V1000 End3: Rated Current Setting Alarm

End3 on the Yaskawa V1000 is the “Rated Current Setting Alarm” alarm. A minor fault or alarm makes the ALM LED flash and the display show the code; the motor does not stop, and the drive returns to normal once the cause is removed. An alarm output can be set on a digital output (H2-oo = 10).

The drive's motor identification (autotune) run did not finish. The drive measures the motor to set up its control; it stopped because the motor was missing, the data entered was wrong, or a limit was reached.

Code
End3
Type
Alarm (warning)
Drive
Yaskawa V1000
Kind of fault
Motor identification

01 / Causes

What causes End3

  • Shown after Auto-Tuning: the motor's line-to-line resistance and rated current do not agree, or the nameplate current was not entered in T1-04.

02 / Checks

What to check for End3

In the order Yaskawa gives them.

  1. 01Check T1-04.
  2. 02Check the motor data and repeat Auto-Tuning.

03 / Clearing it

How to clear End3

A minor fault or alarm makes the ALM LED flash and the display show the code; the motor does not stop, and the drive returns to normal once the cause is removed. An alarm output can be set on a digital output (H2-oo = 10).

If End3 stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.

04 / On site

How motor identification faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the motor is connected and the output contactor (if any) is closed during the run.
  2. 02Check the rating plate data entered in the drive and the motor connection (star or delta).
  3. 03Repeat the identification with the motor cold and uncoupled where possible.

05 / Repair

When End3 means a repair

Repeated failures on a correctly entered, healthy motor point at a winding fault or a drive measurement problem.

If End3 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Motor identification: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F41 Motor data identification failure
Siemens SINAMICS G120A07980 Rotary measurement activated · A07981 No enabling for rotary measurement · A07991 Motor identification activated
Siemens SINAMICS V90F7995 Motor identification failure · A7971 Angular commutation offset determination activated · A7991 Motor data identification activated
Siemens MICROMASTER 440F0041 Failure, motor data identification · F0042 Fault/error when optimizing the speed controller
Allen-Bradley PowerFlex 525F080 Autotune Failure
ABB ACS355F0011 ID RUN FAIL · A2019 ID RUN · A2025 FIRST START
Delta VFD-EAUE Auto tuning error
Delta C2000AUE Auto-tuning error · AUE1 Auto-tune error 1 · AUE2 Auto-tune error 2 · AUE3 Auto-tune error 3 · AUE4 Auto-tune error 4
Schneider Electric Altivar ATV320ASF Angle error · TNF Autotuning detected error
INVT Goodrive20 (GD20)tE Motor autotuning fault · STo Maladjustment fault
Yaskawa A1000dv7 Initial Polarity Estimation Timeout · End1 Excessive V/f Setting · End2 Motor Iron-Core Saturation Coefficient · End3 Rated Current Setting Alarm · End4 Adjusted Slip Calculation Error · End5 Resistance Tuning Error
Yaskawa GA500dv7 Polarity Judge Timeout · End1 Excessive Rated Voltage Setting · End2 Iron Core Saturation Coefficient · End3 Rated Current Setting Alarm · End4 Adjusted Slip Calculation Error · End5 Resistance Tuning Error
Siemens MICROMASTER 420F0041 Failure, motor data identification · A0541 Motor data identification routine active
Siemens MICROMASTER 430F0041 Failure, motor data identification · A0541 Motor data identification routine active
INVT Goodrive200A (GD200A)tE Motor autotuning fault
Danfoss VLT Micro Drive FC 51Alarm 51 AMT check Unom and Inom · Alarm 52 AMT low Inom · Alarm 53 AMT motor too big · Alarm 54 AMT motor too small · Alarm 55 AMT parameter out of range

07 / More codes

Other V1000 codes

Source

Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.