ydc on the Delta C2000 is the “Y-connection / Δ-connection switch error” fault. A fault stops the drive's output. On over-current and over-voltage faults the drive closes its output gate at once and the motor coasts to a stop.
Something outside the drive told it to stop: a digital input or a control word bit set up as a fault input. The drive is reporting another device's trip.
- Code
- ydc
- Type
- Fault (stops the drive)
- Drive
- Delta C2000
- Kind of fault
- External fault
01 / Causes
What causes ydc
- The contactor does not work properly during the Y-Δ changeover.
- Parameters set wrongly.
- The Y-Δ switching function is wired wrongly.
02 / Checks
What to check for ydc
In the order Delta Electronics gives them.
- 01Check the contactor works, and replace it if not.
- 02Check all the related parameters are set, and set correctly.
- 03Check the wiring.
Also in the manual
- Fault ID 61. Both the Y and the Δ confirmation signals are on together, or neither arrives within Pr. 05-25. It resets only once the confirmation signal for the current connection is on.
03 / Clearing it
How to clear ydc
- Remove the cause first. Then press STOP/RESET on the keypad, or switch on a multi-function input set to 5 (Reset).
- Most faults can be reset 5 seconds after the fault has cleared. Over-voltage faults reset only once the DC bus is below 90% of the trip level, and overheating faults only once the temperature is 10°C below it.
- Some faults can only be cleared by switching the power off: the current detection and hardware protection faults (cd1 to cd3, Hd0 to Hd3), the watchdog (WDTT), STO Loss (STL1 to STL3) and the CPU error (TRAP).
- After resetting, if the keypad returns to its main page and shows no fault after ESC, the fault is cleared.
Clear it once. If ydc comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How external fault faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Find which input or control word is set as the external fault source in the drive's parameters.
- 02Trace that input to the device driving it (a thermal switch, pressure switch, PLC output or interlock) and find out why it tripped.
05 / Repair
When ydc means a repair
The fix is usually on the device that raised the input, not in the drive.
If ydc keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.
06 / Other drives
External fault: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F85 External fault |
| Siemens SINAMICS G120 | F07860 External fault 1 · F07861 External fault 2 · F07862 External fault 3 · A07850 External alarm 1 · A07851 External alarm 2 · A07852 External alarm 3 |
| Siemens MICROMASTER 440 | F0085 External fault |
| Allen-Bradley PowerFlex 525 | F002 Auxiliary Input · F094 Function Loss |
| ABB ACS355 | F0014 EXT FAULT 1 · F0015 EXT FAULT 2 · F0030 FORCE TRIP · A2021 START ENABLE 1 MISSING · A2022 START ENABLE 2 MISSING |
| Delta VFD-E | EF External fault |
| Hitachi WJ200 | E12 External trip · E36 Braking error · E50 EzSQ user trip 0 · E51 EzSQ user trip 1 · E52 EzSQ user trip 2 · E53 EzSQ user trip 3 |
| Schneider Electric Altivar ATV320 | BLF Brake control error · BRF Brake feedback error · EPF1 External error · EPF2 Fieldbus external detected error · FCF1 Output contactor closed error · FCF2 Output contactor opened error |
| INVT Goodrive20 (GD20) | EF External fault |
| Yaskawa V1000 | dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (input terminal S1) · EF2 External Fault (input terminal S2) · EF3 External Fault (input terminal S3) · EF4 External Fault (input terminal S4) |
| Yaskawa A1000 | dWAL DriveWorksEZ Fault · dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (input terminal S1) · EF2 External Fault (input terminal S2) · EF3 External Fault (input terminal S3) |
| Yaskawa GA500 | dWF2 DriveWorksEZ Fault 2 · dWF3 DriveWorksEZ Fault 3 · dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (Terminal S1) · EF2 External Fault (Terminal S2) |
| Siemens MICROMASTER 420 | F0085 External fault |
| Siemens MICROMASTER 430 | F0085 External fault |
| Siemens SINAMICS G110 | F0085 External fault |
| INVT Goodrive200A (GD200A) | EF External fault |
| Mitsubishi Electric FR-D700 | E.OHT External thermal relay operation · PS PU stop |
07 / More codes
Other C2000 codes
Source
Delta Electronics, C2000 Series User Manual, Issued edition 01, firmware V2.05 (2019-02-13), DELTA_IA-MDS_VFD-C2000_UM_EN_20190213, Chapter 14, Fault Codes and Descriptions.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.