-53 are set wrongly.
02 / Checks
What to check for AL085
In the order Delta Electronics gives them.
- 01Check the regenerative resistor's connection. Recalculate the resistor value and set P1-52 and P1-53 to match. If it persists, Delta's instruction is to send the drive back to the distributor or contact Delta.
- 02If no regenerative resistor is used, set P1-53 to zero.
- 03Set P1-52 and P1-53 correctly.
Also in the manual
- Regeneration control is in error. ALM output; servo off. Clears by turning on the alarm reset input (DI.ARST).
03 / Clearing it
How to clear AL085
- Remove the cause first. Most alarms clear by turning on the alarm reset input, DI.ARST (assigned to DI5 by default).
- Some alarms clear only after the drive is powered off and on: AL004, AL011, AL024 to AL029, AL031 and AL035. AL003 also needs a power cycle, unless P2-66 bit 2 is set so it clears once the voltage is back to normal.
- AL013 clears by itself once the emergency stop input (DI.EMGS) is off. AL014 and AL015 clear with DI.ARST, by switching the servo off, or by moving the motor back off the limit.
- AL099 clears by setting P2-08 to 30, then to 28, and powering the drive off and on. For AL555 and AL880, do nothing to the drive: Delta's instruction is to send it back to the distributor or contact Delta.
Clear it once. If AL085 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How braking resistor faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Compare the stopping duty (how often, from what speed, how much inertia) with the resistor's rating.
- 02Check the resistor's resistance against the drive manual's minimum.
- 03Check the resistor for heat damage and its wiring for loose terminals.
05 / Repair
When AL085 means a repair
A burnt resistor or a shorted braking transistor in the drive has to be replaced.
If AL085 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.
06 / Other drives
Braking resistor: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | A535 Braking resistor overload |
| Siemens SINAMICS G120 | F07806 Regenerative power limit exceeded |
| Siemens SINAMICS V90 | A52901 Braking resistor reaches alarm threshold |
| Siemens MICROMASTER 440 | A0535 Brake resistor hot |
| Delta C2000 | bF Brake transistor error |
| Hitachi WJ200 | E06 Braking resistor overload protection |
| INVT Goodrive20 (GD20) | bCE Braking unit fault |
| Yaskawa V1000 | oL7 High-Slip Braking oL · rH Braking Resistor Overheat · rr Dynamic Braking Transistor |
| Yaskawa A1000 | boL Braking Transistor Overload Fault · oL7 High Slip Braking oL · rF Braking Resistor Fault · rH Braking Resistor Overheat · rr Dynamic Braking Transistor |
| Yaskawa GA500 | boL Braking Transistor Overload Fault · oL7 High Slip Braking Overload · rF Braking Resistor Fault · rH Braking Resistor Overheat · rr Dynamic Braking Transistor Fault |
| INVT Goodrive200A (GD200A) | bCE Braking unit fault |
| Mitsubishi Electric FR-D700 | E.BE Brake transistor alarm detection · RB Regenerative brake pre-alarm |
| Danfoss VLT Micro Drive FC 51 | Alarm 25 Brake resistor short circuit · Alarm 27 Brake chopper fault · Alarm 28 Brake check failed · Alarm 63 Mechanical brake low |
07 / More codes
Other ASDA-B2 codes
Source
Delta Electronics, ASDA-B2 Standard AC Servo Drive User Manual, Revision May 2018, DELTA_IA-ASDA_B2_UM_EN_20180509, Chapter 9, Troubleshooting (9.1 to 9.3).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007