Allen-Bradley AC drive (VFD) · fault code

PowerFlex 525 F064: Drive Overload

F064 on the Allen-Bradley PowerFlex 525 is the “Drive Overload” fault. A fault stops the drive; it will not restart until the fault is cleared.

The drive's own overload model says it has carried more current, for longer, than its rating allows. The drive is undersized for the duty, or the load has grown.

Code
F064
Type
Fault (stops the drive)
Drive
Allen-Bradley PowerFlex 525, PowerFlex 523
Kind of fault
Drive overload

01 / Causes

What causes F064

Rockwell Automation's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing drive overload faults explains where it usually comes from.

02 / Checks

What to check for F064

In the order Rockwell Automation gives them.

  1. 01Reduce the load or extend the acceleration time.

03 / Clearing it

How to clear F064

  • Rockwell's parameter A551 [Fault Clear] resets a fault when set to 1 (Reset Fault); setting it to 2 (Clear Buffer) also clears the fault queue.
  • Correct the cause first: F033 means the drive has already used up its automatic restart attempts on a fault that is still there.

Clear it once. If F064 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How drive overload faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Record the running current and compare it with the drive's rated current.
  2. 02Look for a change in the load: a dragging bearing, a tighter belt, a heavier product, a blocked impeller.
  3. 03Check acceleration time and boost settings; long periods at high torque add up quickly.

05 / Repair

When F064 means a repair

If the current is well within the rating and the code keeps returning, the drive's current measurement should be checked on the bench.

If F064 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Allen-Bradley drives, and they arrive knowing what to look for.

06 / Other drives

Drive overload: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F5 Inverter I2t · A505 Inverter I2t
Siemens SINAMICS G120F30005 I2t inverter overload · A07805 Drive: Power unit overload I2t
Siemens SINAMICS V90F30005 Power unit: Overload I2t
Siemens MICROMASTER 440F0005 Inverter I2T · A0505 Inverter I2T
Delta VFD-EoL Overload
Delta C2000oL Over load · oL3 Overload protection at low frequency
Hitachi WJ200E38 Low-speed overload protection
INVT Goodrive20 (GD20)OL2 VFD overload
Yaskawa V1000oL2 Drive Overload
Yaskawa A1000oL2 Drive Overload
Yaskawa GA500oL2 Drive Overload
Siemens MICROMASTER 420F0005 Inverter I2t · A0505 Inverter I2t
Siemens MICROMASTER 430F0005 Inverter I2t · A0505 Inverter I2t · A0506 Inverter load duty cycle
Siemens SINAMICS G110F0005 Inverter I2t · A0505 Inverter I2t
INVT Goodrive200A (GD200A)OL2 VFD overload
Mitsubishi Electric FR-D700E.THT Inverter overload trip (electronic thermal O/L relay function)
Danfoss VLT Micro Drive FC 51Alarm 9 Inverter overloaded

07 / More codes

Other PowerFlex 525 codes

Source

Rockwell Automation, PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start, November 2017, 520-QS001B-EN-E, Fault Codes.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Allen-Bradley and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007