MachineryFix

Yaskawa AC drive (VFD) · fault code

GA500 EF7: External Fault (Terminal S7)

EF7 on the Yaskawa GA500 is the “External Fault (Terminal S7)” fault. A fault shuts off the drive's output and the motor coasts to a stop (some faults let you choose the stopping method). ALM/ERR stays lit, a terminal set to H2-01 to H2-03 = E activates, and the drive will not run until the fault is reset.

Something outside the drive told it to stop: a digital input or a control word bit set up as a fault input. The drive is reporting another device's trip.

Code
EF7
Type
Fault (stops the drive)
Drive
Yaskawa GA500
Kind of fault
External fault

01 / Causes

What causes EF7

  • An external device tripped a fault through multi-function input S7, the signal is wired to the wrong terminal, or S7 is set as an external fault input (H1-07 = 20 to 2B) but not in use.

02 / Checks

What to check for EF7

In the order Yaskawa gives them.

  1. 01Find the device that caused the external fault, remove the cause, and clear the external fault input.
  2. 02Connect the signal line to terminal S7.
  3. 03Correct the multi-function input settings.

Also in the manual

  • As a minor fault, the input is set H1-07 = 2C to 2F instead.
  • The GA500 can also show this code as a minor fault or alarm: ALM/ERR flashes instead of staying lit, and the drive keeps running unless set to stop.

03 / Clearing it

How to clear EF7

  • Remove the cause, then reset in one of three ways: the reset key on the keypad while the code is shown, a multi-function input set to H1-xx = 14 (terminal S4 by default), or switching off the main circuit power and switching it back on once the keypad display has gone out.
  • A fault will not reset while a run command is active from the terminals or a communication option; the keypad shows CrST until the run command is removed.
  • oL1 resets only once monitor U4-16 (Motor oL1 Level) is below 100.

Clear it once. If EF7 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How external fault faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Find which input or control word is set as the external fault source in the drive's parameters.
  2. 02Trace that input to the device driving it (a thermal switch, pressure switch, PLC output or interlock) and find out why it tripped.

05 / Repair

When EF7 means a repair

The fix is usually on the device that raised the input, not in the drive.

If EF7 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

External fault: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F85 External fault
Siemens SINAMICS G120F07860 External fault 1 · F07861 External fault 2 · F07862 External fault 3 · A07850 External alarm 1 · A07851 External alarm 2 · A07852 External alarm 3
Siemens MICROMASTER 440F0085 External fault
Allen-Bradley PowerFlex 525F002 Auxiliary Input · F094 Function Loss
ABB ACS355F0014 EXT FAULT 1 · F0015 EXT FAULT 2 · F0030 FORCE TRIP · A2021 START ENABLE 1 MISSING · A2022 START ENABLE 2 MISSING
Delta VFD-EEF External fault
Delta C2000LMIT Limit error · EF External fault · EF1 Emergency stop · bb External base block · ydc Y-connection / Δ-connection switch error · Brk External brake error
Hitachi WJ200E12 External trip · E36 Braking error · E50 EzSQ user trip 0 · E51 EzSQ user trip 1 · E52 EzSQ user trip 2 · E53 EzSQ user trip 3
Schneider Electric Altivar ATV320BLF Brake control error · BRF Brake feedback error · EPF1 External error · EPF2 Fieldbus external detected error · FCF1 Output contactor closed error · FCF2 Output contactor opened error
INVT Goodrive20 (GD20)EF External fault
Yaskawa V1000dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (input terminal S1) · EF2 External Fault (input terminal S2) · EF3 External Fault (input terminal S3) · EF4 External Fault (input terminal S4)
Yaskawa A1000dWAL DriveWorksEZ Fault · dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (input terminal S1) · EF2 External Fault (input terminal S2) · EF3 External Fault (input terminal S3)
Siemens MICROMASTER 420F0085 External fault
Siemens MICROMASTER 430F0085 External fault
Siemens SINAMICS G110F0085 External fault
INVT Goodrive200A (GD200A)EF External fault
Mitsubishi Electric FR-D700E.OHT External thermal relay operation · PS PU stop

07 / More codes

Other GA500 codes

Source

Yaskawa, GA500 Drive Technical Reference, C, SIEP C710617 52, 7 Troubleshooting (7.4 to 7.7, 7.9).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007