oPE08 on the Yaskawa V1000 is the “Parameter Selection Error” fault. A fault interrupts the drive's output and the motor coasts to a stop (unless set to stop another way). The drive stays inoperable until the fault is reset, and a digital output set for fault (H2-oo = E) closes.
A setting the drive cannot accept, or an operating state it is reporting. An alarm of this kind does not stop the motor on its own; a setup fault keeps the drive from running until the setting is corrected.
- Code
- oPE08
- Type
- Fault (stops the drive)
- Drive
- Yaskawa V1000
- Kind of fault
- Setup
01 / Causes
What causes oPE08
- A function is set that the selected control method cannot use: an Open Loop Vector function in V/f, or Simple V/f with PG (H6-01 = 3) outside V/f control.
- In Open Loop Vector, n2-02 above n2-03 or C4-02 above C4-06; in OLV/PM, E5-02 to E5-07 set to 0 or conflicting E5 settings.
02 / Checks
What to check for oPE08
In the order Yaskawa gives them.
- 01Check the control method and the functions it allows.
- 02For Simple V/f with PG, set the control method to V/f (A1-02 = 0).
- 03Set n2-02 below n2-03 and C4-02 below C4-06.
- 04Set the correct motor code in E5-01; for a special motor, set the E5 parameters from its test report.
Also in the manual
- Other errors take precedence over oPE08 when several occur at once.
- An oPE error clears once the setting is corrected; it gives no fault or alarm output. Press ENTER while it is shown to see monitor U1-18, which names the parameter causing it.
03 / Clearing it
How to clear oPE08
- Fix the cause, then reset with the reset key on the digital operator, or by closing and opening terminal S4, which is the fault reset input by default.
- If neither clears it, switch off the drive's main power and switch it back on once the operator display has gone out.
- Some faults need a condition met before they reset: oL1 cannot be reset until monitor U4-16 is below 100.
Clear it once. If oPE08 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How setup faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the parameters the manual names for this code.
05 / Repair
When oPE08 means a repair
No repair: a setting to correct.
If oPE08 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Setup: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | A541 Motor data identification active · A921 Analog output parameters not set properly · A923 Both JOG left and JOG right are requested · A936 PID autotuning active |
| Siemens SINAMICS G120 | F01033 Switching over units: Reference parameter value invalid · F01034 Switching over units: Calculation of the parameter values after reference value change unsuccessful · F01122 Frequency at the probe input too high · F01512 An attempt has been made to establish a conversion factor for scaling which does not exist · F06310 Supply voltage (p0210) incorrectly set · F07086 Switching over units: Parameter limit violation |
| Siemens SINAMICS V90 | F7085 Open-loop/closed-loop control parameters changed · F7442 LR: Multiturn does not match the modulo range · F7490 Enable signal withdrawn while traversing · F7493 LR: Overflow of the value range for position actual value · F52904 Control mode change · F52911 Positive torque limitation value error |
| Siemens MICROMASTER 440 | A0541 Motor data identification routine active · A0542 Speed controller optimization running · A0920 ADC parameters not correctly set · A0921 DAC parameters not set properly · A0923 JOG counter-clockwise as well as JOG clockwise are requested · A0936 PID auto tuning active |
| ABB ACS355 | F1000 PAR HZRPM · F1003 PAR AI SCALE · F1004 PAR AO SCALE · F1005 PAR PCU 2 · F1006 PAR EXT RO · F1007 PAR FBUSMISS |
| Delta VFD-E | cFA Auto accel/decel failure |
| Delta C2000 | Pcod Password is locked |
| Delta ASDA-B2 | AL008 Abnormal pulse command |
| Hitachi WJ200 | E13 USP · E43 EzSQ invalid instruction · E44 EzSQ nesting count error · E45 EzSQ instruction error |
| Schneider Electric Altivar ATV320 | CFF Incorrect configuration error · CFI Invalid configuration error · CFI2 Configuration transfer error · CSF Channel switching detected error · FBE Function block error · FBES Function block stop error |
| INVT Goodrive20 (GD20) | END Running time reached |
| Yaskawa A1000 | CF Control Fault · nSE Node Setup Error · oPE01 Drive Capacity Setting Fault · oPE02 Parameter Range Setting Error · oPE03 Multi-Function Input Selection Error · oPE04 Initialization Required |
| Yaskawa GA500 | CF Control Fault · nSE Node Setup Error · TiM Keypad Time Not Set · oPE01 Drive Capacity Setting Error · oPE02 Parameter Range Setting Error · oPE03 Multi-Function Input Setting Err |
| Siemens MICROMASTER 420 | A0920 ADC parameters not correctly set · A0921 DAC parameters not set properly · A0923 JOG counter-clockwise as well as JOG clockwise are requested |
| Siemens MICROMASTER 430 | A0920 ADC parameters not correctly set · A0921 DAC parameters not correctly set |
| Siemens SINAMICS G110 | F0056 BOP not fitted · F0057 BOP fault · F0058 BOP contents incompatible · A0920 ADC parameters not set properly · A0923 Both JOG left and JOG right are requested |
| INVT Goodrive200A (GD200A) | END Running time reached |
| Mitsubishi Electric FR-D700 | E.AIE Analog input fault · HOLD Operation panel lock · LOCD Password locked · Er1 Write disable error · Er2 Write error during operation · Er3 Calibration error |
| Danfoss VLT Micro Drive FC 51 | Alarm 80 Drive initialised to default value · Error 85 Button disabled · Error 89 Parameter read only · Error 91 Parameter value is not valid in this mode · Error 92 Parameter value exceeds the min/max limits |
07 / More codes
Other V1000 codes
Source
Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007