SPO on the INVT Goodrive20 (GD20) is the “Phase loss on output side” fault. A fault trips the drive and lights the TRIP indicator; the drive stays stopped until the fault is reset.
The drive sees current in only two of the three motor phases. A phase is open somewhere between the drive and the motor winding.
- Code
- SPO
- Type
- Fault (stops the drive)
- Drive
- INVT Goodrive20 (GD20)
- Kind of fault
- Output phase loss
01 / Causes
What causes SPO
- A phase lost on the U, V, W output, or the motor's three phases are unbalanced.
02 / Checks
What to check for SPO
In the order INVT gives them.
- 01Check the output wiring.
- 02Check the motor and cable.
Also in the manual
- Over communication this fault reads as type 14.
03 / Clearing it
How to clear SPO
- Remove the cause, then reset with the keypad's STOP/RST key, through a digital input, or by switching the power off and on. Once the fault is cleared the motor can be restarted.
- INVT's order of work: check the keypad is working; read the fault records in group P07 to see the drive's state when the fault happened; follow the table for that code; fix the cause; then reset and run.
Clear it once. If SPO comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How output phase loss faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Isolate and check continuity of each phase from the drive terminals to the motor terminals.
- 02Inspect any contactor, isolator or junction box in the motor circuit.
- 03Measure winding resistance phase to phase at the motor.
05 / Repair
When SPO means a repair
When cable, connections and windings are all good, an output phase in the drive itself may be open.
If SPO keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on INVT drives, and they arrive knowing what to look for.
06 / Other drives
Output phase loss: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | A922 No load applied to inverter |
| Siemens SINAMICS G120 | F30015 Motor cable phase failure |
| Siemens SINAMICS V90 | F7410 Current controller output limited · F30015 Phase failure motor cable |
| Siemens MICROMASTER 440 | F0023 Output fault · F0422 No load applied to inverter · A0523 Output fault · A0922 No load at the inverter |
| Allen-Bradley PowerFlex 525 | F021 Output Ph Loss |
| ABB ACS355 | F0034 MOTOR PHASE |
| Delta C2000 | OPHL Output phase loss |
| Delta ASDA-B2 | AL031 Incorrect wiring of the motor power line U, V, W, GND |
| Schneider Electric Altivar ATV320 | OPF1 Single output phase loss error · OPF2 Output phase loss error |
| Yaskawa V1000 | LF Output Phase Loss · LF2 Output current imbalance |
| Yaskawa A1000 | LF Output Phase Loss · LF2 Output Current Imbalance · LF3 Power Unit Output Phase Loss 3 · UnbC Current Unbalance |
| Yaskawa GA500 | LF Output Phase Loss · LF2 Output Current Imbalance |
| Siemens MICROMASTER 430 | F0023 Output fault · A0523 Output fault |
| INVT Goodrive200A (GD200A) | SPO Phase loss on output side |
| Mitsubishi Electric FR-D700 | E.LF Output phase loss |
| Danfoss VLT Micro Drive FC 51 | Alarm 30 Motor phase U missing · Alarm 31 Motor phase V missing · Alarm 32 Motor phase W missing |
07 / More codes
Other Goodrive20 (GD20) codes
Source
INVT, Goodrive20 Series VFD Manual, Version V2.1 (2025), Chapter 6, Fault tracking (6.2.3 VFD faults and solutions).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007