MachineryFix

INVT AC drive (VFD) · fault code

Goodrive20 (GD20) OV2: Overvoltage during deceleration

OV2 on the INVT Goodrive20 (GD20) is the “Overvoltage during deceleration” fault. A fault trips the drive and lights the TRIP indicator; the drive stays stopped until the fault is reset.

The voltage on the drive's internal DC bus rose above its limit. Either the incoming supply is too high, or the motor is feeding energy back into the drive because the load is being slowed faster than friction alone would slow it, or an overhauling load is driving the motor.

Code
OV2
Type
Fault (stops the drive)
Drive
INVT Goodrive20 (GD20)
Kind of fault
DC bus overvoltage

01 / Causes

What causes OV2

  • The input voltage is abnormal.
  • Large energy fed back from the load.
  • No braking components.
  • Braking energy consumption is not switched on.

02 / Checks

What to check for OV2

In the order INVT gives them.

  1. 01Check the input power.
  2. 02Check whether the deceleration time is too short for the load, whether the VFD starts while the motor is still turning, or whether more energy-consuming (braking) components are needed.
  3. 03Install braking components.
  4. 04Check the related function code settings.

Also in the manual

  • Over communication this fault reads as type 8.

03 / Clearing it

How to clear OV2

  • Remove the cause, then reset with the keypad's STOP/RST key, through a digital input, or by switching the power off and on. Once the fault is cleared the motor can be restarted.
  • INVT's order of work: check the keypad is working; read the fault records in group P07 to see the drive's state when the fault happened; follow the table for that code; fix the cause; then reset and run.

Clear it once. If OV2 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How dc bus overvoltage faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Note when it trips. Overvoltage while stopping almost always means regenerated energy; overvoltage at standstill points at the supply.
  2. 02Measure the incoming supply between phases, at the drive terminals, during the time the trip happens.
  3. 03Compare the deceleration time with the inertia of the load: fans, flywheels and loaded conveyors need long ramps or a braking resistor.
  4. 04If a braking resistor is fitted, check its resistance and wiring and that the braking function is enabled in the drive.

05 / Repair

When OV2 means a repair

If the supply is normal, the ramp is long and the fault still appears, the braking chopper, the resistor or the drive's voltage measurement may have failed.

If OV2 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on INVT drives, and they arrive knowing what to look for.

06 / Other drives

DC bus overvoltage: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F2 Overvoltage · A502 Overvoltage limit · A910 Vdc_max controller deactivated · A911 Vdc_max controller active
Siemens SINAMICS G120F30002 DC-link voltage overvoltage · A07400 DC-link voltage maximum controller active · A30502 DC-link overvoltage
Siemens SINAMICS V90F7404 Upper DC link voltage threshold reached · F30002 DC link voltage, overvoltage
Siemens MICROMASTER 440F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active
Allen-Bradley PowerFlex 525F005 OverVoltage
ABB ACS355F0002 DC OVERVOLT · A2002 OVERVOLTAGE
Delta VFD-Eov Over-voltage
Delta C2000ovA Over-voltage during acceleration · ovd Over-voltage during deceleration · ovn Over-voltage at constant speed · ovS Over-voltage at stop
Delta ASDA-B2AL002 Over voltage
Hitachi WJ200E07 Over-voltage protection · E15 Input over-voltage
Schneider Electric Altivar ATV320OBF DC bus overvoltage error · OSF Supply mains overvoltage error
Yaskawa V1000ov Overvoltage
Yaskawa A1000ov Overvoltage
Yaskawa GA500ov Overvoltage
Siemens MICROMASTER 420F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active
Siemens MICROMASTER 430F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active
Siemens SINAMICS G110F0002 Overvoltage · A0502 Overvoltage limit · A0910 Vdc-max controller de-activated · A0911 Vdc-max controller active
INVT Goodrive200A (GD200A)OV1 Overvoltage during acceleration · OV2 Overvoltage during deceleration · OV3 Overvoltage during constant speed running
Mitsubishi Electric FR-D700E.OV1 Regenerative overvoltage trip during acceleration · E.OV2 Regenerative overvoltage trip during constant speed · E.OV3 Regenerative overvoltage trip during deceleration or stop · oL Stall prevention (overvoltage)
Danfoss VLT Micro Drive FC 51Alarm 7 DC overvoltage

07 / More codes

Other Goodrive20 (GD20) codes

Source

INVT, Goodrive20 Series VFD Manual, Version V2.1 (2025), Chapter 6, Fault tracking (6.2.3 VFD faults and solutions).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

OV2 won't clear? Get a technician who knows the Goodrive20 (GD20).

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.