MachineryFix

Yaskawa AC drive (VFD) · fault code

V1000 GF: Ground Fault

GF on the Yaskawa V1000 is the “Ground Fault” fault. A fault interrupts the drive's output and the motor coasts to a stop (unless set to stop another way). The drive stays inoperable until the fault is reset, and a digital output set for fault (H2-oo = E) closes.

The drive found current leaving the motor circuit through earth: the three output currents no longer add up to zero. The usual cause is damaged insulation in the motor cable, the motor terminal box or the winding, often where water, oil or vibration has reached it.

Code
GF
Type
Fault (stops the drive)
Drive
Yaskawa V1000
Kind of fault
Earth fault

01 / Causes

What causes GF

  • Current shorted to ground on the drive's output side went above 50% of rated current.
  • Damaged motor insulation, a damaged motor cable shorting to ground, high leakage current at the output, the drive starting during a current offset fault or while the motor coasted, or a hardware problem.

02 / Checks

What to check for GF

In the order Yaskawa gives them.

  1. 01Check the motor's insulation resistance and replace the motor if needed.
  2. 02Check the motor cable and its resistance to the ground terminal; remove the short or replace the cable.
  3. 03Reduce the carrier frequency and the stray capacitance.
  4. 04If the run command was given while the motor was coasting, enable Speed Search at start (b3-01 = 1) or use External Speed Search 1 or 2 on a multi-function input (H1-oo = 61 or 62).
  5. 05If none of these, replace the drive.

Also in the manual

  • On models 2A0020 to 2A0069 and 4A0011 to 4A0038, ground fault detection is turned on by setting L8-09 to 1.

03 / Clearing it

How to clear GF

  • Fix the cause, then reset with the reset key on the digital operator, or by closing and opening terminal S4, which is the fault reset input by default.
  • If neither clears it, switch off the drive's main power and switch it back on once the operator display has gone out.
  • Some faults need a condition met before they reset: oL1 cannot be reset until monitor U4-16 is below 100.

Clear it once. If GF comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How earth fault faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Isolate the supply, wait for the DC bus to discharge, and disconnect the motor cable at the drive.
  2. 02Insulation-test each phase of the cable and motor to earth with the drive disconnected (never megger through the drive).
  3. 03Split the circuit: test the cable alone, then the motor alone, to find which side is low.
  4. 04Open the motor terminal box and look for moisture, carbon tracking or a chafed lead.
  5. 05If cable and motor test healthy, check for long or unscreened motor cable and drive filter settings before suspecting the drive.

05 / Repair

When GF means a repair

When the cable and motor test healthy and the fault returns with the motor disconnected, the drive's current sensing or output stage is suspect and the unit needs bench testing.

If GF keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Earth fault: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F30021 Ground fault
Siemens SINAMICS V90F30021 Ground fault
Siemens MICROMASTER 440F0021 Ground fault
Allen-Bradley PowerFlex 525F013 Ground Fault · F038 Phase U to Gnd · F039 Phase V to Gnd · F040 Phase W to Gnd
ABB ACS355F0016 EARTH FAULT
Delta VFD-EGFF Ground fault
Delta C2000GFF Ground fault
Hitachi WJ200E14 Ground fault
Schneider Electric Altivar ATV320SCF3 Ground short circuit error
INVT Goodrive20 (GD20)ETH1 To-ground short-circuit fault 1 · ETH2 To-ground short-circuit fault 2
Yaskawa A1000GF Ground Fault
Yaskawa GA500GF Ground Fault
Siemens MICROMASTER 430F0021 Ground fault
INVT Goodrive200A (GD200A)ETH1 To-ground short-circuit fault 1 · ETH2 To-ground short-circuit fault 2
Mitsubishi Electric FR-D700E.GF Output side earth (ground) fault overcurrent at start
Danfoss VLT Micro Drive FC 51Alarm 14 Earth (ground) fault · Alarm 44 Earth fault 2

07 / More codes

Other V1000 codes

Source

Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

GF won't clear? Get a technician who knows the V1000.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.