A2026 on the ABB ACS355 is the “INPUT PHASE LOSS” alarm. An alarm warns of a condition without tripping the drive, and the green LED blinks. Some alarms are a normal part of operation, such as A2019 during the motor ID run.
One of the three supply phases is missing or weak, so the DC bus ripple rose above a safe level. Running on two phases overloads the rectifier and the capacitors.
- Code
- A2026
- Type
- Alarm (warning)
- Drive
- ABB ACS355
- Kind of fault
- Input phase loss
01 / Causes
What causes A2026
- The DC bus voltage is oscillating because an input phase is missing or a fuse has blown.
- The alarm comes when the DC voltage ripple exceeds 14% of the nominal DC voltage.
02 / Checks
What to check for A2026
In the order ABB gives them.
- 01Check the input fuses.
- 02Check for imbalance in the input supply.
- 03Check the fault function parameters.
Also in the manual
- ABB lists this as a programmable fault function: parameters 3016 decide whether the condition is reported and how the drive reacts.
03 / Clearing it
How to clear A2026
An alarm warns of a condition without tripping the drive, and the green LED blinks. Some alarms are a normal part of operation, such as A2019 during the motor ID run.
If A2026 stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.
04 / On site
How input phase loss faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Measure all three phases at the drive input terminals with the drive running under load.
- 02Check input fuses, the breaker and the contactor for a blown fuse or a burnt contact.
- 03Tighten and inspect supply terminals for heat damage.
05 / Repair
When A2026 means a repair
If all three phases are healthy at the terminals and the code persists, the drive's rectifier or its supply sensing is at fault.
If A2026 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on ABB drives, and they arrive knowing what to look for.
06 / Other drives
Input phase loss: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F20 DC ripple too high |
| Siemens SINAMICS G120 | F30011 Line phase failure |
| Siemens SINAMICS V90 | F30011 Line phase failure in main circuit |
| Siemens MICROMASTER 440 | F0020 Line supply phase missing |
| Delta VFD-E | PHL Phase loss |
| Delta C2000 | OrP Phase loss protection |
| Delta ASDA-B2 | AL022 Main circuit power lack phase |
| Schneider Electric Altivar ATV320 | PHF Input phase loss error |
| INVT Goodrive20 (GD20) | SPI Phase loss on input side |
| Yaskawa V1000 | PF Input Phase Loss |
| Yaskawa A1000 | PF Input Phase Loss |
| Yaskawa GA500 | PF Input Phase Loss |
| Siemens MICROMASTER 430 | F0020 Line supply phase missing |
| INVT Goodrive200A (GD200A) | SPI Phase loss on input side |
| Mitsubishi Electric FR-D700 | E.ILF Input phase loss |
| Danfoss VLT Micro Drive FC 51 | Alarm 4 Mains phase loss |
07 / More codes
Other ACS355 codes
Source
ABB, ACS355 user's manual, Rev E, effective 2 November 2020, 3AUA0000066143, Fault tracing.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of ABB and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007