dEu on the INVT Goodrive20 (GD20) is the “Speed deviation fault” fault. A fault trips the drive and lights the TRIP indicator; the drive stays stopped until the fault is reset.
The drive could not get the motor to follow the commanded speed: it sat at its current limit for too long. The load is too heavy for the ramp, the motor is jammed, or the motor is connected or set up wrongly.
- Code
- dEu
- Type
- Fault (stops the drive)
- Drive
- INVT Goodrive20 (GD20)
- Kind of fault
- Motor stall
01 / Causes
What causes dEu
- The load is too heavy, or the motor stalled.
02 / Checks
What to check for dEu
In the order INVT gives them.
- 01Check the load is suitable, and increase the detection time.
- 02Check the control parameters are set properly.
Also in the manual
- Over communication this fault reads as type 34.
03 / Clearing it
How to clear dEu
- Remove the cause, then reset with the keypad's STOP/RST key, through a digital input, or by switching the power off and on. Once the fault is cleared the motor can be restarted.
- INVT's order of work: check the keypad is working; read the fault records in group P07 to see the drive's state when the fault happened; follow the table for that code; fix the cause; then reset and run.
Clear it once. If dEu comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How motor stall faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the load turns freely and nothing is jammed.
- 02Lengthen the acceleration time and check the current limit setting.
- 03Check motor connections (star or delta) against the rating plate and the drive's motor data.
05 / Repair
When dEu means a repair
A free-turning load, correct setup and repeated stalls point at a motor winding fault or a drive output problem.
If dEu keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on INVT drives, and they arrive knowing what to look for.
06 / Other drives
Motor stall: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F07900 Motor blocked · F07902 Motor stalled · A07903 Motor speed deviation |
| Siemens SINAMICS V90 | F7450 Standstill monitoring has responded · F7452 Following error too high · F7900 Motor blocked/speed controller at its limit |
| Siemens MICROMASTER 440 | F0453 Motor stalled |
| Allen-Bradley PowerFlex 525 | F006 Motor Stalled |
| ABB ACS355 | F0012 MOTOR STALL · A2012 MOTOR STALL |
| Delta C2000 | oSL Over slip error · SdRv Reverse direction of the speed feedback · SdOr Over speed rotation feedback · SdDe Large deviation of speed feedback · SfLK PMLess shaft lock |
| Delta ASDA-B2 | AL009 Excessive deviation of position command |
| Schneider Electric Altivar ATV320 | ANF Load slipping error · SSF Torque limitation error |
| Yaskawa V1000 | STo Motor Pull Out or Step Out Detection |
| Yaskawa A1000 | LSo LSo Fault · STo Pull-Out Detection |
| Yaskawa GA500 | LSo Low Speed Motor Step-Out · STPo Motor Step-Out Detected |
| Mitsubishi Electric FR-D700 | E.OLT Stall prevention stop |
| Danfoss VLT Micro Drive FC 51 | Warning 12 Torque limit |