FCF1 on the Schneider Electric Altivar ATV320 is the “Output contactor closed error” fault. A detected error stops the drive until it is cleared, in the way the manual gives for that code.
Something outside the drive told it to stop: a digital input or a control word bit set up as a fault input. The drive is reporting another device's trip.
- Code
- FCF1
- Type
- Fault (stops the drive)
- Drive
- Schneider Electric Altivar ATV320
- Kind of fault
- External fault
01 / Causes
What causes FCF1
- The output contactor stays closed although the conditions to open it are met.
02 / Checks
What to check for FCF1
In the order Schneider Electric gives them.
- 01Check the contactor and its wiring.
- 02Check the feedback circuit.
Also in the manual
- Clears only with a power reset, after the cause is removed.
03 / Clearing it
How to clear FCF1
- Remove the cause first. A resettable error can then be cleared by switching the drive off until the display goes out completely and back on, automatically by the Auto Fault Reset (ATR) function, through an input or control bit assigned to Fault reset (RST), or with the STOP/RESET key on the graphic display terminal when it is the active command channel.
- Some codes need a power reset (ANF, ASF, BLF, BRF, CRF1, EEF1, EEF2, FCF1, HDF, ILF, the INF codes, SAFF, SOF, SPF); ASF, BRF, SOF, SPF and TNF can also be cleared remotely with Fault Reset Assign (RSF).
- For an error that cannot be reset, Schneider's steps are: disconnect all power, including external control power; lock the disconnects open; wait 15 minutes for the DC bus capacitors to discharge; check the DC bus between PA/+ and PC/- is below 42 V DC; find and fix the cause; then restore power to confirm.
Clear it once. If FCF1 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How external fault faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Find which input or control word is set as the external fault source in the drive's parameters.
- 02Trace that input to the device driving it (a thermal switch, pressure switch, PLC output or interlock) and find out why it tripped.
05 / Repair
When FCF1 means a repair
The fix is usually on the device that raised the input, not in the drive.
If FCF1 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Schneider Electric drives, and they arrive knowing what to look for.
06 / Other drives
External fault: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F85 External fault |
| Siemens SINAMICS G120 | F07860 External fault 1 · F07861 External fault 2 · F07862 External fault 3 · A07850 External alarm 1 · A07851 External alarm 2 · A07852 External alarm 3 |
| Siemens MICROMASTER 440 | F0085 External fault |
| Allen-Bradley PowerFlex 525 | F002 Auxiliary Input · F094 Function Loss |
| ABB ACS355 | F0014 EXT FAULT 1 · F0015 EXT FAULT 2 · F0030 FORCE TRIP · A2021 START ENABLE 1 MISSING · A2022 START ENABLE 2 MISSING |
| Delta VFD-E | EF External fault |
| Delta C2000 | LMIT Limit error · EF External fault · EF1 Emergency stop · bb External base block · ydc Y-connection / Δ-connection switch error · Brk External brake error |
| Hitachi WJ200 | E12 External trip · E36 Braking error · E50 EzSQ user trip 0 · E51 EzSQ user trip 1 · E52 EzSQ user trip 2 · E53 EzSQ user trip 3 |
| INVT Goodrive20 (GD20) | EF External fault |
| Yaskawa V1000 | dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (input terminal S1) · EF2 External Fault (input terminal S2) · EF3 External Fault (input terminal S3) · EF4 External Fault (input terminal S4) |
| Yaskawa A1000 | dWAL DriveWorksEZ Fault · dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (input terminal S1) · EF2 External Fault (input terminal S2) · EF3 External Fault (input terminal S3) |
| Yaskawa GA500 | dWF2 DriveWorksEZ Fault 2 · dWF3 DriveWorksEZ Fault 3 · dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (Terminal S1) · EF2 External Fault (Terminal S2) |
| Siemens MICROMASTER 420 | F0085 External fault |
| Siemens MICROMASTER 430 | F0085 External fault |
| Siemens SINAMICS G110 | F0085 External fault |
| INVT Goodrive200A (GD200A) | EF External fault |
| Mitsubishi Electric FR-D700 | E.OHT External thermal relay operation · PS PU stop |
07 / More codes
Other Altivar ATV320 codes
Source
Schneider Electric, Altivar Machine ATV320 Programming Manual, 04/2025, NVE41295.06, Diagnostics and Troubleshooting.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Schneider Electric and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007