ETH2 on the INVT Goodrive20 (GD20) is the “To-ground short-circuit fault 2” fault. A fault trips the drive and lights the TRIP indicator; the drive stays stopped until the fault is reset.
The drive found current leaving the motor circuit through earth: the three output currents no longer add up to zero. The usual cause is damaged insulation in the motor cable, the motor terminal box or the winding, often where water, oil or vibration has reached it.
- Code
- ETH2
- Type
- Fault (stops the drive)
- Drive
- INVT Goodrive20 (GD20)
- Kind of fault
- Earth fault
01 / Causes
What causes ETH2
- The VFD's output is short-circuited to ground.
- A fault in the current detection circuit.
- The motor power set differs greatly from the VFD's power.
02 / Checks
What to check for ETH2
In the order INVT gives them.
- 01Check the motor connection.
- 02Replace the Hall sensor.
- 03Replace the main control board.
- 04Set the correct motor parameters, and check the motor power parameters in group P2 match the motor actually used.
Also in the manual
- Over communication this fault reads as type 33.
03 / Clearing it
How to clear ETH2
- Remove the cause, then reset with the keypad's STOP/RST key, through a digital input, or by switching the power off and on. Once the fault is cleared the motor can be restarted.
- INVT's order of work: check the keypad is working; read the fault records in group P07 to see the drive's state when the fault happened; follow the table for that code; fix the cause; then reset and run.
Clear it once. If ETH2 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How earth fault faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Isolate the supply, wait for the DC bus to discharge, and disconnect the motor cable at the drive.
- 02Insulation-test each phase of the cable and motor to earth with the drive disconnected (never megger through the drive).
- 03Split the circuit: test the cable alone, then the motor alone, to find which side is low.
- 04Open the motor terminal box and look for moisture, carbon tracking or a chafed lead.
- 05If cable and motor test healthy, check for long or unscreened motor cable and drive filter settings before suspecting the drive.
05 / Repair
When ETH2 means a repair
When the cable and motor test healthy and the fault returns with the motor disconnected, the drive's current sensing or output stage is suspect and the unit needs bench testing.
If ETH2 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on INVT drives, and they arrive knowing what to look for.
06 / Other drives
Earth fault: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F30021 Ground fault |
| Siemens SINAMICS V90 | F30021 Ground fault |
| Siemens MICROMASTER 440 | F0021 Ground fault |
| Allen-Bradley PowerFlex 525 | F013 Ground Fault · F038 Phase U to Gnd · F039 Phase V to Gnd · F040 Phase W to Gnd |
| ABB ACS355 | F0016 EARTH FAULT |
| Delta VFD-E | GFF Ground fault |
| Delta C2000 | GFF Ground fault |
| Hitachi WJ200 | E14 Ground fault |
| Schneider Electric Altivar ATV320 | SCF3 Ground short circuit error |
| Yaskawa V1000 | GF Ground Fault |
| Yaskawa A1000 | GF Ground Fault |
| Yaskawa GA500 | GF Ground Fault |
| Siemens MICROMASTER 430 | F0021 Ground fault |
| INVT Goodrive200A (GD200A) | ETH1 To-ground short-circuit fault 1 · ETH2 To-ground short-circuit fault 2 |
| Mitsubishi Electric FR-D700 | E.GF Output side earth (ground) fault overcurrent at start |
| Danfoss VLT Micro Drive FC 51 | Alarm 14 Earth (ground) fault · Alarm 44 Earth fault 2 |
07 / More codes
Other Goodrive20 (GD20) codes
Source
INVT, Goodrive20 Series VFD Manual, Version V2.1 (2025), Chapter 6, Fault tracking (6.2.3 VFD faults and solutions).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007