F002 on the Allen-Bradley PowerFlex 525 is the “Auxiliary Input” fault. A fault stops the drive; it will not restart until the fault is cleared.
Something outside the drive told it to stop: a digital input or a control word bit set up as a fault input. The drive is reporting another device's trip.
- Code
- F002
- Type
- Fault (stops the drive)
- Drive
- Allen-Bradley PowerFlex 525, PowerFlex 523
- Kind of fault
- External fault
01 / Causes
What causes F002
Rockwell Automation's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing external fault faults explains where it usually comes from.
02 / Checks
What to check for F002
In the order Rockwell Automation gives them.
- 01Check the remote wiring.
- 02Check whether the communications programming raises this fault on purpose.
03 / Clearing it
How to clear F002
- Rockwell's parameter A551 [Fault Clear] resets a fault when set to 1 (Reset Fault); setting it to 2 (Clear Buffer) also clears the fault queue.
- Correct the cause first: F033 means the drive has already used up its automatic restart attempts on a fault that is still there.
Clear it once. If F002 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How external fault faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Find which input or control word is set as the external fault source in the drive's parameters.
- 02Trace that input to the device driving it (a thermal switch, pressure switch, PLC output or interlock) and find out why it tripped.
05 / Repair
When F002 means a repair
The fix is usually on the device that raised the input, not in the drive.
If F002 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Allen-Bradley drives, and they arrive knowing what to look for.
06 / Other drives
External fault: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F85 External fault |
| Siemens SINAMICS G120 | F07860 External fault 1 · F07861 External fault 2 · F07862 External fault 3 · A07850 External alarm 1 · A07851 External alarm 2 · A07852 External alarm 3 |
| Siemens MICROMASTER 440 | F0085 External fault |
| ABB ACS355 | F0014 EXT FAULT 1 · F0015 EXT FAULT 2 · F0030 FORCE TRIP · A2021 START ENABLE 1 MISSING · A2022 START ENABLE 2 MISSING |
| Delta VFD-E | EF External fault |
| Delta C2000 | LMIT Limit error · EF External fault · EF1 Emergency stop · bb External base block · ydc Y-connection / Δ-connection switch error · Brk External brake error |
| Hitachi WJ200 | E12 External trip · E36 Braking error · E50 EzSQ user trip 0 · E51 EzSQ user trip 1 · E52 EzSQ user trip 2 · E53 EzSQ user trip 3 |
| Schneider Electric Altivar ATV320 | BLF Brake control error · BRF Brake feedback error · EPF1 External error · EPF2 Fieldbus external detected error · FCF1 Output contactor closed error · FCF2 Output contactor opened error |
| INVT Goodrive20 (GD20) | EF External fault |
| Yaskawa V1000 | dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (input terminal S1) · EF2 External Fault (input terminal S2) · EF3 External Fault (input terminal S3) · EF4 External Fault (input terminal S4) |
| Yaskawa A1000 | dWAL DriveWorksEZ Fault · dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (input terminal S1) · EF2 External Fault (input terminal S2) · EF3 External Fault (input terminal S3) |
| Yaskawa GA500 | dWF2 DriveWorksEZ Fault 2 · dWF3 DriveWorksEZ Fault 3 · dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (Terminal S1) · EF2 External Fault (Terminal S2) |
| Siemens MICROMASTER 420 | F0085 External fault |
| Siemens MICROMASTER 430 | F0085 External fault |
| Siemens SINAMICS G110 | F0085 External fault |
| INVT Goodrive200A (GD200A) | EF External fault |
| Mitsubishi Electric FR-D700 | E.OHT External thermal relay operation · PS PU stop |
07 / More codes
Other PowerFlex 525 codes
Source
Rockwell Automation, PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start, November 2017, 520-QS001B-EN-E, Fault Codes.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Allen-Bradley and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007