End1 on the Yaskawa V1000 is the “Excessive V/f Setting” alarm. A minor fault or alarm makes the ALM LED flash and the display show the code; the motor does not stop, and the drive returns to normal once the cause is removed. An alarm output can be set on a digital output (H2-oo = 10).
The drive's motor identification (autotune) run did not finish. The drive measures the motor to set up its control; it stopped because the motor was missing, the data entered was wrong, or a limit was reached.
- Code
- End1
- Type
- Alarm (warning)
- Drive
- Yaskawa V1000
- Kind of fault
- Motor identification
01 / Causes
What causes End1
- Shown after Auto-Tuning: the torque reference went above 20%, or the no-load current went above 80% of the drive's rated current, during tuning.
02 / Checks
What to check for End1
In the order Yaskawa gives them.
- 01Check the motor nameplate and enter its data in T1-03 to T1-05, then repeat Auto-Tuning.
- 02Disconnect the motor from the load for tuning if possible.
03 / Clearing it
How to clear End1
A minor fault or alarm makes the ALM LED flash and the display show the code; the motor does not stop, and the drive returns to normal once the cause is removed. An alarm output can be set on a digital output (H2-oo = 10).
If End1 stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.
04 / On site
How motor identification faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the motor is connected and the output contactor (if any) is closed during the run.
- 02Check the rating plate data entered in the drive and the motor connection (star or delta).
- 03Repeat the identification with the motor cold and uncoupled where possible.
05 / Repair
When End1 means a repair
Repeated failures on a correctly entered, healthy motor point at a winding fault or a drive measurement problem.
If End1 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Motor identification: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F41 Motor data identification failure |
| Siemens SINAMICS G120 | A07980 Rotary measurement activated · A07981 No enabling for rotary measurement · A07991 Motor identification activated |
| Siemens SINAMICS V90 | F7995 Motor identification failure · A7971 Angular commutation offset determination activated · A7991 Motor data identification activated |
| Siemens MICROMASTER 440 | F0041 Failure, motor data identification · F0042 Fault/error when optimizing the speed controller |
| Allen-Bradley PowerFlex 525 | F080 Autotune Failure |
| ABB ACS355 | F0011 ID RUN FAIL · A2019 ID RUN · A2025 FIRST START |
| Delta VFD-E | AUE Auto tuning error |
| Delta C2000 | AUE Auto-tuning error · AUE1 Auto-tune error 1 · AUE2 Auto-tune error 2 · AUE3 Auto-tune error 3 · AUE4 Auto-tune error 4 |
| Schneider Electric Altivar ATV320 | ASF Angle error · TNF Autotuning detected error |
| INVT Goodrive20 (GD20) | tE Motor autotuning fault · STo Maladjustment fault |
| Yaskawa A1000 | dv7 Initial Polarity Estimation Timeout · End1 Excessive V/f Setting · End2 Motor Iron-Core Saturation Coefficient · End3 Rated Current Setting Alarm · End4 Adjusted Slip Calculation Error · End5 Resistance Tuning Error |
| Yaskawa GA500 | dv7 Polarity Judge Timeout · End1 Excessive Rated Voltage Setting · End2 Iron Core Saturation Coefficient · End3 Rated Current Setting Alarm · End4 Adjusted Slip Calculation Error · End5 Resistance Tuning Error |
| Siemens MICROMASTER 420 | F0041 Failure, motor data identification · A0541 Motor data identification routine active |
| Siemens MICROMASTER 430 | F0041 Failure, motor data identification · A0541 Motor data identification routine active |
| INVT Goodrive200A (GD200A) | tE Motor autotuning fault |
| Danfoss VLT Micro Drive FC 51 | Alarm 51 AMT check Unom and Inom · Alarm 52 AMT low Inom · Alarm 53 AMT motor too big · Alarm 54 AMT motor too small · Alarm 55 AMT parameter out of range |
07 / More codes
Other V1000 codes
Source
Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007