GF on the Yaskawa GA500 is the “Ground Fault” fault. A fault shuts off the drive's output and the motor coasts to a stop (some faults let you choose the stopping method). ALM/ERR stays lit, a terminal set to H2-01 to H2-03 = E activates, and the drive will not run until the fault is reset.
The drive found current leaving the motor circuit through earth: the three output currents no longer add up to zero. The usual cause is damaged insulation in the motor cable, the motor terminal box or the winding, often where water, oil or vibration has reached it.
- Code
- GF
- Type
- Fault (stops the drive)
- Drive
- Yaskawa GA500
- Kind of fault
- Earth fault
01 / Causes
What causes GF
- The motor is damaged by overheating or its insulation is poor, or the motor cable is shorting to ground.
- Higher stray capacitance between the cable and ground has raised the leakage current, or the drive hardware has failed.
02 / Checks
What to check for GF
In the order Yaskawa gives them.
- 01Measure the motor insulation resistance, and replace the motor if it conducts or the insulation is unserviceable.
- 02Examine the motor cable for damage and repair short circuits; measure the resistance between the motor cable and the ground terminal, and replace the cable if it conducts.
- 03On cable runs over 100 m, lower the carrier frequency and reduce stray capacitance.
- 04Replace the control board or the drive (contact Yaskawa about replacing the control board).
Also in the manual
- Detected when ground leakage on the output side exceeds 50% of rated current. L5-08 disables Auto Restart for this fault.
03 / Clearing it
How to clear GF
- Remove the cause, then reset in one of three ways: the reset key on the keypad while the code is shown, a multi-function input set to H1-xx = 14 (terminal S4 by default), or switching off the main circuit power and switching it back on once the keypad display has gone out.
- A fault will not reset while a run command is active from the terminals or a communication option; the keypad shows CrST until the run command is removed.
- oL1 resets only once monitor U4-16 (Motor oL1 Level) is below 100.
Clear it once. If GF comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How earth fault faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Isolate the supply, wait for the DC bus to discharge, and disconnect the motor cable at the drive.
- 02Insulation-test each phase of the cable and motor to earth with the drive disconnected (never megger through the drive).
- 03Split the circuit: test the cable alone, then the motor alone, to find which side is low.
- 04Open the motor terminal box and look for moisture, carbon tracking or a chafed lead.
- 05If cable and motor test healthy, check for long or unscreened motor cable and drive filter settings before suspecting the drive.
05 / Repair
When GF means a repair
When the cable and motor test healthy and the fault returns with the motor disconnected, the drive's current sensing or output stage is suspect and the unit needs bench testing.
If GF keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Earth fault: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F30021 Ground fault |
| Siemens SINAMICS V90 | F30021 Ground fault |
| Siemens MICROMASTER 440 | F0021 Ground fault |
| Allen-Bradley PowerFlex 525 | F013 Ground Fault · F038 Phase U to Gnd · F039 Phase V to Gnd · F040 Phase W to Gnd |
| ABB ACS355 | F0016 EARTH FAULT |
| Delta VFD-E | GFF Ground fault |
| Delta C2000 | GFF Ground fault |
| Hitachi WJ200 | E14 Ground fault |
| Schneider Electric Altivar ATV320 | SCF3 Ground short circuit error |
| INVT Goodrive20 (GD20) | ETH1 To-ground short-circuit fault 1 · ETH2 To-ground short-circuit fault 2 |
| Yaskawa V1000 | GF Ground Fault |
| Yaskawa A1000 | GF Ground Fault |
| Siemens MICROMASTER 430 | F0021 Ground fault |
| INVT Goodrive200A (GD200A) | ETH1 To-ground short-circuit fault 1 · ETH2 To-ground short-circuit fault 2 |
| Mitsubishi Electric FR-D700 | E.GF Output side earth (ground) fault overcurrent at start |
| Danfoss VLT Micro Drive FC 51 | Alarm 14 Earth (ground) fault · Alarm 44 Earth fault 2 |
07 / More codes