V1000 LF2: Output current imbalance

LF2 on the Yaskawa V1000 is the “Output current imbalance” fault. A fault interrupts the drive's output and the motor coasts to a stop (unless set to stop another way). The drive stays inoperable until the fault is reset, and a digital output set for fault (H2-oo = E) closes.

The drive sees current in only two of the three motor phases. A phase is open somewhere between the drive and the motor winding.

Code
LF2
Type
Fault (stops the drive)
Drive
Yaskawa V1000
Kind of fault
Output phase loss

01 / Causes

What causes LF2

  • One or more output current phases is lost.
  • Phase loss or loose terminals on the output side, no signal from the gate driver board, or uneven motor impedance or phases.

02 / Checks

What to check for LF2

In the order Yaskawa gives them.

  1. 01Check for faulty wiring or poor connections on the output side and correct them.
  2. 02Tighten the output terminals to the torque in the manual.
  3. 03Measure the line-to-line resistance of each motor phase; they should be the same. Replace the motor if not.
  4. 04If there is no gate driver signal, replace the drive and contact Yaskawa.

03 / Clearing it

How to clear LF2

  • Fix the cause, then reset with the reset key on the digital operator, or by closing and opening terminal S4, which is the fault reset input by default.
  • If neither clears it, switch off the drive's main power and switch it back on once the operator display has gone out.
  • Some faults need a condition met before they reset: oL1 cannot be reset until monitor U4-16 is below 100.

Clear it once. If LF2 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How output phase loss faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Isolate and check continuity of each phase from the drive terminals to the motor terminals.
  2. 02Inspect any contactor, isolator or junction box in the motor circuit.
  3. 03Measure winding resistance phase to phase at the motor.

05 / Repair

When LF2 means a repair

When cable, connections and windings are all good, an output phase in the drive itself may be open.

If LF2 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Output phase loss: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20A922 No load applied to inverter
Siemens SINAMICS G120F30015 Motor cable phase failure
Siemens SINAMICS V90F7410 Current controller output limited · F30015 Phase failure motor cable
Siemens MICROMASTER 440F0023 Output fault · F0422 No load applied to inverter · A0523 Output fault · A0922 No load at the inverter
Allen-Bradley PowerFlex 525F021 Output Ph Loss
ABB ACS355F0034 MOTOR PHASE
Delta C2000OPHL Output phase loss
Delta ASDA-B2AL031 Incorrect wiring of the motor power line U, V, W, GND
Schneider Electric Altivar ATV320OPF1 Single output phase loss error · OPF2 Output phase loss error
INVT Goodrive20 (GD20)SPO Phase loss on output side
Yaskawa A1000LF Output Phase Loss · LF2 Output Current Imbalance · LF3 Power Unit Output Phase Loss 3 · UnbC Current Unbalance
Yaskawa GA500LF Output Phase Loss · LF2 Output Current Imbalance
Siemens MICROMASTER 430F0023 Output fault · A0523 Output fault
INVT Goodrive200A (GD200A)SPO Phase loss on output side
Mitsubishi Electric FR-D700E.LF Output phase loss
Danfoss VLT Micro Drive FC 51Alarm 30 Motor phase U missing · Alarm 31 Motor phase V missing · Alarm 32 Motor phase W missing

07 / More codes

Other V1000 codes

Source

Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

LF2 won't clear? Get a technician who knows the V1000.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.