MachineryFix

Siemens AC drive (VFD) · fault code

SINAMICS V20 F85: External fault

F85 on the Siemens SINAMICS V20 is the “External fault” fault. A fault stops the inverter's output; the motor will not run again until the fault is cleared.

Something outside the drive told it to stop: a digital input or a control word bit set up as a fault input. The drive is reporting another device's trip.

Code
F85
Type
Fault (stops the drive)
Drive
Siemens SINAMICS V20
Kind of fault
External fault

01 / Causes

What causes F85

  • An external fault was triggered through control word 2, bit 13.

02 / Checks

What to check for F85

In the order Siemens gives them.

  1. 01Check P2106.
  2. 02Disable control word 2 bit 13 as a command source if it should not trip the inverter.
  3. 03Disable the terminal input set up to trigger the fault.

03 / Clearing it

How to clear F85

  • Clear or acknowledge a fault from the BOP, or externally if the inverter is set up for it.
  • Holding the function key for more than two seconds shows the inverter's status at the moment of the fault.
  • Some faults (F64, F350) can only be cleared by switching the power off and on, and F5 cannot be cleared until the inverter's overload utilisation has fallen below its warning level.

Clear it once. If F85 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How external fault faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Find which input or control word is set as the external fault source in the drive's parameters.
  2. 02Trace that input to the device driving it (a thermal switch, pressure switch, PLC output or interlock) and find out why it tripped.

05 / Repair

When F85 means a repair

The fix is usually on the device that raised the input, not in the drive.

If F85 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

External fault: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F07860 External fault 1 · F07861 External fault 2 · F07862 External fault 3 · A07850 External alarm 1 · A07851 External alarm 2 · A07852 External alarm 3
Siemens MICROMASTER 440F0085 External fault
Allen-Bradley PowerFlex 525F002 Auxiliary Input · F094 Function Loss
ABB ACS355F0014 EXT FAULT 1 · F0015 EXT FAULT 2 · F0030 FORCE TRIP · A2021 START ENABLE 1 MISSING · A2022 START ENABLE 2 MISSING
Delta VFD-EEF External fault
Delta C2000LMIT Limit error · EF External fault · EF1 Emergency stop · bb External base block · ydc Y-connection / Δ-connection switch error · Brk External brake error
Hitachi WJ200E12 External trip · E36 Braking error · E50 EzSQ user trip 0 · E51 EzSQ user trip 1 · E52 EzSQ user trip 2 · E53 EzSQ user trip 3
Schneider Electric Altivar ATV320BLF Brake control error · BRF Brake feedback error · EPF1 External error · EPF2 Fieldbus external detected error · FCF1 Output contactor closed error · FCF2 Output contactor opened error
INVT Goodrive20 (GD20)EF External fault
Yaskawa V1000dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (input terminal S1) · EF2 External Fault (input terminal S2) · EF3 External Fault (input terminal S3) · EF4 External Fault (input terminal S4)
Yaskawa A1000dWAL DriveWorksEZ Fault · dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (input terminal S1) · EF2 External Fault (input terminal S2) · EF3 External Fault (input terminal S3)
Yaskawa GA500dWF2 DriveWorksEZ Fault 2 · dWF3 DriveWorksEZ Fault 3 · dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (Terminal S1) · EF2 External Fault (Terminal S2)
Siemens MICROMASTER 420F0085 External fault
Siemens MICROMASTER 430F0085 External fault
Siemens SINAMICS G110F0085 External fault
INVT Goodrive200A (GD200A)EF External fault
Mitsubishi Electric FR-D700E.OHT External thermal relay operation · PS PU stop

07 / More codes

Other SINAMICS V20 codes

Source

Siemens, SINAMICS V20 Inverter Operating Instructions, 01/2018, A5E34559884-009, Chapter 9, Faults and alarms.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007