Goodrive20 (GD20) ETH1: To-ground short-circuit fault 1

ETH1 on the INVT Goodrive20 (GD20) is the “To-ground short-circuit fault 1” fault. A fault trips the drive and lights the TRIP indicator; the drive stays stopped until the fault is reset.

The drive found current leaving the motor circuit through earth: the three output currents no longer add up to zero. The usual cause is damaged insulation in the motor cable, the motor terminal box or the winding, often where water, oil or vibration has reached it.

Code
ETH1
Type
Fault (stops the drive)
Drive
INVT Goodrive20 (GD20)
Kind of fault
Earth fault

01 / Causes

What causes ETH1

  • The VFD's output is short-circuited to ground.
  • A fault in the current detection circuit.
  • The motor power set differs greatly from the VFD's power.

02 / Checks

What to check for ETH1

In the order INVT gives them.

  1. 01Check the motor connection.
  2. 02Replace the Hall sensor.
  3. 03Replace the main control board.
  4. 04Set the correct motor parameters, and check the motor power parameters in group P2 match the motor actually used.

Also in the manual

  • Over communication this fault reads as type 32.

03 / Clearing it

How to clear ETH1

  • Remove the cause, then reset with the keypad's STOP/RST key, through a digital input, or by switching the power off and on. Once the fault is cleared the motor can be restarted.
  • INVT's order of work: check the keypad is working; read the fault records in group P07 to see the drive's state when the fault happened; follow the table for that code; fix the cause; then reset and run.

Clear it once. If ETH1 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How earth fault faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Isolate the supply, wait for the DC bus to discharge, and disconnect the motor cable at the drive.
  2. 02Insulation-test each phase of the cable and motor to earth with the drive disconnected (never megger through the drive).
  3. 03Split the circuit: test the cable alone, then the motor alone, to find which side is low.
  4. 04Open the motor terminal box and look for moisture, carbon tracking or a chafed lead.
  5. 05If cable and motor test healthy, check for long or unscreened motor cable and drive filter settings before suspecting the drive.

05 / Repair

When ETH1 means a repair

When the cable and motor test healthy and the fault returns with the motor disconnected, the drive's current sensing or output stage is suspect and the unit needs bench testing.

If ETH1 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on INVT drives, and they arrive knowing what to look for.

06 / Other drives

Earth fault: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F30021 Ground fault
Siemens SINAMICS V90F30021 Ground fault
Siemens MICROMASTER 440F0021 Ground fault
Allen-Bradley PowerFlex 525F013 Ground Fault · F038 Phase U to Gnd · F039 Phase V to Gnd · F040 Phase W to Gnd
ABB ACS355F0016 EARTH FAULT
Delta VFD-EGFF Ground fault
Delta C2000GFF Ground fault
Hitachi WJ200E14 Ground fault
Schneider Electric Altivar ATV320SCF3 Ground short circuit error
Yaskawa V1000GF Ground Fault
Yaskawa A1000GF Ground Fault
Yaskawa GA500GF Ground Fault
Siemens MICROMASTER 430F0021 Ground fault
INVT Goodrive200A (GD200A)ETH1 To-ground short-circuit fault 1 · ETH2 To-ground short-circuit fault 2
Mitsubishi Electric FR-D700E.GF Output side earth (ground) fault overcurrent at start
Danfoss VLT Micro Drive FC 51Alarm 14 Earth (ground) fault · Alarm 44 Earth fault 2

07 / More codes

Other Goodrive20 (GD20) codes

Source

INVT, Goodrive20 Series VFD Manual, Version V2.1 (2025), Chapter 6, Fault tracking (6.2.3 VFD faults and solutions).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

ETH1 won't clear? Get a technician who knows the Goodrive20 (GD20).

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.