Uv on the Yaskawa GA500 is the “DC Bus Undervoltage” alarm. A minor fault or alarm leaves the drive running the motor (some let you choose a stopping method) while ALM/ERR flashes. A minor fault activates a terminal set to H2-01 to H2-03 = 10; an alarm gives no signal. No fault reset is needed.

The DC bus voltage fell below the level the drive needs to run. Most often the supply dipped or one phase was lost, but a failing pre-charge circuit or tired DC bus capacitors give the same code.

Code
Uv
Type
Alarm (warning)
Drive
Yaskawa GA500
Kind of fault
DC bus undervoltage

01 / Causes

What causes Uv

  • With the drive stopped: the DC bus below L2-05, the inrush contactor open, or low control power.
  • An unstable supply, phase loss, loose input terminals, a power loss, worn capacitors, a supply transformer too small, hot air inside the drive, or a broken Charge LED.

02 / Checks

What to check for Uv

In the order Yaskawa gives them.

  1. 01Make the supply stable and within the drive's rating; if it is good, check the main circuit contactor.
  2. 02Correct the input wiring and tighten loose screws.
  3. 03Check U4-05; above 90%, replace the control board or the drive.
  4. 04Check for the alarm as the breaker, leakage breaker or contactor closes, and check the supply transformer's capacity.
  5. 05Measure the drive's ambient temperature; replace the board or drive if the Charge LED is broken.

03 / Clearing it

How to clear Uv

A minor fault or alarm leaves the drive running the motor (some let you choose a stopping method) while ALM/ERR flashes. A minor fault activates a terminal set to H2-01 to H2-03 = 10; an alarm gives no signal. No fault reset is needed.

If Uv stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.

04 / On site

How dc bus undervoltage faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check whether the trip lines up with other plant loads starting, generator changeovers or known supply dips.
  2. 02Measure all three supply phases at the drive terminals, and check input fuses and contactor contacts.
  3. 03Look for loose or heat-discoloured supply terminals.
  4. 04If the supply is steady, record the DC bus voltage reading from the drive's display while running.

05 / Repair

When Uv means a repair

A drive that shows undervoltage on a healthy, steady supply usually has a failed pre-charge relay or resistor, or aged DC bus capacitors. Both are repaired on the bench.

If Uv keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

DC bus undervoltage: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F3 Undervoltage · A503 Undervoltage limit · A912 Vdc_min controller active
Siemens SINAMICS G120F30003 DC-link voltage undervoltage · F30027 Time monitoring for DC link pre-charging
Siemens SINAMICS V90F7403 Lower DC link voltage threshold reached · F30003 DC link voltage, undervoltage · F30027 Precharging DC link time monitoring · A30016 Load supply switched off
Siemens MICROMASTER 440F0003 Undervoltage · A0503 Undervoltage limit value · A0912 Vdc-min controller active
Allen-Bradley PowerFlex 525F003 Power Loss · F004 UnderVoltage
ABB ACS355F0006 DC UNDERVOLT · A2003 UNDERVOLTAGE · A5031 Drive is not ready for operation, for example because of low DC voltage
Delta VFD-ELv Low voltage · dEb Deceleration energy backup error
Delta C2000LvA Low-voltage during acceleration · Lvd Low-voltage during deceleration · Lvn Low-voltage at constant speed · LvS Low-voltage at stop · dEb Deceleration energy backup error
Delta ASDA-B2AL003 Under voltage
Hitachi WJ200E09 Under-voltage error
Schneider Electric Altivar ATV320USF Supply mains undervoltage error
INVT Goodrive20 (GD20)UV Bus undervoltage · PoFF System power off
Yaskawa V1000Uv1 DC Bus Undervoltage · Uv2 Control Power Supply Voltage Fault · Uv Undervoltage
Yaskawa A1000Uv1 DC Bus Undervoltage · Uv2 Control Power Supply Voltage Fault · Uv Undervoltage
Siemens MICROMASTER 420F0003 Undervoltage · A0503 Undervoltage limit value · A0912 Vdc-min controller active
Siemens MICROMASTER 430F0003 Undervoltage · A0503 Undervoltage limit value
Siemens SINAMICS G110F0003 Undervoltage · A0503 Undervoltage limit
INVT Goodrive200A (GD200A)UV Bus undervoltage · PoFF System power failure
Mitsubishi Electric FR-D700UV Undervoltage
Danfoss VLT Micro Drive FC 51Alarm 8 DC under voltage

07 / More codes

Other GA500 codes

Source

Yaskawa, GA500 Drive Technical Reference, C, SIEP C710617 52, 7 Troubleshooting (7.4 to 7.7, 7.9).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007