Schneider Electric AC drive (VFD) · fault code

Altivar ATV320 BLF: Brake control error

BLF on the Schneider Electric Altivar ATV320 is the “Brake control error” fault. A detected error stops the drive until it is cleared, in the way the manual gives for that code.

Something outside the drive told it to stop: a digital input or a control word bit set up as a fault input. The drive is reporting another device's trip.

Code
BLF
Type
Fault (stops the drive)
Drive
Schneider Electric Altivar ATV320
Kind of fault
External fault

01 / Causes

What causes BLF

  • The brake release current was not reached.
  • The brake engage frequency threshold (BEN) is only regulated when brake logic control is assigned.

02 / Checks

What to check for BLF

In the order Schneider Electric gives them.

  1. 01Check the connection between the drive and the motor.
  2. 02Check the motor windings.
  3. 03Check the brake release current settings (IBR and IRD).
  4. 04Apply the recommended setting for the brake engage frequency (BEN).

Also in the manual

  • Clears only with a power reset, after the cause is removed.

03 / Clearing it

How to clear BLF

  • Remove the cause first. A resettable error can then be cleared by switching the drive off until the display goes out completely and back on, automatically by the Auto Fault Reset (ATR) function, through an input or control bit assigned to Fault reset (RST), or with the STOP/RESET key on the graphic display terminal when it is the active command channel.
  • Some codes need a power reset (ANF, ASF, BLF, BRF, CRF1, EEF1, EEF2, FCF1, HDF, ILF, the INF codes, SAFF, SOF, SPF); ASF, BRF, SOF, SPF and TNF can also be cleared remotely with Fault Reset Assign (RSF).
  • For an error that cannot be reset, Schneider's steps are: disconnect all power, including external control power; lock the disconnects open; wait 15 minutes for the DC bus capacitors to discharge; check the DC bus between PA/+ and PC/- is below 42 V DC; find and fix the cause; then restore power to confirm.

Clear it once. If BLF comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How external fault faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Find which input or control word is set as the external fault source in the drive's parameters.
  2. 02Trace that input to the device driving it (a thermal switch, pressure switch, PLC output or interlock) and find out why it tripped.

05 / Repair

When BLF means a repair

The fix is usually on the device that raised the input, not in the drive.

If BLF keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Schneider Electric drives, and they arrive knowing what to look for.

06 / Other drives

External fault: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F85 External fault
Siemens SINAMICS G120F07860 External fault 1 · F07861 External fault 2 · F07862 External fault 3 · A07850 External alarm 1 · A07851 External alarm 2 · A07852 External alarm 3
Siemens MICROMASTER 440F0085 External fault
Allen-Bradley PowerFlex 525F002 Auxiliary Input · F094 Function Loss
ABB ACS355F0014 EXT FAULT 1 · F0015 EXT FAULT 2 · F0030 FORCE TRIP · A2021 START ENABLE 1 MISSING · A2022 START ENABLE 2 MISSING
Delta VFD-EEF External fault
Delta C2000LMIT Limit error · EF External fault · EF1 Emergency stop · bb External base block · ydc Y-connection / Δ-connection switch error · Brk External brake error
Hitachi WJ200E12 External trip · E36 Braking error · E50 EzSQ user trip 0 · E51 EzSQ user trip 1 · E52 EzSQ user trip 2 · E53 EzSQ user trip 3
INVT Goodrive20 (GD20)EF External fault
Yaskawa V1000dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (input terminal S1) · EF2 External Fault (input terminal S2) · EF3 External Fault (input terminal S3) · EF4 External Fault (input terminal S4)
Yaskawa A1000dWAL DriveWorksEZ Fault · dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (input terminal S1) · EF2 External Fault (input terminal S2) · EF3 External Fault (input terminal S3)
Yaskawa GA500dWF2 DriveWorksEZ Fault 2 · dWF3 DriveWorksEZ Fault 3 · dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (Terminal S1) · EF2 External Fault (Terminal S2)
Siemens MICROMASTER 420F0085 External fault
Siemens MICROMASTER 430F0085 External fault
Siemens SINAMICS G110F0085 External fault
INVT Goodrive200A (GD200A)EF External fault
Mitsubishi Electric FR-D700E.OHT External thermal relay operation · PS PU stop

07 / More codes

Other Altivar ATV320 codes

Source

Schneider Electric, Altivar Machine ATV320 Programming Manual, 04/2025, NVE41295.06, Diagnostics and Troubleshooting.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Schneider Electric and is not its authorised service partner.